Important Safeguards and Warnings
WARNING: FIRE AND SHOCK HAZARD.
nVent RAYCHEM Surface Snow Melting Systems must
be installed correctly to ensure proper operation and to
prevent shock and fire. Read these important warnings
and carefully follow all the installation instructions.
To avoid damage to the heating cables, do not energize
cables until they have been completely embedded and
the installation has been completed.
To minimize the danger of fire from sustained electrical
arcing if the heating cable is damaged or improperly
installed, and to comply with the requirements of nVent,
agency certifications, and national electrical codes,
groundfault equipment protection must be used on each
heating cable branch circuit. Arcing may not be stopped
by conventional circuit protection.
Heating cables must be spaced at least 1/2 in (1.3cm)
from any combustible surface.
Approvals and performance of the Surface Snow Melting
Systems are based on the use of approved components
and accessories.
Cable terminations must be kept dry before, during, and
after installation.
Damaged heating cable can cause electrical arcing or
fire. Damaged heating cable or terminations must be
repaired or replaced. Contact factory for assistance.
If the heating cable sheath is stainless steel, the
cable must be grounded, but must not be used as the
grounding means.
Reinforcing rod, mesh or other materials used for the
support of, or on which the heating cables are installed,
must be grounded in accordance with CSA Standard
C22.1, Section 10 or the National Electrical Code as
applicable.
Megohmmeters operate at high voltage. This voltage
is hazardous and possibly lethal. Read and follow all
instructions included with the instrument you are using.
nVent.com | iii
Table of Contents
1
General Information 1
1.1 Use of the Manual 1
1.2 MI Applications 2
1.3 Safety Guidelines 2
1.4 Electrical Codes 2
1.5 Approvals 2
1.6 Warranty 3
1.7 Heating Cable Construction 3
1.8 Heating Cable Identification 4
1.9 Heating Cable Catalog Number Decoder 6
2
General Installation Guidelines 7
2.1 Before You Start 7
2.2 Materials Specifications 8
2.3 Heating Cable Storage 8
2.4 Tools Required 8
2.5 Cable Testing Guidelines 8
2.6 Heating Cable Handling 9
2.7 Junction Boxes and Electrical Enclosures 11
2.8 Protecting the Heating Cable 11
2.9 Check Materials Received 11
2.10 Review the Design 12
2.11 Slab Temperature Sensor 18
2.12 Waterproofing Membranes 19
2.13 Drainage and Trench Drains 20
2.14 Visual Inspection 20
3
Heating Cable Installation 22
3.1 Heating Cables Installed in Concrete 22
3.2 Heating Cables Installed in Asphalt 31
3.3 Heating Cables Installed in Mastic Asphalt 35
3.4 Heating Cables Installed Under Brick
and Concrete Pavers 40
3.5 Concrete and Asphalt Wheel Tracks 44
3.6 Concrete Stairs 46
4
Accessory Installation 51
4.1 Junction Boxes 51
4.2 Slab Thermostat Installation 61
iv | nVent.com
5
Control, Monitoring and Power Distribution 63
5.1 Manual On/Off Control 63
5.2 Slab Sensing Thermostat 63
5.3 Automatic Snow Controller 63
6
Power Supply and Electrical Protection 65
6.1 Voltage Rating 65
6.2 Circuit Breaker Sizing 65
6.3 Ground-Fault Protection 66
6.4 Junction Box Wiring 68
6.5 Typical Wiring Diagrams 68
7
Commissioning and Preventive Maintenance 76
7.1 System Tests 76
7.2 Preventive Maintenance 77
8
Test Procedures 79
8.1 Visual Inspection 79
8.2 Insulation Resistance Test – Test 1 79
8.3 Continuity (Resistance) Test – Test 2 80
8.4 Insulation Resistance and Continuity
Test Procedure 80
8.5 Power Check 82
8.6 Fault Location Testing 85
9
Troubleshooting Guide 86
10
Installation and Inspection Records 90
1
General Information
nVent.com | 1
1.1 Use of the Manual
This manual covers the installation of nVent
RAYCHEM Mineral Insulated (MI) heating cables for
surface snow melting in concrete, asphalt, and sand
or limestone screenings under paving stones*.
The manual covers general heating cable installation
procedures and specific installation details and
provides information on available accessories.
The manual also provides information on controls,
testing, and periodic maintenance.
