Pre-Repair Information
2.1 General
Both single conductor and dual conductor copper
sheath and Alloy 825 sheath cables can be field
repaired or modified. The field repair kits can be
used to complete the following:
• To repair or replace a joint in the heated section
(hot-hot joint)
• To repair or replace a joint between the heated
section and the non-heating cold lead section (hot-
cold joint)
• To repair or replace the end cap for Design D
cables
Brass joints and end caps are used to repair or
modify heating cables with a copper sheath heated
section and copper sheath cold lead section and
are suitable for exposure temperatures up to 392°F
(200°C).
Stainless steel joints and end caps are used to repair
or modify heating cables with an Alloy 825 sheath
heated section and Alloy 825 sheath cold lead
section and are suitable for exposure temperatures
up to 1022°F (550°C). They are also used to repair
or modify heating cables with an Alloy 825 sheath
heated section and copper sheath cold lead section
for exposure temperatures up to 482°F (250°C).
Note: If the attempted repair cannot be done
successfully, please contact nVent for assistance.
2.2 Safety Precautions
• Safety glasses and gloves must be worn when
making field repair joints
• Take care to avoid burns when handling welding
torches and hot work pieces
• Wear a welding apron when working with welding
torches
• Follow all safety instructions supplied with the
equipment you are using
• Disconnect all power before repairing or modifying
the heating cable
CAUTION: When drying out cable, care
must be taken not to trap moisture as this could
cause the cable to burst, possibly causing injury.