Allen-Bradley PowerFlex 6000 Firmware, Parameters, And Troubleshooting Manual

Type
Firmware, Parameters, And Troubleshooting Manual
PowerFlex 6000 Medium Voltage Variable Frequency Drive
Firmware, Parameters, and Troubleshooting Manual
Firmware Revision 6.xxx
Technical Data
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Labels may also be on or inside the equipment to provide specific precautions.
Allen-Bradley, Rockwell Automation, Rockwell Software, PowerFlex, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 3
Table of Contents
Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Preface
About this Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Acronyms and Abbreviations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1
Functional Descriptions
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Control Owner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
HMI Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Ramp. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Rated Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Stop Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Motor Direction Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Switch Frequency Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Trends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
VF Curve Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Digital Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Drive Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Pre-charge Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Cell Information Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Customized Trip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Over Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Line Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Voltage Sag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Low Voltage Ride Through (LVRT) . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Power Loss Auto Restart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Motor Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Current Limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Current Stability Loop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Flying Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Load Loss Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Motor Auto-tune. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Restart Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Skip Frequency Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Start and Stop Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Process Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Deceleration and Acceleration Process User Define . . . . . . . . . . . . . 39
PID Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
4 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Table of Contents
Deceleration Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Chapter 2
Parameter Descriptions
PowerFlex 6000 Medium Voltage AC Drive
Database Revision # 6.xxx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Interpreting Bit-Encoded Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Control Owner Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Nameplate Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Other Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
HMI Display Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Ramp Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Frequency Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Stop Mode Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Motor Direction Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Switch Frequency Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
VF Curve Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Analog Input Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Digital Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Analog Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Version Control Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Fan Control Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Pre-charge Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Customized Trip Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Over Speed Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Voltage Sag Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Voltage Loop Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Low Voltage Ride Through Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Power Loss Auto Restart Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Cell Bypass Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Bypass Mode Switch Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Fault Automatic Switch to Bypass Parameters. . . . . . . . . . . . . . . . . . . . . . 107
Current Limit Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Current Stability Loop Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Flying Start Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Load Loss Control Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Motor Auto-tune Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Restart Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Skip Frequency Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Start and Stop Sequence Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Deceleration and Acceleration Process Parameters . . . . . . . . . . . . . . . . . 128
PID Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Deceleration Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Protection Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Parameters Listed by Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Control Owner Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 5
Table of Contents
Nameplate Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Other Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
HMI Display Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Ramp Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Frequency Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Stop Mode Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
Motor Direction Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . 155
Switch Frequency Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . 155
VF Curve Setting Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156
Analog Input Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Digital Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Analog Output Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Version Control Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Fan Control Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Pre-charge Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Customized Trip Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Over Speed Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Voltage Sag Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Voltage Loop Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Low Voltage Ride Through Parameters. . . . . . . . . . . . . . . . . . . . . . . . 162
Power Loss Auto Restart Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Cell Bypass Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Bypass Mode Switch Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Fault Automatic Switch to Bypass Parameters. . . . . . . . . . . . . . . . . . 164
Current Limit Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Current Stability Loop Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Flying Start Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Load Loss Control Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Motor Auto-tune Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Restart Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
Skip Frequency Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Start and Stop Sequence Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Deceleration and Acceleration Parameters. . . . . . . . . . . . . . . . . . . . . 168
PID Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Deceleration Control Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Protection Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170
Parameters Listed by Linear Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
Alphabetical Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
Linear Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Chapter 3
Fault Messages
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Fault Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
System Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Logic Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204
Power Cell Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
6 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Table of Contents
Chapter 4
Warning Messages
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Warning Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
System Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Logic Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Power Cell Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 7
Preface
About this Publication
This manual provides details regarding functions, parameters and
troubleshooting information for medium voltage PowerFlex® 6000 drives.
Who Should Use This Manual
This manual is intended for qualified service personnel responsible for
troubleshooting and repairing medium voltage PowerFlex 6000 drives. You
should have previous experience with, and basic understanding of, electrical
terminology, procedures, required troubleshooting equipment, equipment
protection procedures and methods, and safety precautions.
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
You can view or download publications at
http:/www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
Acronyms and Abbreviations
Resource Description
PowerFlex 6000 Medium Voltage Variable
Frequency Drive Installation Manual,
publication 6000-IN006
Provides instructions for installing the drive, dimensions,
requirements, and wiring information.
PowerFlex 6000 Medium Voltage Variable
Frequency Drive Shipping and Handling
Manual, publication 6000-IN008
Provides instructions for shipping and handling a Medium Voltage
variable frequency drive and related equipment.