This manual assumes that a proper snow melting
or anti-icing design has been completed according
to nVent's recommendations. Only the applications
described in this manual are approved by nVent for
nVent RAYCHEM MI Surface Snow Melting Systems
and only when used with approved accessories.
The instructions in this manual and the installation
instructions included with the control systems,
power distribution systems, and accessories must
be followed for the nVent warranty to apply.
For design assistance, technical support, or
information regarding other applications not shown
here, please contact your nVent representative or
nVent directly.
nVent
7433 Harwin Drive
Houston, TX 77036
USA
Tel +1.800.545.6258
Fax +1.800.527.5703
nVent.com
Important: For the nVent warranty and agency
approvals to apply, the instructions that are included in
this manual and product packages must be followed.
* Special permission for paver snow melting is
required from the Authority Having Jurisdiction.
1
General Information
2 | nVent.com
1.2 MI Applications
Surface Snow Melting
Surface Snow Melting Systems prevent the
accumulation of snow on ramps, slabs, driveways,
sidewalks, platform scales, and stairs under typical
snow conditions.
Anti-Icing
Anti-icing systems keep the surface temperature
above freezing to prevent ice formation.
1.3 Safety Guidelines
As with any electrical equipment, the safety and
reliability of any system depends on the quality
of the products selected and the manner in which
they are installed and maintained. Incorrect design,
handling, installation, or maintenance of any of the
system components could damage the Surface
Snow Melting System and may result in inadequate
snow melting, electric shock, or fire. To minimize
these risks and to ensure that the system performs
reliably, read and carefully follow the information,
warnings, and instructions in this guide.
Pay special attention to the following:
Important instructions are marked Important
Warnings are marked WARNING
1.4 Electrical Codes
Article 426 of the National Electrical Code (NEC) and
Section 62 of the Canadian Electrical Code (CEC)
govern the installation of fixed outdoor surface
snow melting and de-icing systems. All installations
must be in compliance with these and any other
applicable national and local codes.
1.5 Approvals
MI heating cables are approved for use in
nonhazardous and hazardous locations.
1
General Information
nVent.com | 3
For a complete list of approvals, refer to the product
data sheets available on our web site at
nVent.com or contact your nVent representative.
H57796 – MI Heating Cable for Surface Snow
Melting – MI data sheet
H56990 – MI Heating Cable for Commercial
Applications data sheet
Important: Types SUA and SUB heating cables are
approved for use in nonhazardous areas only.
1.6 Warranty
nVent’s standard limited warranty applies to Surface
Snow Melting Systems.
An extension of the limited warranty period to ten
(10) years from the date of installation is available,
except for the control and distribution systems,
if a properly completed online warranty form is
submitted within thirty (30) days from the date of
installation. You can access the complete warranty
on our web site at nVent.com
1.7 Heating Cable Construction
The MI heating cables are comprised of one or
two conductors surrounded by magnesium oxide
insulation and a solid copper or Alloy 825 sheath.
nVent RAYCHEM Copper sheath cables are covered
with an extruded low-smoke zero-halogen (LSZH)
jacket that protects the copper sheath from
corrosive elements that can exist in surface
snow melting applications. All of the cables
include both a heated section (heated length) and
a nonheating cold lead section. These sections
are joined at the hot/cold joint where the heating
element is spliced into larger bus wires. A final
transition at the end of the cold lead section
provides an environmental seal and tails for the
electrical connection. The heating cables are
available as factory-terminated configurations
shown in Table 1.
1
General Information
4 | nVent.com
TABLE 1:
MI HEATING CABLE CONFIGURATIONS
MI cable
design
Number of
conductors
Configuration
Heated length
Heated length
Cold lead length
Cold lead length
Cold lead length
NPT threaded
connector
Hot/cold
joint
NPT threaded
connector
Hot/cold
joint
Heated length
Cold lead length
NPT threaded
connector
Hot/cold
joint
A Single
conductor
(61 series)
B Single
conductor
(61 series)
D Dual
conductor
(32 & 62
series)
(SUA)
(SUB)
1.8 Heating Cable Identification
Each MI heating cable is supplied with an
identification tag on which the heating cable catalog
number is permanently printed. In addition to its
identification purposes, the catalog number provides
information regarding the heating cable length,
power output, and operating voltage. Also printed on
the tag are the serial number and temperature code.
