The luminaire comes supplied with either an electrical tray or
a SnapDrive electrical module.
If unit is designated as multi-volt or multi-watt, follow specific
instruction below. Do not remove insulated connectors from wires
not needed for required voltage connection. When changing
voltage on reconnectable units, move only the lead with the
insulated connector.
IF SINGLE VOLTAGE:
All single voltage, tray mounted ballasts are pre-wired such
that user need only connect the supply conductors.
IF MULTIVOLT (120/208/240/277 volts):
Connect the tray mounted ballast lead with the insulated
terminal to the desired voltage terminal as indicated on the
ballast terminal nameplate.
IF MULTI-WATT
Tray mounted multi-watt ballasts are available in various
combinations of wattage. See wiring instructions on wiring tag
inside the luminaire.
The SnapDrive is equipped with a multi-volt ballast. Ballast
has been wired to the voltage indicated on the nameplate. Verify
that supply voltage is correct by comparing it to nameplate. If
another voltage is desired, place the voltage selection jumper onto
the appropriate voltage position as indicated on the wiring
diagram. Optional features such as fusing, switched quartz safety
lights and photocontrols are voltage specific. Do not change
jumper positions if fixture is equipped with these features.
This will damage or destroy these optional parts and will void
the safety listing (UL, CUL, CSA, etc.) of the fixture.
The SnapDrive is equipped with a multi-watt ballast. Ballast
and jumper have been configured as indicated on the nameplate.
If another wattage is desired, place the wattage selection jumper
onto the appropriate position as indicated on the wiring diagram.
Do not change the wattage jumper position if fixture is
equipped with fusing. Fuses have been sized to the wattage
that was ordered. Changing wattage may damage the fuses and
will void the safety listing (UL, CUL, CSA, etc.) of the fixture.
Replace power fuses only with fuses of the same type and ratings.
To complete installation refer to MOUNTING.
LAMP INSTALLATION
35-201578-137 (1/05)
For luminaires equipped with the adjustable slipfitter, install
luminaire on the 2-3/8” OD arm. Arm should be in contact with
“stop” located on the upper front surface of the slipfitter (see
Figure 5). The edges of both pipe clamps must be fully seated
on the arm.
Tighten rear bolts equally to bring leveling ball to center (if
so equipped) or until top housing is level. Tighten front bolts
equally to a torque of 5-12 foot-pounds. Tighten rear bolts to a
torque of 10-20 foot-pounds. Confirm torque using a crossing
pattern (see Figure 5)
B. WIRING
Make all electrical connections in accordance with all
applicable code requirements (National Electrical Code,
Canadian Electrical Code and applicable local Codes).
Verify that supply voltage is correct by comparing it to nameplate.
Supply wiring entering from pole to interior terminal board
must be routed through the wiring clips and maintain one-
half inch (1/2”) (113mm) minimum spacing to SnapDrive (see
Figure 6).
Connect ground lead to the green lead, green ground screw
on housing or terminal block provided.
Figure 3
Figure 4
SNAPDRIVE
HINGE
SNAPDRIVE
SPRING CLIP
SUPPLY WIRE
CLIP
Figure 6
Use only lamps specified on nameplate. Observe lamp manufacturer’s
recommendations and restrictions on lamp operation, particularly ballast
type, burning position, etc. Replace blackened lamps immediately.
Lamp Tightness-Mogul Base Lamp: The lamp should be securely
inserted to the NEMA-EEI specified torque of 35 inch-pounds (3.95 N•m),
which is best achieved by very firm tightening sufficient to fully
depress and load the center contact of the socket.
MAINTENANCE AND CLEANING
It will occasionally be necessary to clean the outside of the refractor
to maintain light levels. Frequency of cleaning will depend on ambient
dirt level and minimum light level which is acceptable to the user.
The refractor should be washed in a solution of warm water and any
mild, nonabrasive household detergent, rinsed with clean water and
wiped dry. Should the optical assembly become dirty on the inside,
wipe the reflector and clean the refractor in the above manner.
The light output of a luminaire is also dependent on the age of
the lamp. In applications where the light level is critical, it may be
desirable to replace lamps before they burn out. The lamp
manufacturer can provide data showing how the lamp light output
decreases with use.
BOLTS
PIPE CLAMPS
SET SCREWS
WARNING
Risk of burn
• Do not touch operating luminaire
CAUTION
Risk of burn
• Allow lamp/fixture to cool before
handling
Figure 5
g
GE Lighting Solutions is a subsidiary of the General Electric Company. Evolve and other trademarks belong to GE Lighting Solutions. The GE brand and logo are trademarks of the General Electric Company.
© 2011 GE Lighting Solutions. Information provided is subject to change without notice. All values are design or typical values when measured under laboratory conditions.