PowerFlex 6000 Medium Voltage Variable
Frequency Drive User Manual, publication
6000-UM002
Provides instructions for daily recurring drive usage, HMI interface and
maintenance tasks for the product’s end-user.
Acronym/
Abbreviation
Description Acronym/
Abbreviation
Description
A2D Analog to Digital FPGA Field-Programmable Gate Array
A/D Analog/Digital Freq Frequency
AC Alternating Current GND Ground
ACB Analog Control Board Gnrl General
Accel Acceleration HECS Hall Effect Current Sensor
ADC Analog to Digital Converter Hi High
Anlg Analog HP Horse Power
BW Bandwidth HW Hardware
Cap Capacitor I Current
Ch Channel IGDPS Isolated Gate Driver Power Supply
Chn Channel Init Initialize
8 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Preface
CIB Customer Interface Board Inv Inverter
CMC Common Mode Choke IO Input/Output
Cmd Command Isoltn Sw Isolation Switch
Conv Converter L Inductance
CT Current Transformer L Line
Ctctr Contactor LED Light-emitting diode
Cur Current Liq Liquid
DAC Digital to Analog Converter LR Line Reactor
DB Dynamic Braking Lo Low
DC Direct Current LV Low Voltage
DCB Drive Control Board M Machine
DCSL Drive Control and Synchronization Link Magntz Magnetizing
DD Dimensional Drawings Max Maximum
Decel Deceleration Min Minimum
DIM Drive Identity Module Mstr Master
Dly Delay MTR Motor
DO Drive Output NVRAM Non-Volatile Random Access Memory
DPI Drive Peripheral Interface OC Overcurrent
DPM Drive Processor Module OL Overload
DrvIn Drive Input OP Output
ED Electrical Drawings PF Power Factor
ESP Electric Submersible Pump PFC Power Factor Correction
Fbk Feedback PID Proportional, Integral, Derivative (process control)
Flt Fault PLC Programmable Logic Control
Fltr Filter Sync Synchronous
FO Fiber-Optic Tach Tachometer
FOB Fiber-Optic Interface Board
FOI Fiber-Optic Interface TFB Temperature Feedback Board
PWM Pulse-Width Modulation TFB3 Temperature Feedback Board, 3
rd
generation
Rect Rectifier Trp Trip
Rotn Rotation Trq Torque
SCB Signal Conditioning Board TSN Transient Suppression Network
SCR Silicon-Controlled Rectifier UB Unbalance
SGCT Symmetrical-Gate Commutated Thyristor UPS Uninterrupted Power Supply
Slv Slave USART Universal Synchronous/Asynchronous Transmitter/Receiver
Spd Speed V Volt
SPGD Self-Powered Gate Driver VSB Volt Sensing Board
SW Software Wrn Warning
OT Overtemperature Xfer Transfer
OV Overvoltage XIO External Input/Output
PD Parallel Drive
Acronym/
Abbreviation
Description Acronym/
Abbreviation
Description
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 9
Chapter 1
Functional Descriptions
Introduction
The PowerFlex 6000 is an adjustable speed AC drive that is particularly suitable
for new and retrofit centrifugal fan and pump applications. Air-cooled PowerFlex
6000 drives are designed to maximize energy efficiency by enabling soft-starting
and variable-speed control in medium voltage, normal duty applications.
To achieve the low input harmonics and near-unity power factor that make this
an ideal solution for standard motors, the drives utilize Cascaded “H’” Bridge
(CHB) topology. This proven CHB topology combines an integrally mounted
phase-shifting isolation transformer with series-connected power modules for
each phase. In addition to stepping down the input voltage, the isolation
transformer also provides two other principal functions:
Mitigate common mode voltage stress so motors with standard insulation
levels can be used.
Reduce Total Harmonic Distortion (THD), due to the phase shifting of
its secondary windings, so input side harmonics dont negatively impact
the plant or utility power grid.
System Settings
The system settings include the following functions:
Control Owner
on page 10
HMI Display on page 12
Nameplate on page 13
Ramp on page 14
Rated Frequency on page 15
Stop Mode on page 15
Motor Direction Control on page 16
Switch Frequency Settings on page 16
Tre n d s on page 17
VF Curve Setting on page 17
10 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 1 Functional Descriptions
Control Owner
This function is used to switch the control source between Local, DCS, and
Remote Box. The switch can be performed while the drive is online.