If the cable has been designed for a hazardous
location, the area classification is printed in the
“Haz. Locations” section of the tag (for custom
engineered cables only).
Important: If the metal tag is removed during cold
lead installation, it must be reinstalled on the cold lead
within 3 in (7.5 cm) of the end of the cold lead/power
connections.
Figure 1 shows a typical identification tag supplied
with pre-engineered SUA/SUB heating cables
(SUA1 through SUB22). These heating cables
are designed to be used for several different
applications depending on the supply voltage
selected. In Figure 2, a typical identification tag
supplied with custom engineered heating cables
is shown.
1
General Information
nVent.com | 5
Figure 1: Typical SUA/SUB MI heating cable identifica-
tion tag (front)
Important: Several SUA and SUB series of heating
cables are designed for use on either 208, 240, or 277
volts when used in surface snow melting applications.
For these cables, the catalog number printed on the tag
will show only the highest voltage to which the cable
may be connected, and the highest wattage produced.
The wattages produced at other supply voltages are
shown in the area below the catalog number and
across from the “SNOW MELTING / PS,C” heading
(see Figure 1).
Figure 2: Typical custom engineered heating cable
identification tag (front)
1
General Information
6 | nVent.com
1.9 Heating Cable Catalog Number Decoder
The heating cable catalog number may be broken
out as follows:
Gland size
(N12 = 1/2 in NPT)
Cold joint ‘Y’ is standard
for copper sheath heating
cables
Cold joint ‘X’ is standard
for Alloy 825 sheath
heating cables
Cold lead code
Cold lead length (in feet)
(4.6M = 4.6 meters)
Heating cable voltage
Heating cable wattage
Heated cable length
(in feet)
(97.6M = 97.6 meters)
Heating cable reference
Heating cable design
configuration (A, B, D)
B/61RE4300-RD/320/8000/277/15/R30A/Y/N12
Figure 3: MI heating cable catalog number
2
General Installation Guidelines
nVent.com | 7
The guidelines in Section 2 are provided to assist
the installer throughout the installation process and
should be reviewed before the installation begins.
2.1 Before You Start
The Surface Snow Melting System is an engineered
system that has been designed for your application.
To ensure a smooth, efficient installation and start-
up, obtain all the relevant engineering information
before commencing work. Contact the general
contractor, owner, or owner’s representative to
obtain a statement of the project design basis,
project specifications, and the heating cable layout
drawings.
It is important that the heating cable depth and
spacing be maintained for proper operation of
the system for all concrete, asphalt and paver
installations. For sloping ramps, such as a ramp
to an underground parking garage, serpentine the
cables across the width of the ramp to improve
snow melting effectiveness.
To ensure that the installation proceeds smoothly
and meets the design objectives, the following
questions should be answered.
What are the exact dimensions of the area to be
heated?
What is the supply voltage and phase?
Are the heating cables being installed in concrete
or asphalt, or if paver area, in limestone screenings
or sand?
Where are the control joints, expansion joints, and
construction joints located?
What is the heating cable spacing?
Is a waterproof membrane being used?
What is the depth of burial of the heating cable?
Where are the junction boxes located?
Is there adequate drainage for melted snow and ice?
Important: Fuel storage areas and aircraft
hangar doors are classified as hazardous areas.
Heating cables installed in these areas must be
approved for the area classification.
2
General Installation Guidelines
8 | nVent.com
2.2 Materials Specifications
Install the heating cables in concrete, asphalt, or
other materials that have been designed to handle
the expected load and environmental conditions, and
for long term structural stability. The quality of the
granular base materials, concrete, and asphalt must
conform to generally accepted standards and
specifications set by the American Society for
Testing and Materials (ASTM) and/or Canadian
Standards Association (CSA). Site preparation
and material selection should be done under the
direction of the Soil Consultant, Engineer, Architect,
or Landscape Architect.
2.3 Heating Cable Storage
Store heating cables in a clean, dry location and
protect from mechanical damage. Temperature
range: –40°F to 140°F (–40°C to 60°C).
Store heating cables in their shipping container
until ready to install.
2.4 Tools Required
The following tools are recommended for installing
MI heating cables:
Pliers
1000 Vdc megohmmeter
Multimeter
Large adjustable wrench
Torque wrench
Pay-off reel (to uncoil long cables)
2.5 Cable Testing Guidelines
Insulation resistance (IR) testing is recommended
at four stages during the installation process and
as part of regularly scheduled maintenance. Further
details on IR testing can be found in Section 8.
