Custom Performance Climate
Changer PSCA AHUs
Outstanding performance and the exibility
to t any building space requirement
Performance Climate Changer® air handling units (AHUs)
deliver energy eciency, superior performance and one of the
lowest installed costs in the industry. The PSCA model utilizes
a common platform for both indoor and outdoor units. It is
highly customizable due to dimensional, casing and component
exibility; oers numerous integrated controls options; and
delivers proven performance.
Custom Flexibility
Performance Climate Changer PSCA AHUs are among the
most versatile air handler solutions on the market, giving you
the exibility to meet tight mechanical space constraints or
critical application needs. Casing options include 3-inch R-19
foam-injected wall panels and premium doors; and variable
length sections meet desired performance, conguration and
service needs. Component options oer further opportunities
for customization. These include door options, direct-drive fan
arrays, motorized impellers and many others.
Performance
With robust casing construction, component redundancy and
smart controls, the Performance Climate Changer PSCA AHUs
provide an ecient solution in the air handler market. Robust
casing construction results in low panel deection. And the
casing, including the unit base, has no-thru-metal with mid-span
thermal break panel construction. Our industry-low leakage
rates meet ASHRAE® 111 Class 6 for leakage — your assurance
that energy will not be wasted and conditioned air will be
delivered to the intended space.
Trane Select Assist
To make your ordering process
easier than ever, Trane
Performance Climate Changer
PSCA is now available through
Mobile TOPSS®. Our web-
based selection software
delivers signicant speed
improvement in time to get a
PSCA unit layout. The updated
process has an integrated
sizing screen to get the most
cost-eective aspect ratio based on job requirements.
Enhanced outputs and reports are intuitive and easy
to read. The new Mobile TOPSS program improves
eciency and accuracy in your selection process.
Trane Performance Climate Changer Air Handler
Unit Overview - AHU-1
Application Calculated Unit
Size
External Dimensions Weight
Height Width Length Installed Rigging
Outdoor unit 72 100.330 150.000 621.949 28130.2 lb 26448.7 lb
Quantity of Shipping Sections Largest Ship Split Heaviest Ship Split Elevation
Height Width Length
7 pieces 100.330 in 150.000 in 105.899 in 6071.3 lb 0.00 ft
Supply Fan
Airflow 35000 cfm Total Static Pressure 7.383 in H2O
Return/Exhaust Fan
Airflow 35000 cfm Total Static Pressure 3.324 in H2O
Note: The unit's height includes the outdoor roof.
Construction Features
Panel 3" Casing Foam injected
R-19 with thermal break
Panel Material All unit inner panels -
galvanized
Integral Base
Frame 7.25 in. integral base frame
Paint Slate gray
Factory
Leakage/Deflection
Testing
Test report only leakage &
deflection
Agency Approval YES
Unit Electrical
Circuit Voltage/Phase/Frequency FLA MCA Fuse Size
Circuit number 1 Single point power 460/3/60 165.30 A 172.05 A 175.00 A
Circuit number 2 UV lights 1 115/1/60 6.16 A 7.70 A 15.00 A
Circuit number 3 Receptacle 115/1/60 8.00 A 10.00 A 15.00 A
Unit Controls
Factory Controls Package Variable volume
Controller Type UC600
Controller mounting Unit mounted
Controller location Left
PPS Configuration Addl field prog rqd, closest PPS AH0300
Warranty
Warranty section Std. warranty only
VFD only - Position: 1
Return Fan Motor Interface Door Ret/Exh high volt. door - right
Blank (0 to 14in) - Position: 2
Section Options
Section Length 10.000
2017-12-04 15:26:36Z Page1 of 5
Product Version: 1