Three parameters are used to determine the control method and given frequency
reference. The value range of Owner #1 Selection (P475) is “0 or 1”, the value
range of Owner #2 Selection (P476) is “2...23”, and the value range of Owner #3
Selection (P477) is “18...23”. The default values for the parameters are “0, 8, and
23” respectively. The combinations are shown in the following table.
Table 1 - Frequency Reference and Control Command Source Matrix
The control command selections are:
1. Drive HMI or control panel buttons
2. Remote hardwired
3. Remote communications
4. Remote box buttons
The frequency reference selections are:
1. Local touchscreen
2. Potentiometer on the control panel
3. Remote control analog 4-20 mA
4. Remote communications
5. 4-speed governor
(Four frequency values are stored in parameters: 4-Step Variable Speed -
Speed1 (P480), 4-Step Variable Speed - Speed2 (P481), 4- Step Variable
Speed - Speed3 (P482), and 4-Step Variable Speed - Speed4 (P483))
6. Remote box buttons
Frequency Owner
Control Owner
HMI Comm /
Local Button
DCS I/O DCS Comm Remote Box
(Option)
HMI 061218
Potentiometer
0-10V (Option)
171319
Analog 4-20 mA 281420
Comm 391521
4-Speed 4 101622
Remote Box 5 111723
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 11
Functional Descriptions Chapter 1
Take note of the following:
When HMI is selected, the HMI converts the frequency reference to a
value from 0...100 and sends it to the controller. The controller converts
the received value to a unified data value from 0...10000 for internal
calculations within the controller and computes the given frequency to be
sent to the DSP.
When the potentiometer is selected, the 0-10V signal sent to the controller
is adjusted using the potentiometer. The controller processes the signal and
computes the given frequency to be sent to the DSP (If the wiring is
disconnected, the frequency reference value changes to zero and there will
be no message prompt).
When analog 4-20 mA is selected, the controller processes the signal and
computes the given frequency to be sent to the DSP.
When 4-speed governor is selected, the four frequency values stored in
parameters 4-Step Variable Speed - Speed1, 4-Step Variable Speed - Speed2,
4-Step Variable Speed - Speed3, and 4-Step Variable Speed - Speed4 are used.
These parameters correspond to the controller input points I-24, I-25, I-
26, and I-27.
When the controller receives an input at a high level from an input point
that corresponds to a frequency reference stored in one of the 4-Step
Variable Speed parameters, the drive frequency reference is set to that
value. For example, when the input I-24 is at a high level, the value of 4-
Step Variable Speed - Speed1 is read as the frequency reference of the drive
and so on.
When remote communication is selected, the frequency reference value is
provided by the remove communication with a range from 0...1000
(1000 = maximum frequency reference).
When there is a fault between the host computer and remote
communications, the drive response is determine by the value set in
parameter When Disconnected Between DCS and PLC (P485) and
described as follows:
P485= 0; The drive stops immediately.
P485 = 1; The drive continues running at current frequency.
P485 = 2; The drive continues running at frequency set in
4-step Variable peed - Speed1.
P485 = 3; The drive continues running at frequency set in
4-step Variable Speed - Speed2.
P485 = 4; The drive continues running at frequency set in
4-step Variable Speed - Speed3.
P485 = 5; The drive continues running at frequency set in
4-step Variable Speed - Speed4.
When Remote box is selected, the frequency reference is set by using the
acceleration/deceleration button on the HMI, or the acceleration/
deceleration button on the remote control box. The frequency step size is
determined by the value of Frequency Step For Acceleration Or Deceleration
(P493).
12 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 1 Functional Descriptions
Switching between Local, DCS, or Remote box can be performed on the HMI,
or using a selector switch mounted on the control panel. When Local/Remote
Owner Selection (P478) is set to “1”, the selector switch is used. When Local/
Remote Owner Selection is set to “0”, the HMI is used. When Local control
method is selected, Owner #1 Selection is active. When DCS control method is
selected, Owner #2 Selection is active. When Remote box control method is
selected, Owner #3 Selection is active.
HMI Display
This function is used to set the display parameters of some analog output signals
such as setting-frequency, actual-frequency, stator-voltage, and stator-current.
Each signal is made up of four display parameters, such as memory address, filter
parameter, HMI display integer part, and HMI display decimal part. See the
following table for the different display signals and their respective parameters.
Table 2 - Analog Output Signals and Corresponding Parameters
For example, if we want to output the “given frequency” with the settings –
memory address is 221, the filter time is 100 ms, the maximum integer part is 60,
and the maximum decimal part is 0 – then we can set the following:
Rated Frequency HMI Display Filter Time (P351) = 100
Rated Frequency HMI Display Integer Part (P352) = 60
Rated Frequency HMI Display Decimal Part (P353) =0
Rated Frequency HMI Display Address (P371) = 221
IMPORTANT
Remote box control method is only applicable to manual bypass, one-drive-
one-motor, and automatic bypass, one-drive-one-motor.
Analog Output Signals Parameters
Setting frequency display Rated Frequency HMI Display Filter Time (P351)
Rated Frequency HMI Display Integer Part (P352)
Rated Frequency HMI Display Decimal Part (P353)
Rated Frequency HMI Display Address (P371)
Stator voltage display Motor Voltage HMI Display Filter Time (P354)
Motor Voltage HMI Display Integer Part (P355)
Motor Voltage HMI Display Decimal Part (P356)
Motor Voltage HMI Display Address (P372)
Output frequency display Actual Frequency HMI Display Filter Time (P357)
Actual Frequency HMI Display Integer Part (P358)
Actual Frequency HMI Display Decimal Part (P359)
Actual Frequency HMI Display Address (P373)
Stator current display Motor Current HMI Display Filter Time (P360)
Motor Current HMI Display Integer Part P(361)
Motor Current HMI Display Decimal Part (P362)
Motor Current HMI Display Address (P374)
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 13
Functional Descriptions Chapter 1
The values of the four parameters Rated Frequency HMI Display Address (P371),
Motor Voltage HMI Display Address (P372), Actual Frequency HMI Display
Address (P373), and Motor Current HMI Display Address (P374) need not be
changed and can be left at their default values. The field support engineer can
change them according to the specific case.
Nameplate
This function is used to set the basic parameters of motor, drive, transformer, and
HECS. They are rated current, rated power, rated speed, rated power factor,
number of motor pole pairs, and so on.
Number of Power Cells Per Phase (P007) is the amount of power cells in one
phase.
For example, if the amount of power cells in one phase is five, then Number of
Power Cells Per Phase must be set to five. The number of power cell’s fault
information and warning information is based on Number of Power Cells Per
Phase. If Number of Power Cells Per Phase is set to zero, then all power cells fault
information and warning information is ignored. This allows the drive to be run
in low voltage. This function can be used for checking of low voltage components
and the control box.
Power Cell DC Bus Rated Voltage (P011) is the DC bus rated voltage of the
power cell. Motor Rated Current (P199) is used for the fault judgment related
motor current. The parameters Motor Rated Voltage (P012), Motor Rated Power
(P013), Motor Rated Speed (P014), Motor Rated Power Factor (P015), and
Number of Motor Pole Pairs (P017) are used for calculating the motor stator's
parameters.
Encoder Resolution (P019), Line CT Ratio (P195), and Line CT Burden Resistor
(P196). Motor HECS Ratio (P197) and Motor HECS Burden Resistor (P198) are
used to calculate the Hall current sensor's rated current, which is used for the
sampling of the drive's current (Line CT Ratio, Line CT Burden Resistor, Motor
HECS Ratio, and Motor HECS Burden Resistor are set based on the AT board
configuration).
IMPORTANT
The value of this parameter must be set to the actual amount used in each
phase.
14 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 1 Functional Descriptions
Ramp
This function includes the S curve setting, frequency dead zone setting, and
frequency amplitude limit.
The S curve setting means integral setting on frequency signal, also known as the
ramp setting. In PowerFlex 6000 drives, the curve is used to set the motors speed.
The ramp curve in S curve can avoid the over current and over voltage faults by
reducing the increasing or decreasing speed. Also, the rounded corners in S curve
can reduce the impact on mechanical components.