When received – minimum 100
After the cables have been installed – minimum
20 MΩ
Continuously during placement of concrete,
asphalt, etc. minimum 20
2
General Installation Guidelines
nVent.com | 9
Prior to initial start-up (commissioning) –
minimum 20
As part of the regular system inspection
After any maintenance or repair work
2.6 Heating Cable Handling
Avoid damage to the MI heating cable as follows:
Important: Do not energize the heating cables
before they have been completely embedded and the
installation has been completed.
Use a pay-off reel to uncoil heating cable
during installation; do not pull cable out into a spi-
ral (Figure 4).
Right Wrong
Figure 4: Unreeling/uncoiling cable
Do not alter cable length.
Avoid damaging heating cables by cutting or crush-
ing (Figure 5).
Figure 5: Avoid cutting and crushing the heating cable
Do not install cables if the temperature is below
–4°F (–0°C) for UL, and –2°F (–0°C) for CSA.
Important: Do not install so that heating cables
are crossed, overlapped, or grouped (Figure 6).
Grouped heating cables can cause localized
overheating with a risk of fire or cable failure.
2
General Installation Guidelines
10 | nVent.com
Figure 6: Figure 6: Do not cross, overlap, or group heat-
ing cables
Do not repeatedly bend and straighten the cable.
Do not install heating cable in contact with
insulating materials.
Install heating cable at the recommended spacing
to ensure correct watt density.
Use a plank to tip wheelbarrow on.
Handle the hot/cold joint carefully. Support the
joint on both sides when moving and positioning
the cold lead.
Position hot/cold joints 6 in (15 cm) in from edge
of snow melted area and spaced at least 6 in (15
cm) apart from each other (do not bunch hot/cold
joints – see Figure 7).
Wrong
hot/cold joints
installed on
slab edge
Wrong
hot/cold joints
bunched
Right
hot/cold joints
6 in (15 cm) apart
and 6 in (15 cm)
from slab edge
Figure 7: Positioning hot/cold joints
During installation, protect tails from breaking
where they emerge from brass pot by taping over
tails and pot with electrical tape.
Do not bend the heating cable or cold lead within
6 in (15 cm) of a splice, the hot/cold joint, or the
end cap.
Do not bend cable to an inside radius less than
6times the outside diameter of the cable.
Do not space runs of heating cable closer than
3in (7.5 cm) together.
2
General Installation Guidelines
nVent.com | 11
Do not use sharp objects such as shovels, rakes,
etc. when installing the cable (Figure 8).
Figure 8: Avoid damage by not using shovels or rakes
2.7 Junction Boxes and Electrical Enclosures
Junction boxes and enclosures used for electrical
connections to the heating cables must be listed
and approved for the environment in which they are
installed.
Junction boxes should be mounted indoors or
above grade when possible. For electrical connec-
tions made outdoors at grade level, use a handhole
type grade mounted enclosure.
Keep covers on junction boxes to prevent moisture
from entering them.
2.8 Protecting the Heating Cable
On many projects, there is a delay between
installation of the heating cables and placement
of the topping course (concrete, asphalt, limestone
screenings/sand). If there is any delay at all, take the
following precautions to protect the installation until
the heating cables can be completely covered.
Do not energize the heating cables
Mechanically protect the heating cables so that
they cannot be damaged by being walked on, run
over, painted, sandblasted, burned, welded, or cut.
2.9 Check Materials Received
Review the project specifications, drawings, and
schedules and compare the list of materials to the
catalog numbers of heating cables and components
received to confirm that proper materials are on site.
The heating cable catalog number, voltage, wattage,
and length are printed on the metal tag attached to
the cold lead.
2
General Installation Guidelines
12 | nVent.com
Ensure that the heating cable voltage rating is
suitable for the power supply voltage available.
Inspect the heating cable and components for
in-transit damage.
2.10 Review the Design
Hold a project coordination meeting. Review the
design at this meeting and ensure that the cables
supplied meet the design requirements and conform
to the watt density (watts per square foot/watts per
square meter) requirements for the project at the
specified cable spacing. This can be verified in
conjunction with the MI Surface Snow Melting
Design Guide (H57045).
Review the installation steps in Section 3 for the
particular application as several trades may be
involved in the system installation. Review Section 4
on accessory installation including the location of all
junction boxes. During the meeting, discuss the role
of each trade and the contractor.
Spacing and watt density may be confirmed as
follows:
English
Cable Spacing (in) = Heated Area (ft
2
) X 12
Heating Cable Length (ft)
Watt Density (W/ft
2
) = Heating Cable Wattage (W)
Heated Area (ft
2
)
Metric
Cable Spacing (cm) = Heated Area (m
2
) X 100
Heating Cable Length (m)
Watt Density (W/m
2
) = Heating Cable Wattage (W)
Heated Area (m
2
)
2
General Installation Guidelines
nVent.com | 13
For three-phase supply voltages, the total area is
generally divided into multiples of three equal
subsections, allowing for installation of a single
cable in each subsection. Heating cables of the
same length and wattage, installed in each
subsection, will provide a balanced electrical load.
It may not be possible to use a balanced electrical
load for small areas, therefore one or two heating
cables, single-phase connected, must be used.
Ensure that the cold lead length is sufficient to reach
the junction box. The standard cold lead length for
pre-engineered (SUB) cables is 15 ft (4.6 m), but
heating cables may have been custom designed
using longer cold leads. Plan the location of all
junction boxes and supply points so that they are
located within reach of the heating cable cold leads.
Typical junction box installation details are shown in
Section4.
The location of all joints in the ramp or slab
should be recorded on the layout drawing. Plan the
general layout of the heating cables to avoid cross-
ing control and expansion joints. In some cases, the
placement of these joints may have to be relocated
in order to divide the area equally since the quantity
of heating cables supplied may have been based
on equal subsection areas. If necessary, control
joints can be crossed using one of the two methods
shown in Figure 9. Crossing expansion joints should
be avoided, but if this is not possible, use the
method shown in Figure 10.
Types of Joints
Control joints are intended to control where the slab
will crack. Their exact location is determined by the
concrete installers before the concrete is poured.
Because of the reinforcement in the base slab, there
is rarely a shearing action caused by differential
vertical movement between the concrete on either
side of the crack. As a precautionary measure, how-
ever, either of the two methods of crossing control
joints shown in Figure 9 should be used. Minimize
the number of times the joint is crossed as shown in
Figure 9. When installing cables using the two-pour
2
General Installation Guidelines
14 | nVent.com
method, control joints must be placed in both the
base slab and the surface slab.
WARNING: Use caution when saw cutting the
control joints to avoid damaging the heating cables.
Consult with the electrical contractor or cable
installer before cutting or drilling to find out cable
depth.
2
General Installation Guidelines
nVent.com | 15
Angle iron
Hot/cold joints
Cold leads
Control joints
(cut into both bottom
and top slabs for two
pour installations)
Well-drained base
Nonmetallic
conduit
Base slab
Heating cable
1 x 1 x 12 in
(2.5 x 2.5 x 30 cm)
angle iron filled
with RTV or silicone
rubber caulk
Control joint
Steel rebar
Heating cable secured
to rebar with plastic
tie wraps
Concrete
Figure 9: Crossing control joints
Construction joints are joints that occur when the
concrete pour is going to stop but will resume at
a later date. Therefore, their location may not be
known beforehand. However, the reinforcement
is left protruding out of the first pour so that it
enters the next pour and therefore shearing action
2
General Installation Guidelines
16 | nVent.com
rarely occurs due to differential vertical movement
between the concrete on either side of the joint. As
a precautionary measure, either of the two methods
of crossing control joints shown in Figure 9 should
be used.
Expansion joints are placed where a concrete slab
abuts some structure, such as a building, a slab, or a
foundation, etc. Because the reinforcement does not
cross expansion joints, differential movement will
occur between the slab and the adjoining structure.
Avoid crossing expansion joints with the heating
cable. If this is not possible, expansion joints can be
crossed using a sand filled metal box as shown in
Figure 10.
Well drained
gravel base
Concrete slab
Expansion
joint
Heating
cable
Heating
cable
Metal
box
6 in x 6 in x 4 in
(15 cm x 15 cm x 10 cm)
metal box filled with sand
Figure 10: Crossing expansion joints
Refer to the installation instructions in Section 3
for your specific application. This section gives
details on the minimum and maximum concrete
or asphalt cover required over the heating cables
and maximum paver thickness, cable testing
requirements during installation, and other specific
installation details.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100

Raychem MI Surface Snow Melting Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI