Installation and operating instructions
GRUNDFOS INSTRUCTIONS
English (GB)
2
English (GB) Installation and operating instructions
Original installation and operating instructions
These installation and operation instructions apply to the
Grundfos Hydro Multi-E booster systems.
CONTENTS
Page
1. Symbols used in this document
3
1.1 Warnings against hazards involving risk of death or
personal injury
3
1.2 Other important notes
3
2. Product introduction
3
2.1 Product description
3
2.2 Intended use
3
3. Receiving the product
4
3.1 Transporting the product
4
3.2 Inspecting the product
4
3.3 Scope of delivery
4
3.4 Handling and lifting the product
4
4. Identification
5
4.1 Nameplate
5
5. Type key
6
6. Installation
7
6.1 Location
7
6.2 Mechanical installation
7
6.3 Drain holes
7
6.4 Electrical installation
8
6.5 Mains supply
8
6.6 Additional protection
9
6.7 Connection terminals
9
6.8 Signal cables
13
7. Optional bus communication via Grundfos CIM
modules
13
7.1 Installing a Communication Interface Module
13
8. Identification of functional module
14
9. Startup
15
9.1 Hygiene
15
9.2 Hydro Multi-E in system with positive inlet pressure
15
9.3 Hydro Multi-E in system without inlet pressure
16
10. User interfaces
16
10.1 Standard control panel
16
10.2 Advanced control panel
18
11. Multimaster function
19
11.1 Systems with two or more outlet-pressure sensors
19
12. Description of functions for the system
19
12.1 Settings
19
12.2 Operating mode
19
12.3 Control mode
20
12.4 Pipe-filling function
20
12.5 Stop function
21
12.6 Controller
22
12.7 Operating range
23
12.8 Limit-exceeded function
23
12.9 Proportional pressure
24
12.10 "Pump changeover"
24
12.11 "Undo"
24
12.12 "Pump name"
24
12.13 "Unit configuration"
24
13. Description of functions for pumps
25
13.1 Analog inputs
25
13.2 Pt100/1000 inputs
26
13.3 Digital inputs
26
13.4 Digital inputs/outputs
27
13.5 "Signal relays" 1 and 2 ("Relay outputs")
28
13.6 "Analog output"
28
13.7 External setpoint function
29
13.8 "Predefined setpoints"
30
13.9 Alarm log
30
13.10 Warning log
30
13.11 "Multi-pump setup"
30
14. Setting the product (E products)
31
14.1 Setting by means of the pumps
31
14.2 Setting by means of Grundfos GO Remote
31
14.3 Communication
31
14.4 Menu overview for Grundfos GO Remote
32
15. Protective functions
33
15.1 Dry-running protection
33
16. Priority of settings
35
17. Grundfos Eye
36
18. Signal relays
37
19. Digital input
38
20. Data communication
38
21. Maintenance
38
21.1 Pumps
38
21.2 Motors
38
21.3 Breaker cabinet
38
21.4 Service kits
38
22. Taking the product out of operation
38
22.1 Frost protection
38
23. Startup the product after standstill
38
24. Fault finding
39
25. Technical data, Hydro Multi-E with single-phase
pumps
40
25.1 Supply voltage
40
25.2 Leakage current
40
25.3 Torques
40
26. Technical data, Hydro Multi-E with three-phase
pumps
40
26.1 Supply voltage
40
26.2 Leakage current
40
26.3 Torques
40
27. Operating conditions
40
27.1 Temperatures
40
27.2 Installation altitude
41
27.3 Humidity
41
27.4 Maximum operating pressure
41
27.5 Minimum inlet pressure
41
27.6 Maximum inlet pressure
42
27.7 Minimum flow rate
42
27.8 Maximum starts and stops
42
27.9 Diaphragm tank
42
28. Inputs and outputs
42
29. Factory settings
44
30. Other technical data
45
31. Sound pressure level
45
31.1 Hydro Multi-E with single-phase pumps
45
31.2 Hydro Multi-E with three-phase pumps
45
32. Disposal
45
Read this document before installing the product.
Installation and operation must comply with local
regulations and accepted codes of good practice.
English (GB)
3
1. Symbols used in this document
1.1 Warnings against hazards involving risk of death
or personal injury
The text accompanying the three hazard symbols DANGER,
WARNING and CAUTION is structured in the following way:
1.2 Other important notes
2. Product introduction
2.1 Product description
Hydro Multi-E incorporates Grundfos CRE, CRIE, CME-A or
CME-I pumps with integrated frequency-controlled single- or
three-phase MGE motors and a breaker cabinet.
Grundfos Hydro Multi-E booster systems are designed for
pressure boosting of clean water.
Typical applications:
blocks of flats
hotels
hospitals
schools
office buildings.
The system adjusts its performance to the demand by cutting the
required number of pumps in or out and through parallel control of
the pumps in operation.
2.2 Intended use
Hydro Multi-E is a range of factory-assembled booster systems
ready for installation and operation.
The system maintains a constant pressure through continuous
variable adjustment of the speed of the connected pumps.
Fig. 1 Hydro Multi-E components
The breaker cabinet incorporates a main switch and circuit
breakers.
DANGER
Indicates a hazardous situation which, if not avoided,
will result in death or serious personal injury.
WARNING
Indicates a hazardous situation which, if not avoided,
could result in death or serious personal injury.
CAUTION
Indicates a hazardous situation which, if not avoided,
could result in minor or moderate personal injury.
SIGNAL WORD
Description of hazard
Consequence of ignoring the warning.
- Action to avoid the hazard.
A blue or grey circle with a white graphical symbol
indicates that an action must be taken.
A red or grey circle with a diagonal bar, possibly with
a black graphical symbol, indicates that an action
must not be taken or must be stopped.
If these instructions are not observed, it may result in
malfunction or damage to the equipment.
Tips and advice that make the work easier.
TM07 4824 2519
Pos. Description
1Pump
2 Diaphragm tank
3 Pressure sensor and gauge
4 Outlet manifold
5 Bent base frame or base frame C-profile
6 Breaker box
7Nameplate
8 Non-return valve
9 Pressure switch or pressure sensor and gauge
10 Inlet manifold
11 Isolating valve
11
10
9
8
7
6
5
4
3
2
1
English (GB)
4
3. Receiving the product
3.1 Transporting the product
Depending on the size, the booster system is supplied in a
wooden cage, closed wooden box, wrapped on a pallet or
cardboard box designed for transport by forklift truck or similar
vehicle.
3.2 Inspecting the product
Before installing the product, check the following:
• The booster system corresponds to the order.
• All visible parts are intact.
3.3 Scope of delivery
The box contains the following:
1 Hydro Multi-E system
installation and operating instructions for Hydro Multi-E
quick guide for Hydro Multi-E
installation and operating instructions for CRE, CRIE, CRNE,
SPKE, MTRE, CME.
3.4 Handling and lifting the product
Hydro Multi-E with CRE or CME with a base frame made of bent
steel plate has lifting brackets fitted on the base frame. See fig. 5.
Hydro Multi-E with CRE with a C-profile base frame has eyebolts
for lifting the system. See fig. 6.
Use lifting gear that ensures a vertical lift. See fig. 3.
Use a safety strap around one of the pump motors to prevent
the system from tilting. See fig. 3.
For systems with lifting brackets, you can remove these from the
base frame after installation. See fig. 5.
Fig. 2 Lifting a Hydro Multi-E system correctly with a fork lift
Fig. 3 Lifting gear that ensures a vertical lift for Hydro Multi-E
system with a bent base frame
DANGER
Overhead load
Death or serious personal injury
- When lifting the booster system, do not use the
eyebolts of the motors.
- Do not lift the booster system by the manifolds.
- Do not stand on the manifolds.
WARNING
Crushing of feet
Death or serious personal injury
- Use the supplied wooden beams delivered to
support the system when mounting machine
shoes.
WARNING
Overhead load
Death or serious personal injury
- Use safety equipment when mounting the base
frame.
- Restrict access to the area.
- Installation must be carried out by trained
personnel.
CAUTION
Overhead load
Minor or moderate personal injury
- Use appropriate lifting equipment when placing the
system.
When lifting the product, the lifting point must always
be above the centre of gravity to ensure stability.
Do not stand on the manifolds.
TM07 4815 2719TM07 48165 2719
1
3
2
7
4
6
5
English (GB)
5
Fig. 4 Lifting gear that ensures a vertical lift for Hydro Multi-E
with CME
Fig. 5 Position of lifting brackets for Hydro Multi-E CRE and
CME
Fig. 6 Lifting a Hydro Multi-E system with a C-profile base
correctly in brackets
4. Identification
4.1 Nameplate
Fig. 7 Hydro Multi-E nameplate
TM07 4817 2719TM07 4818 2719
TM07 4819 2719
Pos. Description
1 Wooden beam (included)
2 Wooden screws (included)
3Fork lift
4 Lifting strap
5 Safety strap
6Shackles
7 Lifting gear
8 Split pin (included)
9 Lifting brackets (included)
10 Bolted C-profile base frame
7
4
6
5
9
8
10
TM06 7460 3516
Pos. Description
1 Type designation
2 Model
3 Serial number
4 Supply voltage
5 Maximum operating pressure in bar
6 Liquid temperature
7 Enclosure class
8 Weight in kg
9 Country of origin
10 Company logo
11 Maximum flow rate in m
3
/h
12 Nominal head in metres
13 Approval mark
14 Approval mark
15 QR code
MADE IN GERMANY
DK - 8850 - Bjerringbro - Denmark
QR
code
IP Class: IP54
Weight: 83kg
Liq. temp.: 5-60ºC
pMax: 16 bar
Q Nom / Max: 14 / 20 m /h
H Nom / Max: 68 / 93 m
3
Mains supply: 3 x 380 - 415
Serial No
Model: 98486745
Type: Hydro Multi-E 2 CRIE 5-9 U2 A-A-A-A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
English (GB)
6
5. Type key
Example Hydro Multi -E 2 CRIE 15-3 U7 A- A- A- A- ABCD
Name
System type
E: All pumps with E-motor
Number of main pumps
Pump type
Voltage code
U1: 3 x 380-415, N, PE, 50/60 Hz
U2: 3 x 380-415, PE, 50/60 Hz
U7: 1 x 200-240, PE, 50/60 Hz
U8: 1 x 200-240, N, PE, 50/60 Hz
UJ: 1 x 208-230, PE, 60 Hz
UX: CSU variant (special voltage rating)
Design
A: Systems with breaker cabinet mounted on the system
B: Systems with wall mounted breaker cabinet and 5 m cable
C: Systems with breaker cabinet mounted on the left side.
Starting method
A: E
Material combination
A: Stainless steel manifold, base frame and standard valves
B: Stainless steel manifold, base frame and valves
C: Galvanised steel manifold, base frame and standard valves (CME-A pumps only)
G: Galvanised steel manifold, base frame and standard valves
I: Stainless steel manifold, base frame painted black and standard valves
P: Stainless steel manifold, galvanised steel base frame and standard valves
Drinking water approvals
A: ACS-approved components
B: Belgaqua-approved components
D: DVGW-approved components
K: KIWA-approved components
N: NFS-approved components
V: WRAS-approved components
W: WRAS-approved system
Y: No special approval
Options
A: Standard hydraulics
B: No redundant outlet-pressure sensor
C: Outlet-pressure sensor on each pump
D: Sensor as dry-running protection
E: No dry-running protection
F: Level switch as dry-running protection
G: CIM module included
H: Terminal for dry-running protection
K: No inlet manifold
L: Non-return valves on the inlet side
M: Pressure gauge on inlet side
O: PN 25 pressure rating
S: CSU variant
T: Certificate
U: Undersized motor
X: More than four options
English (GB)
7
6. Installation
6.1 Location
Observe the following to ensure adequate cooling of motor and
electronics:
Position Hydro Multi-E in such a way that adequate cooling is
ensured. See section 6.2.1 Ensuring motor cooling
The ambient temperature must not exceed 50 °C.
Keep motor cooling fins and fan blades clean.
The booster system must have a 1-metre clearance in front and
on the two sides.
6.2 Mechanical installation
Arrows on the pump base show the direction of the flow of water
through the pump.
1. The pipes connected to the booster system must be of
adequate size. Fit expansion joints in the inlet and outlet pipes
to avoid resonance. See fig. 8.
Connect the pipes to the manifolds of the booster system.
The manifold comes with a screw cap fitted to one end. If this end
is to be used, remove the screw cap, apply sealing compound to
the other end of the manifold, and fit the screw. Fit a blanking
flange with gasket on flanged manifolds.
Tighten up the booster system before starting it.
If booster systems are installed in blocks of flats or the first
consumer on the line is close to the booster system, we
recommend that you fit expansion joints on the inlet and outlet
pipes to prevent vibration being transmitted through the pipes.
See fig. 8.
2. Position the booster system on a plane and solid surface, for
example a concrete floor or foundation. If the booster system
is not fitted with vibration dampers, it must be bolted to the
floor or the foundation.
3. Fasten the pipes to parts of the building to ensure that they
cannot move or be twisted.
Fig. 8 Installation example with expansion joints and pipe
supports
The expansion joints and pipe supports shown in fig. 8 are not
included in the standard booster system.
6.2.1 Ensuring motor cooling
Leave at least 50 mm between the end of the fan cover and a wall
or other fixed objects. See fig. 9.
Fig. 9 Minimum distance (D) from the motor to a wall or other
fixed objects
6.3 Drain holes
When the motor is installed in moist surroundings or areas with
high humidity, the bottom drain hole must be open. If the humidity
is constantly high and above 85 %, open the drain holes in the
drive-end flange. The enclosure class of the motor will then be
lower. This helps prevent condensation in the motor as the motor
becomes self-venting, and it allows water and humid air to
escape.
The motor has a plugged drain hole on the drive side. You can
turn the flange 90 ° to both sides or 180 °.
Fig. 10 Drain holes
WARNING
Overhead load
Death or serious personal injury
- Use safety equipment when mounting the base
frame.
- Restrict access to area.
- Installation must be carried out by trained
personnel.
WARNING
Crushing of feet
Death or serious personal injury
- Use safety equipment when replacing the flange.
- Restrict access to area.
- Installation must be carried out by trained
personnel.
CAUTION
Crushing of feet
Minor or moderate personal injury
-Use
safety equipment when installing the tank.
For outdoor installation, always place the system
under a roof to avoid exposing the system to direct
sunlight. See section 28. Inputs and outputs
TM00 7748 1996
Pos. Description
1 Expansion joint
2 Pipe supports
TM05 5236 3512
TM02 9037 1604
2
2
11
2
D
B3 B14 B5
English (GB)
8
6.4 Electrical installation
Carry out the electrical connection according to local regulations.
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
If the power supply cable is damaged, it must be replaced by the
manufacturer, the manufacturer's service partner or a similarly
qualified person.
The user or the installer is responsible for the installation of
correct earthing and protection according to local regulations. All
operations must be carried out by a qualified electrician.
The booster system must be stationary and installed permanently.
Furthermore, connect the booster system permanently to the
power supply.
Carry out the earth connection as duplicate conductors.
If the system cannot be installed with the supply disconnecting
device located minimum 0.6 m above service level according to
EN 60204-1 paragraph 5.3.4, install the system with an external
"supply disconnecting device" made according to EN 60204-1,
paragraph 5.3.2. The system must be provided with a means
permitting it to be locked in OFF (isolated) position.
6.4.1 Protection against electric shock, indirect contact
Protective-earth conductors must always have a yellow and
green (PE) or yellow, green and blue (PEN) colour marking.
Protection against mains voltage transients
The motor is protected against mains voltage transients in
accordance with EN 61800-3.
Motor protection
The motor requires no external motor protection. The motor
incorporates thermal protection against slow overloading and
blocking.
6.4.2 Insulation resistance
6.5 Mains supply
Check that the supply voltage and frequency correspond to the
values stated on the nameplate.
The wires in the breaker cabinet must be as short as possible.
Excepted from this is the separated earth conductor which must
be so long that it is the last one to be disconnected in case the
cable is inadvertently pulled out of the cable entry.
For maximum backup fuse, see section 25.1 Supply voltage.
Fig. 11 Example of a mains-connected Hydro Multi-E with
backup fuses and additional protection (applies only
for systems with single-phase motors)
For maximum backup fuse, see section 26.1 Supply voltage.
Fig. 12 Example of a mains-connected Hydro Multi-E with
backup fuses and additional protection (applies only
for systems with three-phase motors)
DANGER
Electric shock
Death or serious personal injury
- Switch off the power supply and wait at least five
minutes before you make any connections in the
breaker cabinet or terminal boxes. Make sure that
the power supply cannot be accidentally switched
on.
- Connect the motor to protective earth and protect
against indirect contact according to local
regulations.
- Installation must be carried out by trained
personnel.
WARNING
Electric shock
Death or serious personal injury
- Connect the motor to protective earth and protect
against indirect contact according to local
regulations.
Do not measure the insulation resistance of motor
windings or an installation incorporating motors with
integrated frequency converters using high-voltage
megging equipment as this may damage the built-in
electronics.
Use dedicated IT network motors if the booster
system is supplied through an IT network. Contact
Grundfos.
TM02 4547 4211TM02 4546 4211
ELCB
Breaker cabinet
Installation in building
ELCB
(GFCI)
Breaker cabinetInstallation in building
English (GB)
9
6.6 Additional protection
6.6.1 Systems with single-phase motors
If Hydro Multi-E is connected to an electric installation where an
earth leakage circuit breaker (ELCB) or ground fault circuit
interrupter (GFCI) is used as additional protection, this circuit
breaker or interrupter must be marked with the following symbol:
The leakage current of Hydro Multi-E can be found in section
25.2 Leakage current.
6.6.2 Systems with three-phase motors
If Hydro Multi-E is connected to an electric installation where an
earth leakage circuit breaker (ELCB) or ground fault circuit
interrupter (GFCI) is used as additional protection, this circuit
breaker or interrupter must be of the following type:
It must be suitable for handling leakage currents and cutting-in
with short pulse-shaped leakage.
It must trip when alternating fault currents and fault currents
with DC content, i.e. pulsating DC and smooth DC fault
currents, occur.
For these systems an earth leakage circuit breaker or ground
fault circuit interrupter, type B, must be used.
This circuit breaker or interrupter must be marked with the
following symbols:
The leakage current of Hydro Multi-E can be found in section
26.2 Leakage current.
Protection against phase unbalance
The motors must be connected to a power supply with a quality
corresponding to IEC 60146-1-1, class C, to ensure correct motor
operation at phase unbalance.
This Also Ensures Long Life Of The Components.
6.7 Connection terminals
The descriptions and terminal overviews in this section apply to
both single- and three-phase motors.
For maximum torques, see section 25.3 Torques.
6.7.1 Connection terminals, CRE, CRIE and CRNE pumps
CRE, CRIE and CRNE pumps have a number of inputs and
outputs enabling the pumps to be used in advanced applications
where many inputs and outputs are required.
The pumps have these connections:
three analog inputs
one analog output
two dedicated digital inputs
two configurable digital inputs or open-collector outputs
Grundfos Digital Sensor input and output
two Pt100/1000 inputs
two LiqTec sensor inputs
two signal relay outputs
GENIbus connection.
See fig. 13.
Inputs and outputs
All inputs and outputs are internally separated from the
mains-conducting parts by reinforced insulation and galvanically
separated from other circuits. All control terminals are supplied by
protective extra-low voltage (PELV) to ensure protection against
electric shock.
Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
Mains supply (terminals N, PE, L or L1, L2, L3, PE).
When an earth leakage circuit breaker or ground
fault circuit interrupter is selected, the total leakage
current of all the electrical equipment in the
installation must be taken into account.
When an earth leakage circuit breaker or ground
fault circuit interrupter is selected, the total leakage
current of all the electrical equipment in the
installation must be taken into account.
ELCB
(GFCI)
ELCB
(GFCI)
RDC Type B
Digital input 1 is factory-set to be the start-stop input
when open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the
jumper if digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
English (GB)
10
* If you use an external supply source, there must be a
connection to GND.
Fig. 13 Connection terminals, CRE, CRIE and CRNE pumps
TM05 3509 3512
3
15
8
26
23
25
24
7
21
20
22
B
Y
6
5
2
4
10
A
+24 V*
1
14
9
12
17
19
11
18
+24 V*
+
+24 V*
OC
DI
+24 V*/5 V*
+24 V*
+
+
+
+24 V*/5 V*
+24 V*
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
LiqTec
AI3
GND
DI2
LiqTec
GND
AO
Pt100/1000
Pt100/1000
DI4/OC2
GND
+24 V*
OC
DI
GND
NC
C2
NO
NC
C1
NO
+5 V*
Terminal Type Function
NC
Normally closed
contact
Signal relay 1
(LIVE or PELV)
C1 Common
NO
Normally open
contact
NC
Normally closed
contact
Signal relay 2
(PELV only)
C2 Common
NO
Normally open
contact
18 GND Ground
11 DI4/OC2
Digital input/output,
configurable
Open collector: Max. 24 V
resistive or inductive
19 Pt100/1000 input 2 Pt100/1000 sensor input
17 Pt100/1000 input 1 Pt100/1000 sensor input
12 AO
Analog output:
0-20 mA / 4-20 mA
0-10 V
9 GND Ground
14 AI3
Analog input:
0-20 mA / 4-20 mA
0-10 V
1 DI2 Digital input, configurable
21 LiqTec sensor input 1
LiqTec sensor input
(white conductor)
20 GND
Ground (brown and black
conductors)
22 LiqTec sensor input 2
LiqTec sensor input
(blue conductor)
10 DI3/OC1
Digital input/output,
configurable
Open collector: Max. 24 V
resistive or inductive
4AI1
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2 DI1 Digital input, configurable
5+5 V
Supply to potentiometer
and sensor
6 GND Ground
A GENIbus, A GENIbus, A (+)
Y GENIbus, Y GENIbus, GND
B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
8 +24 V Supply
26 +5 V
Supply to potentiometer
and sensor
23 GND Ground
25 GDS TX
Grundfos Digital Sensor
output
24 GDS RX
Grundfos Digital Sensor
input
7AI2
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
English (GB)
11
6.7.2 Connection terminals, CME pumps
The CME pump has these connections:
two analog inputs
two digital inputs or one digital input and one open-collector
output
Grundfos Digital Sensor input and output
two signal relay outputs
GENIbus connection.
See fig. 14.
Inputs and outputs
All inputs and outputs are internally separated from the
mains-conducting parts by reinforced insulation and galvanically
separated from other circuits. All control terminals are supplied by
protective extra-low voltage (PELV) to ensure protection against
electric shock.
Signal relay outputs
– Signal relay 1:
LIVE:
You can connect supply voltages up to 250 VAC to the
output.
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
– Signal relay 2:
PELV:
The output is galvanically separated from other circuits.
Therefore, you can connect the supply voltage or protective
extra-low voltage to the output as desired.
Mains supply (terminals N, PE, L or L1, L2, L3, PE).
Digital input 1 is factory-set to be the start-stop input
when open circuit results in stop. A jumper has been
factory-fitted between terminals 2 and 6. Remove the
jumper if digital input 1 is to be used as external
start-stop or any other external function.
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
English (GB)
12
* If you use an external supply source, there must be a
connection to GND.
Fig. 14 Connection terminals, CME pump (optional for CRE,
CRIE, CRNE, SPKE and MTRE pumps)
TM05 3510 3512
3
15
8
26
23
25
24
7
B
Y
6
5
2
4
10
A
AI2
GDS RX
GDS TX
GND
GENIbus A
GENIbus B
+5 V
+24 V
+24 V
GND
GENIbus Y
GND
+5 V
DI1
AI1
DI3/OC1
+24 V*
+
+
+24 V*/5 V*
+24 V*
+5 V*
NC
C2
NO
NC
C1
NO
+24 V*
+
+
+24 V*/5 V*
+24 V*
+24 V*
OC
DI
GND
Terminal Type Function
NC
Normally closed
contact
Signal relay 1
(LIVE or PELV)
C1 Common
NO
Normally open
contact
NC
Normally closed
contact
Signal relay 2
(PELV only)
C2 Common
NO
Normally open
contact
10 DI3/OC1
Digital input/output,
configurable
Open collector: Max. 24 V
resistive or inductive
4AI1
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
2 DI1 Digital input, configurable
5+5 V
Supply to potentiometer and
sensor
6 GND Ground
A GENIbus, A GENIbus, A (+)
Y GENIbus, Y GENIbus, GND
B GENIbus, B GENIbus, B (-)
3 GND Ground
15 +24 V Supply
8 +24 V Supply
26 +5 V
Supply to potentiometer and
sensor
23 GND Ground
25 GDS TX Grundfos Digital Sensor output
24 GDS RX Grundfos Digital Sensor input
7AI2
Analog input:
0-20 mA / 4-20 mA
0.5 - 3.5 V / 0-5 V / 0-10 V
English (GB)
13
6.8 Signal cables
Use screened cables with a cross-sectional area of minimum
0.5 mm
2
and maximum 1.5 mm
2
for the external on/off switch,
digital inputs, setpoint and sensor signals.
Connect the screens of the cables to the frame at both ends.
The screens must be as close as possible to the terminals.
See fig. 15.
Fig. 15 Stripped cable with screen and wire connections
Always tighten screws for frame connections whether a cable
is fitted or not.
The wires in the motor terminal box must be as short as
possible.
7. Optional bus communication via Grundfos
CIM modules
7.1 Installing a Communication Interface Module
f
Fig. 16 Antistatic service kit
1. Loosen the four screws (fig. 17, A) and remove the terminal
box cover (fig. 17, B).
Fig. 17 Removing the terminal box cover
2. Remove the CIM cover (fig. 18, A) by pressing the locking tab
(fig. 18, B) and lifting the end of the cover (fig. 18, C). Then lift
the cover off the hooks (fig. 18, D).
Fig. 18 Removing the CIM cover
3. Remove the securing screw (fig. 19, A).
Fig. 19 Removing the securing screw
4. Fit the CIM module by aligning it with the three plastic holders
(fig. 20, A) and the connecting plug (fig. 20, B). Press the
module home using your fingers.
Fig. 20 Fitting the CIM module
5. Fit and tighten the securing screw (fig. 19, A) to 1.3 Nm.
6. Make the electrical connections to the CIM module as
described in the instructions supplied with the module.
7. Connect the cable screens of the bus cables to earth via one
of the earth clamps (fig. 21, A).
Fig. 21 Connecting the cable screens to earth
TM02 1325 4402
DANGER
Electric shock
- Death or serious personal injury
- Switch off the power supply to the motor and to the
signal relays. Wait at least 5 minutes before
starting any work on the motor. Make sure that the
power supply cannot be accidentally switched on.
Always use an antistatic service kit when handling
electronic components. This prevents static electricity
from damaging the components.
When unprotected, place the component on the
antistatic cloth.
TM06 4081 1515
A
B
TM06 4084 1515TM06 4082 1515
TM06 4083 1515
TM06 4195 1615
B
C
D
A
A
A
B
A
English (GB)
14
8. Route the wires for the CIM module. See the example in fig.
22.
Fig. 22 Example of wire routing
9. Fit the CIM cover.
10.If the CIM module is supplied with an FCC label, then place
the label on the terminal box. See fig. 23.
Fig. 23 FCC label
11. Fit the terminal box cover (fig. 17, B) and cross-tighten the
four mounting screws (fig. 17, A) to 6 Nm.
8. Identification of functional module
You can identify the fitted module in one of the following ways:
Grundfos GO
You can identify the functional module in the "Fitted modules"
menu under "Status".
Pump display
For pumps fitted with the advanced control panel, you can identify
the functional module in the Fitted modules menu under Status.
Motor nameplate
You can identify the fitted module on the motor nameplate. See
fig. 24.
Fig. 24 Identification of functional module
TM06 4085 1515TM05 7028 0413
Make sure that the terminal box cover is aligned with
the control panel.
FCC
TM06 1889 3314
Variant Description
FM 200 Standard functional module
FM 300 Advanced functional module
Env.Type :
Serial no :
SF CL:
PF:
PB
FM
HMIEff
n max:
CIMWgt
:
DE
:
kg
NDE
:
T
amb
:
:
FAA
V
~
P.C.
:
Made in Hungary
OUTPUT
VARIANT
INPUT
TEFC
Type
:
P.N.
:
U
in
:
I
1/1
:
f
in
Hp
Hz
P2
I
SF Amp:
rpm
:::
:
:
:
:
Xxxxxxxxxxx
E.P. Motor
DK - 8850 Bjerringbro, Denmark
E
n
v
.
T
y
y
p
e
p
:
S
eri
a
l
n
o
:
SF
C
L
:
P
F
:
Eff
n
W
g
g
t
:
DE
:
k
g
g
N
D
E
:
T
a
m
b
:
:
F
A
A
V
~
P
.
C
.
:
IN
PU
T
T
E
F
C
T
yp
yp
e
:
P
.N
.
:
U
i
n
:
I
1
/
1
:
f
i
n
H
z
P
I
S
F Am
p
p
:
:
PB
FM
HMI
CIM
VARIANT
Hp
rpm
:
:
:
:
PB
:
HMI
:
C
IM
:
H
p
r
pm
English (GB)
15
9. Startup
9.1 Hygiene
Grundfos pressure booster systems are functionally tested by
running water through the system. During the test, Grundfos
continuously surveys the quality of the test water. Since it is not
possible to completely drain and dry the system after the test, the
system must be rinsed or flushed thoroughly before being taken
into use in a drinking water sector due to risk of bacteria growth.
This also applies if the system has been shut down for a long
period of time. Rinsing and flushing must always be done in
accordance with local regulations.
Contaminated drinking water endangers health.
9.2 Hydro Multi-E in system with positive inlet
pressure
When you have carried out the mechanical and electrical
installation described in section 6. Installation, proceed as
follows:
1. Check that Hydro Multi-E corresponds to the order and that no
single parts have been damaged.
2. Check that the precharge pressure in the diaphragm tank is
0.7 times the required outlet pressure (setpoint).
3. Connect water and power supplies to the system.
4. Open all pump inlet and outlet valves.
5. Vent all pumps by means of the vent screws.
Fig. 25 Position of vent screws in systems with CME-A/-I
pumps
Fig. 26 Position of vent screws in systems with CRI, CRIE
pumps
6. Switch on the power supply with the main switch.
7. Start pump 1 by pressing the start/stop button on the pump
control panel.
8. Vent pump 1 using the vent screw.
9. Repeat steps 9 and 10 for the other pumps in the system.
10.Set the desired outlet pressure.
11. Check that the pumps are cutting in and out, thus adjusting
the performance to the demand.
Hydro Multi-E is now in automatic mode and ready for operation.
The standard settings can be changed using Grundfos Go
Remote, see 11. Multimaster function or advanced control panel.
DANGER
Electric shock
- Death or serious personal injury
- Make sure that the wires to be connected to the
connection groups below are separated from each
other by reinforced insulation in their entire
lengths.
DANGER
Contaminated drinking water
- Death or serious personal injury
- Flush the system before starting it or after a
standstill period.
WARNING
Electric shock
Death or serious personal injury
- Switch off the power supply and wait at least five
minutes before you make any connections in the
breaker cabinet
- Tighten the screws.
WARNING
High noise level
Death or serious personal injury
- Use ear protection.
Make sure that the power is switched off on the main
switch and the circuit breakers.
Do not start the pumps until they have been filled
with liquid.
Measure the precharge pressure while the system is
pressureless.
TM05 2008 4211TM05 2009 1717
If you change the outlet pressure, change the
diaphragm tank precharge pressure accordingly.
Vent screws
Vent screws
English (GB)
16
9.3 Hydro Multi-E in system without inlet pressure
When you have carried out the mechanical and electrical
installation described in section 6. Installation, proceed as
follows:
1. Check that Hydro Multi-E corresponds to the order and that no
single parts have been damaged.
2. Check that the precharge pressure in the diaphragm tank is
0.7 times the required outlet pressure (setpoint).
3. Connect water and power supplies to the system.
4. Open all pump inlet valves.
5. Close all pump outlet valves, and prime all pumps and the
inlet pipe.
Fig. 27 Position of vent screw and filling screw
6. Switch on the power supply with the main switch.
7. Start pump 1 by pressing the start/stop button on the pump
control panel.
8. Vent pump 1 using the vent screw.
9. Slowly open the outlet valve approximately 50 %.
10.Repeat steps 9 and 11 for the other pumps in the system.
11. Slowly fully open all pump outlet valves.
12. Wait for a few minutes.
13. Set the desired outlet pressure.
14.Check that the pumps are cutting in and out, thus adjusting
the performance to the demand.
Hydro Multi-E is now in automatic mode and ready for operation.
The standard settings can be changed using Grundfos Go
Remote, see section11. Multimaster function or advanced control
panel.
10. User interfaces
You can configure pump settings using the following user
interfaces:
Standard control panel
See section 10.1 Standard control panel.
Advanced control panel
See section 10.2 Advanced control panel
Grundfos GO Remote.
See section 11. Multimaster function.
If the power supply is switched off, the settings will be stored.
10.1 Standard control panel
Fig. 28 Standard control panel
Make sure that the power is switched off on the main
switch and the circuit breakers.
Do not start the pumps until they have been filled
with liquid.
Hydro Multi-E systems with CME pumps require a
positive inlet pressure during startup and operation.
The following startup procedure therefore only
applies to Hydro Multi-E systems with CRE or CRIE
pumps.
Measure the precharge pressure while the system is
pressureless.
TM05 2009 1717
If you change the outlet pressure, change the
diaphragm tank precharge pressure accordingly.
Vent screw
Filling screw
WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as the
product may be very hot.
TM05 4848 3512
Pos. Symbol Description
1
Grundfos Eye
Shows the operating status of individuals
pump.
See section 17. Grundfos Eye for further
information.
2 - Light fields for indication of setpoint.
3
Changes the setpoint and resets alarms
and warnings.
4
Enables radio communication with
Grundfos GO Remote and other products of
the same type.
5
Makes the pump ready for operation or
starts and stops the pump.
Start:
If the button is pressed when the pump is
stopped, the pump will only start if no other
functions with higher priority have been
enabled. See section 16. Priority of
settings.
Stop:
If the button is pressed when the pump is
running, the pump will always be stopped.
When the pump is stopped via this button,
the "Stop" text next to the button will
illuminate.
1
2
3
4
5
Stop
English (GB)
17
10.1.1 Setpoint setting
Set the desired setpoint by pressing or . The setpoint can
be set on any of the pumps in the system and applies to the
complete booster system.
The light fields on the control panel will indicate the setpoint set.
Pump in constant-pressure control mode
Hydro Multi-E systems are as standard set up from factory as
pressure boosting systems, but can be set up to other control
modes. See CRI and CRIE IO installation and operating
instructions. The following example applies to a pump in an
application where a pressure sensor gives a feedback to the
pump. If the sensor is retrofitted to the pump, it must be set
manually as the pump does not automatically register a
connected sensor.
Figure 29 shows that the light fields 5 and 6 are activated,
indicating a desired setpoint of 3 bar with a sensor measuring
range from 0 to 6 bar. The setting range is equal to the sensor
measuring range.
Fig. 29 Setpoint set to 3 bar, constant-pressure control mode
Fig. 30 Constant pressure curve
Setting to maximum curve:
Press
continuously to change over to the maximum curve
of the pump (top light field flashes). When the top light field is
on, press and hold for
for 3 seconds until the light field
starts flashing.
To change back, press
continuously until the desired
setpoint is indicated.
Example: Pump set to maximum curve.
Figure 31 shows that the top light field is flashing, indicating
maximum curve.
Fig. 31 Maximum curve duty
Setting to minimum curve:
Press
continuously to change over to the minimum curve
of the pump (bottom light field flashes). When the bottom light
field is on, press and hold
for 3 seconds until the light field
starts flashing.
To change back, press continuously until the desired
setpoint is indicated.
Example: Pump set to minimum curve.
Figure 32 shows that the bottom light field is flashing, indicating
minimum curve.
Fig. 32 Minimum curve duty
TM05 4894 3512TM05 7901 35122
0
6
3
bar
H
Q
TM05 4896 2812TM05 4897 2812
H
Q
H
Q
English (GB)
18
10.1.2 Start or stop the system
Start each pump by pressing
or by continuously pressing
until the desired setpoint is indicated.
Stop the system by pressing on each pump. When the pump
is stopped, the "Stop" text next to the button will illuminate. Each
pump can also be stopped by continuously pressing
until
none of the light fields are on.
If a pump has been stopped by pressing , it can only be
released for operation by pressing again.
If a pump has been stopped by pressing , it can only be
restarted by pressing .
The pump can also be stopped with Grundfos GO Remote or via
a digital input set to "External stop". See section 16. Priority of
settings.
10.1.3 Resetting of fault indications
A fault indication can be reset in one of the following ways:
Via the digital input if it has been set to "Alarm resetting".
Briefly press or
on one of the pumps. This will not
change the setpoint.
A fault indication cannot be reset by pressing or
if the
buttons have been locked.
Switch off the power supply until the indicator lights are off.
Switch the external start/stop input off and then on again.
With Grundfos GO Remote.
10.2 Advanced control panel
The pumps can be fitted with the advanced control panel as an
option.
Fig. 33 Advanced control panel
TM05 4849 1013
Pos. Symbol Description
1
Grundfos Eye
Shows the operating status of individual
pumps.
For further information, see section
17. Grundfos Eye.
2 - Graphical colour display.
3 Goes one step back.
4
Navigates between main menus, displays and
digits.
When you change the menu, the display
always shows the top display of the new
menu.
Navigates between submenus.
Changes value settings.
Note: If you have disabled the function to
configure settings with the Enable/Disable
Settings function, you can temporarily enable
it again by pressing these buttons
simultaneously for at least 5 seconds. See
section "Buttons on product".
4
Saves changed values, resets alarms and
expands the value field.
Enables radio communication with Grundfos
GO and other products of the same type.
When you try to establish radio
communication between the pump and
Grundfos GO or another pump, the green
indicator light in Grundfos Eye flashes. A note
also appears in the pump display stating that
a wireless device wants to connect to the
pump. Press on the pump control panel to
allow radio communication with Grundfos GO
and other products of the same type.
5
Makes the pump ready for operation, and
starts and stops the pump.
Start:
If you press the button when the pump is
stopped, the pump only starts if no other
functions with higher priority have been
enabled. See section 16. Priority of settings.
Stop:
If you press the button when the pump is
running, the pump will always stop. When you
stop the pump via this button, the icon
appears in the bottom of the display.
6 Return to the Home menu.
1
2
3
4
5
6
English (GB)
19
10.2.1 Home display
Fig. 34 Example of Home display
11. Multimaster function
11.1 Systems with two or more outlet-pressure
sensors
If two or more pumps in the system are configured with an
outlet-pressure sensor (standard option), they can all function as
master pumps. As standard, the pump with the lowest number will
be the master pump. From factory, the master pump is marked
with number 1.
If master pump 1 is switched off or stopped due to an alarm, one
of the other master pumps will automatically take control of the
system.
12. Description of functions for the system
Hydro Multi-E offers the following functions via Grundfos Go
Remote or the advanced control panel.
12.1 Settings
12.1.1 Setpoint
You can set the setpoint for all control modes when you have
selected the desired control mode. See section 12.3 Control
mode.
Factory setting
See section 29. Factory settings.
12.2 Operating mode
The operating modes are the operating conditions that the
booster system can be brought in by the user.
Possible operating modes:
"Stop"
All pumps stop.
"Normal" (factory setting)
One or more pumps are operating to maintain the set
pressure.
•"Max."
All pumps run at maximum speed.
The operating modes can be selected on the control panel, with
Grundfos GO Remote or via bus.
12.2.1 Normal operation
Fig. 35 Hydro Multi-E in normal operation, meaning
constant-pressure mode
In constant-pressure mode, Hydro Multi-E adjusts its
performance to the desired setpoint.
TM06 4516 2415
Pos. Symbol Description
1
Home
This menu shows up to four user-defined
parameters. You can select parameters
shown as shortcut icon , and when
pressing you go directly to the "Settings"
display for the selected parameter.
2-
Status
This menu shows the status of the pump
and system as well as warnings and
alarms.
3-
Settings
This menu gives access to all setting
parameters. You can make detailed
settings of the pump in this menu.
See section 13. Description of functions for
pumps.
4-
Assist
This menu enables assisted pump setup,
provides a short description of the control
modes and offers fault advice.
5
Indicates that the pump has been stopped
via the button.
6
Indicates that the pump is functioning as
master pump in a multipump system.
7
Indicates that the pump is functioning as a
slave pump in a multipump system.
8
Indicates that the pump is operating in a
multipump system. See section
13.11 "Multi-pump setup".
9
Indicates that the function to configure
settings has been disabled for safety
reasons. See section "Buttons on product".
Setpoint
5.00 bar
Operating mode
Normal
Actual controlled value
4.90 bar
Control mode
Const. pressure
Status Settings Assist
1 2 3 4
56789
Home
TM02 4328 0602
Q
H
set
H
Hset
English (GB)
20
12.2.2 "Stop" or "Max." operation
In addition to "Normal" operating mode, you can select the
operating modes "Stop" or "Max.". See the example in fig. 36.
Fig. 36 Hydro Multi-E in operating mode "Max."
"Max." operation can for instance be used in connection with the
venting and startup procedures.
12.2.3 Operating condition in case of disconnection of power
supply
If the power supply to Hydro Multi-E disconnects, the settings will
be stored. Hydro Multi-E will restart in the same operating
condition it was in before the disconnection.
12.2.4 Further settings
You can make further settings with Grundfos GO Remote. See
section 11. Multimaster function.
12.3 Control mode
Here you can choose between the different control modes.
12.3.1 Constant pressure
We recommend this control mode if the pump is to deliver a
constant pressure, independently of the flow in the system. See
fig. 37.
Fig. 37 "Constant pressure"
This control mode uses the factory-fitted pressure sensor, if any,
which measures the outlet pressure of the pump.
For pumps without a factory-fitted sensor, you must connect a
pressure sensor to one of the analog inputs of the pump. You can
set the pressure sensor in the Assist menu.
Fig. 38 "Constant pressure"
Controller settings
For recommended controller settings, see section 12.6 Controller.
Factory setting
See section 29. Factory settings.
12.3.2 Proportional pressure
For proportional pressure, see 12.9 Proportional pressure.
12.4 Pipe-filling function
This function is typically used in pressure-boosting applications,
and it ensures a smooth startup of systems with, for instance,
empty pipes.
Startup takes place over two phases. See fig. 39.
1. Filling phase.
The pipes are slowly filled with water. When the pressure
sensor of the system detects that the pipes have been filled,
phase two begins.
2. Pressure buildup phase.
The system pressure is increased until the setpoint is
reached. The pressure buildup takes place over a pressure
buildup period. If the setpoint is not reached within the given
time, a warning or an alarm can be given, and the pumps can
be stopped at the same time.
Fig. 39 Filling and pressure buildup phases
Setting range
"Filling speed".
Fixed speed of the pump during the filling phase.
"Flling pressure".
The pressure that the pump must reach before the maximum
filling time.
"Max. filling time".
The time in which the pump must reach the filling pressure.
Max. time reaction.
Reaction of the pump if the maximum filling time is exceeded:
– warning
– alarm (pump stops).
"Pressure build-up time".
Ramp time from when the filling pressure is reached until the
setpoint must be reached.
Factory setting
See section 29. Factory settings.
TM02 4318 0602
TM05 7901 1613
Examples
One external pressure sensor.
Q
H
Max.
H
Q
p
p
TM06 4267 1815
When you activate this function, the function always
starts when the pump has been in operating mode
"Stop" and is changed to "Normal".
1. Filling phase
(constant-curve
operation)
Pressure
2. Pressure buildup phase
(constant-pressure
operation)
Setpoint
Filling pressure
Actual value
Setpoint
ramp-up
Filling time
Pressure
buildup
time
Time
[sec]
Maximum filling time
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54