Deceleration-time “Td” is determined by the formula:
Deceleration Time (P399) * Deceleration Time Unit (P406)
This value should be adjusted according to the actual case. An
inappropriate setting will result in an input voltage over-voltage fault in the
power cell.
Deceleration-rounded-corner-time “Trd” is determined by the formula:
Deceleration Ramp Transition Time (P405) * Deceleration Time Unit
(P406)
In most cases, the default value need not be changed.
Acceleration-time “Tu” is determined by the formula:
Acceleration Time (P401) * Acceleration Time Unit (P403)
This value should be adjusted according to the actual case. An
inappropriate setting will result in an over-current fault.
Acceleration-rounded-corner-time “Tru” is determined by the formula:
Acceleration Ramp Transition Time (P402) * Acceleration Time Unit
(P403)
In most cases, the default value need not be changed.
Amplification Coefficient Of Error Terms (P409) is also used.
See the following diagram for the explanation of the different time settings.
Figure 1 - S Curve Diagram
Frequency
Tru
Tu
Td
Tru
Trd
Trd
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 15
Functional Descriptions Chapter 1
Rated Frequency
This function is used to the set the drive's rated frequency parameters and also
the frequency limit. Frequency dead zone setting is used to limit the low
frequency starting range, and prevent output fluctuations when the drive is in
analog input mode and the frequency is around zero Hz. Frequency amplitude
limit is used to limit the amplitude of set frequency, thus it prevents the set
frequency from exceeding the drive's maximum output frequency.
Parameter Rated Output Frequency (P460) is the drive’s rated output frequency.
The frequency value ranges from 0...75 Hz and should be set equal to the motor’s
rated frequency. If Rated Output Frequency is not set correctly it may cause
damage to the motor.
Parameter Maximum Output Frequency (P466) is the drive’s maximum output
frequency. Rated Output Frequency cannot be set higher than Maximum Output
Frequency. Any attempt to do so will fail.
If the original setting-frequency is lower than parameter Frequency Command
Deadband Upper Limit (P414), frequency dead zone setting can change the
setting- frequency to equal Frequency Command Deadband Upper Limit.
Frequency amplitude limit can limit the setting-frequency between parameters
Frequency Command Lower Limit (P413) and Frequency Command Upper Limit
(P415). Following the rule:
Frequency Command Upper Limit > Frequency Command Lower Limit > 0
This function is used to limit the amplitude for setting-frequency. This prevents
the setting-frequency from becoming bigger than the drive’s maximum output
frequency.
Stop Mode
There are two methods in which a PowerFlex 6000 drive can use to stop – ramp
down and coast stop.
The stop mode can be selected by setting Stop Method (P024) to “1” for coast
stop and “0” for ramp down.
If coast stop was selected, you must wait for a certain time to elapse before
restarting the drive. The time is determined by the formula:
Time = Motor Coast Stop Time (P253) * frequency before stop / max frequency
If ramp down was selected, the motor will ramp down.
Parameters Frequency Command-Low Frequency Region Boundary (P251) and
Delayed Lockout Time of Stop Operation (P270) are also used in this function.
16 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 1 Functional Descriptions
Motor Direction Control
This function is designed to work with other functions such as command source,
motor rotation direction, switch frequency, and frequency command source
selection.
The command source function is used to select the command source for starting,
stopping, and resetting the drive.
The motor rotation direction function is used to change the motor's rotating
direction without any hardware changing. There are two methods available in
PowerFlex 6000. The offline method is performed locally and cannot be done
when the motor is running. The online method is performed remotely and can be
done using the DCS while the motor is running.
When Motor Rotation Direction Command Selection (P009) is set to “0”, it means
offline local control, and the user can only change the motors rotating direction
using the HMI when the drive is stopped. DCS control is disabled. To change the
motor’s rotating direction, set parameter Motor Rotation Direction Under Local
Control (P008) to “0” for reverse rotating or “1” for forward rotating.
When Motor Rotation Direction Command Selection (P009) is set to “1”, it means
online remote control, and the user can change the motor’s rotating direction
using the DCS while the drive is running. HMI control is disabled.
Switch Frequency Settings
The switch frequency function is used to set the switch frequency of the power
semiconductor. The frequency command source selection function is used the
select the given frequency mode.
Set parameter Switch Frequency Setting Enable Code (P087) to “0” to disable or
“1” to enable the function.
Set parameter Switch Frequency Setting (P088) to “0” to set the switch frequency
at 600 Hz or “1” to set the switch frequency at 1200 Hz.
IMPORTANT
Set the Switch Frequency Setting Enable Code parameter back to zero after
changing the Switch Frequency Setting parameter. The Switch Frequency
Setting parameter can only be changed when offline.
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 17
Functional Descriptions Chapter 1
Trends
There are two kinds of dynamic trends available for PowerFlex 6000. The first
type of trend cannot be changed but can save history data. It can only show the
output voltage, output current and output frequency. The second type of trend
can be configured but cannot save the history data. It can show output frequency,
output voltage, motor estimated speed, output current, average DC voltage,
maximum DC voltage and minimum DC voltage by drawing curves of this status
data.
For the first type of trend, no configuration is required. For the second type of
trend, you can configure the parameter to display. Trends curves are showed by
the percentage value. For more details, see the PowerFlex 6000 Medium Voltage
Variable Frequency Drive User Manual(6000-UM002
).
VF Curve Setting
This function is designed to calculate the drive's output voltage according to the
set frequency. There are six kinds of V/F curves available – linear, curve, straight-
curve, parabolic-curve, 5 point VF, and SVC. Compensation voltage can be set to
improve the lower frequency start torque.
When a linear, curve, straight-curve, parabolic-curve, or SVC is selected, set the
parameters Low Speed Voltage Compensation (P451) and Low Speed Voltage
Compensation Frequency Threshold (P452). If the output frequency is lower than
the value of Low Speed Voltage Compensation Frequency Threshold, the output
voltage will be improved by the percentage value set in Low Speed Voltage
Compensation to enhance the output torque. If SVC is selected, the above
parameters need to be set based on the field conditions.
When VF curve is selected, the five points are defined based on their load curve.
These five points are Point 1 (f1, V1), Point 2 (f2, V2), Point 3 (f3, V3), Point 4
(f4, V4), and Point 5 (f5, V5).
The following parameters are used to define the five points:
f1 = Frequency At First Point For 5 Point VF (P375)
V1 = Amplitude At First Point For 5 Point VF (P376)
f2 = Frequency At Second Point For 5 Point VF (P377)
V2 = Amplitude At Second Point For 5 Point VF (P378)
f3 = Frequency At Third Point For 5 Point VF (P379)
V3 = Amplitude At Third Point For 5 Point VF (P380)
f4 = Frequency At Fourth Point For 5 Point VF (P381)
V4 = Amplitude At Fourth Point For 5 Point VF (P382)
f5 = Frequency At Fifth Point For 5 Point VF (P383)
V5 = Amplitude At Fifth Point For 5 Point VF (P384)
18 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 1 Functional Descriptions
The voltage value for each of the five points should be set as follows:
V1 < V2 < V3 < V4 < V5
The voltage and frequency values for each of the five points should be set as
follows:
V1 < f1; V2 < f2; V3 < f3; V4 < f4; V5 < f5.
The relationship between the five points is shown in the diagram below.
Figure 2 - 5 Point VF Diagram
Digital Output
This function is used to set the digital output channel parameters. There are eight
digital output channels available in PowerFlex 6000 drives. The address, polarity,
and output delay time parameters can be adjusted according to the users
requirements.
For example, a user wants to configure a warning bell that is controlled through
the digital channel. This warning bell will go off when the digital channel output
voltage reaches a high level. Follow these steps below to configure the settings for
this example:
1. Set the address of the “warning bell” with parameter Digital Output #5
Memory Address (P320). The default value is “99”.
2. Enable this function by setting parameter Digital Output #5 Bit Selection
(P322) to “5” because this function corresponds to the position of Bit 5 of
K99.
3. Set the polarity with parameter Digital Output #5 Logic (P321). If you
want a high voltage level, set the value to “0”, else set the value to “1”.
4. If a one second signal delay is needed, set Digital Output #5 Delay (P323)
to “1000 ms.
f1
V1
V2
V3
V4
V5
1
Voltage
Frequency
f2 f3 f4 f5 1
Rockwell Automation Publication 6000-TD004D-EN-P - November 2017 19
Functional Descriptions Chapter 1
Table 3 - Digital Output Signal Parameter Setting Group
Analog Output
This function is used to set the analog output channel. The analog signal can be
output into 0-5V voltage or 4-20 mA current. There are four analog output
channels available in PowerFlex 6000 drives – one for actual frequency variant,
one for stator current variant, and the rest are reserved.
The selected variant will undergo a Low-Pass Filter, Amplitude-correction, and
Amplitude-limitation process before the final result is output as a 0-5V and 4-20
mA analog signal. See the following diagram for the process.
Figure 3 - Analog Output Function Diagram
The actual frequency was filtered through the Low-Pass Filter with the filter time
set to one second, amplitude scaling factor to 50%, offset to zero, and the output
channel number is one.
Analog Output #1 Memory Address (P332) = 252
Analog Output #1 Filter Time (P333) = 1000 ms
Analog Output #1 Offset (P334) = 0
Analog Output #1 Scaling Factor (P335) = 50.00%
Hardwired I/O Interface Description Related Parameters
I/O0 High voltage can be closed P300, P301, P302, P303
I/O1 System running P304, P305, P306, P307
I/O2 System fault P308, P309, P310, P311
I/O3 System trip P312, P313, P314, P315
I/O4 Warning P316, P317, P318, P319
I/O5 Warning bell P320, P321, P322, P323
I/O6 Customized trip P324, P325, P326, P327
I/O7 Pre-charge complete P328, P329, P330, P331
Low-pass Filter
Y = x / (P333 * s + 1)
Linear Transformation
Y = P335 * (x +P334)
Limit Amplitude
Digital/Analog
Transformation
0-5V
4-20 mA
20 Rockwell Automation Publication 6000-TD004D-EN-P - November 2017
Chapter 1 Functional Descriptions
Table 4 - Analog Output Display Parameter Setting Group
Drive Configuration
The drive configuration include the following functions:
Fan Control
on page 20
Pre-charge Control on page 23
Customized Trip on page 25
Over Speed on page 26
Fan Control
This function is used to manage heat dissipation in the transformer cabinet, filter
cabinet, and power module cabinet when the drive is running. If the additional
heat generated is not dissipated in time, the drive will trip, or the transformer,
power module, or filter device may be damaged. There are three fan control
modes – non-redundant fan, one fan as redundant fan, all fans work in cycle
mode. Configuring a redundant fan can help to improve reliability of the drive
and reduce downtime.
Table 5 - PLC I/O and K Register Definition
Analog Output Data Storage Parameters Hardwired I/O
Interface (current)
Hardwired I/O
Interface (voltage)
Actual frequency K252 P332, P333,
P334, P335
IoutA equals P11.5
Signal ground equals P11.1
UoutA equals P10.5
Signal ground equals P10.1
System current K206 P336, P337,
P338, P339
IoutB equals P11.6
Signal ground equals P11.2
UoutB equals P10.6
Signal ground equals P10.2
Channel 3 Reserved P340, P341,
P342, P343
IoutC equals P11.7
Signal ground equals P11.3
UoutC equals P10.7
Signal ground equals P10.3
Channel 4 Reserved P344, P345,
P346, P347
IoutD equals P11.8
Signal ground equals P11.4
UoutD equals P10.8
Signal ground equals P10.4
Fan Control I/O Assign
TX Cabinet Fan Control Power Cabinet Filter Cabinet
PLC Module PLC8 PLC9
Fan CMD I/O O-8 O-9 O-10 O-11 O-12 O-13 O-14 O-15 O-0 O-1 O-2 O-3 O-4 O-5 O-6 O-7 O-8 O-9 O-10 O-11 O-12
Register Mapping K201...K202 K203 K204
PLC Module PLC7
Fan Fdb I/O I-1 I-2 I-3 I-4 I-5 I-6 I-7 I-8 I-9 I-10 I-11 I-12 I-13 I-14 I-15 I-16 I-17 I-18 I-19 I-20 I-21
Register Mapping K66 and K67 K68 K69
Fan Type Definition TX1 Main Cooling Fan I/O TX2 Main Cooling Fan I/O R-Fan
I/O
Main
Cooling
Fan
R-Fan
I/O
R-Fan
I/O
R-Fan
I/O
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214

Allen-Bradley PowerFlex 6000 Firmware, Parameters, And Troubleshooting Manual

Type
Firmware, Parameters, And Troubleshooting Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI