GDS Corp GDS-48 Operation and Maintenance Manual

Type
Operation and Maintenance Manual
GDSCorp.
1245ButlerRoadLeagueCity,TX77573
40992729804099274180(Fax)www.gdscorp.com
Operation and Maintenance
Manual
GDS48RemoteBridgeSensorforCombustibleGases,VOCsandCO2

GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 2 [email protected]
CAUTION: FOR SAFETY REASONS THIS EQUIPMENT MUST BE OPERATED AND
SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND INSTRUCTION
MANUAL COMPLETELY BEFORE OPERATING OR SERVICING.
ATTENTION: POUR DES RAISONS DE SÉCURITÉ, CET ÉQUIPEMENT DOIT ÊTRE UTILISÉ,
ENTRETENU ET RÉPARÉ UNIQUEMENT PAR UN PERSONNEL QUALIFIÉ. ÉTUDIER LE
MANUE D’INSTRUCTIONS EN ENTIER AVANT D’UTILISER, D’ENTRETENIR OU DE
RÉPARER L’ÉQUIPEMENT.
REVISIONHISTORY
Revision1.05/1/13 InitialRelease
Copyright©2013GDSCorp.AllRightsReserved
P/N1200085301
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 3 [email protected]
CONTENTS
1SAFETYINFORMATION.............................................................................................................................................4
2GENERALINFORMATION..........................................................................................................................................5
CATALYTICBEADSENSORS................................................................................................................................................5
INFRAREDSENSORS.........................................................................................................................................................5
PIDSENSORS.................................................................................................................................................................5
3SPECIFICATIONS........................................................................................................................................................6
4INSTALLATION..........................................................................................................................................................8
CHOOSINGALOCATION...................................................................................................................................................8
ELECTRICALCONNECTIONS...............................................................................................................................................9
5CALIBRATION..........................................................................................................................................................11
CALIBRATIONOVERVIEW................................................................................................................................................11
GENERALIZEDCALIBRATIONPROCEDURE...........................................................................................................................11
6OPERATIONANDMAINTENANCE............................................................................................................................13
SENSORREPLACEMENT..................................................................................................................................................13
7SPAREPARTS..........................................................................................................................................................15
GRAYENCLOSURE.........................................................................................................................................................15
YELLOWENCLOSURE.....................................................................................................................................................15
SENSORHEADACCESSORIES...........................................................................................................................................15
TableofFigures
Figure31:RecommendedSensorTemperatureRangesandExcitation*....................................................................7
Figure32:RecommendedSensorWarmupTimes.......................................................................................................7
Figure41:GDS48GrayEnclosure................................................................................................................................8
Figure42:GDS48WiringConnections(GrayEnclosure).............................................................................................9
Figure51:ApplyingCalibrationGastoGDS48..........................................................................................................12
Figure61:SensorReplacement..................................................................................................................................14
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 4 [email protected]
1 SAFETYINFORMATION
ImportantReadBeforeInstallation
UsersshouldhaveadetailedunderstandingofGDS48operatingandmaintenanceinstructions.UsetheGDS48
onlyasspecifiedinthismanualordetectionofgasesandtheresultingprotectionprovidedmaybeimpaired.Read
thefollowingWARNINGSpriortouse.
WARNINGS
TheGDS48sensortransmitterdescribedinthismanualmustbeinstalled,operatedandmaintainedin
accordancewithinformationcontainedherein.Installationinanyhazardousareamustcomplywithall
applicablerestrictions,requirementsandguidelinesforsaidhazardousareas.Itistheendusercustomer’s
finaldecisiontoensurethattheGDS48issuitablefortheintendeduse.
TheGDS48isdesignedandconstructedtomeasurethelevelofcertaingasesinambientair.Accuracyin
atmospherescontainingsteamorinertgasescannotbeguaranteed.
Alwaysmountthesensorheadverticallywiththesensorheadfacingdown.
Donotpaintsensorassembly.
DonotoperatetheGDS48ifitsenclosureisdamagedorcrackedorhasmissingcomponents.Makesure
thecover,internalPCB’sandfieldwiringaresecurelyinplacebeforeapplyingpower.
DonotexposetheGDS48toelectricalshockorcontinuousseveremechanicalshock.ProtecttheGDS48
andrelatedsensorassembliesfromdrippingliquidsandhighpowersprays.
Calibratewithknowntargetgasatstartupandcheckonaregularschedule,atleastevery90days.More
frequentinspectionsareencouragedtospotproblemssuchasdirt,oil,paint,greaseorotherforeign
materialsonthesensorhead.
Periodicallytestforcorrectoperationofthesystem’salarmeventsbyexposingthemonitortoatargeted
gasconcentrationabovetheHighAlarmsetpoint.
Useonlyforapplicationsdescribedwithinthismanual.
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 5 [email protected]
2 GENERALINFORMATION
TheGDS48RemoteBridgeSensorisdesignedtosupportremotesensorswithbridgestyleoutputsignalsthatare
suitablefortransmissionoverlongdistances.TheGDS48isideallysuitedforinstallationwherereliabilityandcost
arecriticallyimportantandwherealocaldisplayisnotrequired.
ThreewirebridgestyleoutputcompatiblewithGDSCorpcontrollers.
CertifiedforuseinClassIDivision1,GroupsB,C&Dhazardousareas
Easilyreplaceablesensorelement
Faultindicationforsensorfailormissingsensor(atcontroller)
Constructedof316stainlesssteel
Reliablecatalyticbead,infraredorphotoionizationsensortechnology
CATALYTICBEADSENSORSarethemostcosteffectivesolutionforthedetectionofcombustiblegases.
Catalyticbeadsensorsarecomprisedoftwoindependent‘beads’thatarewrappedwithaspecialwirethatvaries
inresistancebasedonchangesintemperature.Onebeadiscoatedwithamaterial(“catalyst”)thatpromotesthe
burningofanycombustiblegasthatmaybepresent.Duringoperation,anexcitationvoltageappliedtothesensor
raisesthetemperatureofbothbeadstoaprespecifiedvalue.Whengasispresent,thetemperatureofthebead
withthecatalystcoatingincreases.Thischangestheratioofresistancebetweenthetwobeadsandindicatesthe
presenceofgas.Tooperateproperly,catalyticbeadsensorsmustbeinstalledandbalancedforzerowhennogasis
present.
INFRAREDSENSORSuseinfraredlightsourcetodetecthydrocarbons.Carbonhydrogenbondsinmost
commonhydrocarbonmoleculesabsorbcertainfrequenciesofinfraredlight.Asaresult,whenanyhydrocarbon
gaspassesbetweentheinfraredsourceanddetector,thedetectoroutputdrops,indicatingthepresenceofgas.A
referencebeamthatisnotaffectedbyHCbondsisusedtomonitorchangesinsourceintensityandeliminatefalse
alarms.GDSCorpSmartIRinfraredsensorscontainfullyintegratedsource,receiverandmicroprocessorbased
circuitrytoperformthisfunctionandgenerateacatalyticbeadstylebridgeoutput.
PIDSENSORSareappropriateforvolatileorganiccompoundssuchasbenzeneortoluene.Aphotoionization
detector(PID)sensorusesultravioletlighttobreakdowncomplexmoleculesanddetecttheionizedcomponents.
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 6 [email protected]
3 SPECIFICATIONS
Model:GDSCorpRemoteBridgeSensorforCombustibleGasesandCarbonDioxide
PowerInput:Excitationvoltage,dependentonsensor
Display:None
Input:DirectconnectbridgesensorsforcombustibleandCO2gases.
Accuracy:+/‐5%offullscale(typical)
Calibration:Outputisfactoryadjustedbutisnotcalibrated.Receivingdevicemustprovidezero
andspan(twopoint)calibration.TheGDS48iscompatiblewithallGDSCorp
controllerswithbridgestyleinputsthatprovidetwopointcalibrationcapability.
Output:Millivoltbridgestyleoutputs
ResponseTime:Determinedbysensortype andrange
Temperature:Seeindividualsensortemperaturespecifications
FaultIndication:Providedbycontrollerorreceiver
Housing:Junctionboxepoxycoatedaluminum,sensorhead316stainlesssteel.
Approvals: CSAClass1,Division1,GroupsB,CandDExplosionProofwithflamearrestor;
Warranty:Twoyearsonelectronics,oneyearonsensor

GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 7 [email protected]
SensorRange Temperature ExcitationVoltage*
50Methane0100%LEL 20°Cto+50
°
C4.5VDC@80mA
51Propane0100%LEL 20°Cto+50
°
C4.5VDC@80mA
52Methane0100%v/v 20°Cto+50
°
C4.5VDC@80mA
53CarbonDioxideMultiple 20°Cto+50
°
C4.5VDC@80mA
57EthyleneOxide0100%LEL 20°Cto+50
°
C4.5VDC@80mA
61PID10.6eVLowrange 20°Cto+60
°
C3.3VDC@35mA
62PID10.6eVHighrange 20°Cto+60
°
C3.3VDC@35mA
63PID9.6eVLowrange 20°Cto+60
°
C3.3VDC@35mA
64PID10.0eVLowrange 20°Cto+60
°
C3.3VDC@35mA
65PID10.0eVHighrange 20°Cto+60
°
C3.3VDC@35mA
70CatalyticBead0100%LELCH4 40°Cto+60
°
C2.0VDC@300mA
71CatalyticBead0100%LELother 40°Cto+60
°
C2.0VDC@300mA
Figure 3-1: Recommended Sensor Temperature Ranges and Excitation*
*Excitationvoltageisalwaysmeasuredatthesensorjunctionboxbetweenterminals“R”and“A”
TypeSensorRecommendedWarmupTimeComments
5057SmartIRInfrared1hourInternalmicroprocessorprovidesfault
signalandtempcompensation
6164PhotoionizationDetector8hourAllowstimeforcontaminantsto
‘burnoff’bulb
7071CatalyticBead
4hoursOninitialstartupmayrequireless
timeifpowerhasbeenturnedofffor
shorttime
Figure 3-2: Recommended Sensor Warmup Times
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 8 [email protected]
4 INSTALLATION
CHOOSINGALOCATION
Factorssuchasairmovement,gasdensity,emissionsourcesandenvironmentalvariablesaffectsensorlocation.
Airmovementbyfans,prevailingwindsandconvectionshouldbecarefullyevaluatedtodetermineifaleakismore
likelytoraisegaslevelsincertainareaswithinthefacility.Vapordensityofagasdeterminesifitwillriseorfallin
airwhentherearenosignificantcurrents.Lighterthanairgasesshouldhavethemonitorsmounted1218inches
(3045cm)abovethepotentialgasleakandheavierthanairgasesshouldbethisdistancebelow.Eventhough
theGDS48sensortransmitterisdesignedforruggedservice,itshouldbeprotectedfromenvironmentaldamage
fromwater,snow,shock,vibrationanddirt.
TheGDS48shouldalwaysbemountedwiththesensorheadopeningfacingdown.Ifnecessary,aSplashGuard
(p/n100205)shouldbeattachedifthereisanychancethatwaterorliquidspraycouldenterthesensoropening
frombelow.Besuretoleavesufficientroom(~12”)belowthesensorheadtoalloweasyaccessforattachmentof
aCalibrationCupand/orremovalofthesensorheadcoverforsensorreplacement.
Figure 4-1: GDS-48 Remote Bridge Sensor
TB1
USERCAforCO MB US TI B L E, CO2orPIDSENSOR
USESRCfo r OX YG EN orTOXICGASSENSOR
S—R—C
R—C—A
GrayEnclosureYellowEnclosure
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 9 [email protected]
ELECTRICALCONNECTIONS
TheGDS48isathreewirebridgetypesensorthatrequiresexcitationvoltageandoutputsamillivoltlevelsignal
totheremotecontrollerorreceiver.Incorrectwiringcanresultinsensordamageorsensorfailure.
Figure 4-2: GDS-48 Wiring Connections (Gray Enclosure)
Figure 4-3: GDS-48 Wiring Connections (Yellow Enclosure)
TB1
USERCAforCO MB US T I B L E, CO2orPIDSENSOR
USESRCfo rOX Y GEN orTOXIC GASSEN SOR
S—R—C
R—C—A
Threewireconnection
toremotereceiveror
controller
Threewireconnection
toremotereceiveror
controller
“R”
“C”
“A”
“R”
“C”
“A”
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 10 [email protected]
Shieldedcableisalwaysrecommended.Wiringshouldbeinstalledinmetalconduitwithnoothercablinginthe
sameconduit.WhenpowerisinitiallyappliedtotheGDS48theoutputmaymomentarilyindicateatemporaryoff
scalelow(FAULT)oroffscalehigh(OVERRANGE)valuebeforesettlingdown.AllGDSCorpcontrollersprovidea
‘warmup’intervalduringwhichthesensorinputisignored.Thiskeepsthecontrollerfromindicatinganalarmdue
tosensorwarmupcharacteristics.
Totalwarmuptimeisdependentonthetypeofsensorandrangeselected.GDSCorprecommendsafourtoeight
hourintervalbetweeninitialpoweronandfirstcalibration.Ifthesensorhasbeenpoweredup,andhasonlybeen
offlineforafewhours,thewarmuptimewillbeshorter.
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 11 [email protected]
5 CALIBRATION
CALIBRATIONOVERVIEW
TheGDS48doesnothavethecapabilitytoperformzeroandspancalibration.Finalzeroandspancalibrationmust
beperformedbythecontrollerorreceivingdevice.
FollowtheseGDS48calibrationguidelines:
Calibrationaccuracyisonlyasgoodasthecalibrationgasaccuracy.GDSCorpcalibrationgasesare
traceabletoNIST(NationalInstituteofStandardsandTechnology).
Neverusecalibrationgasthathaspasseditsexpirationdate.
AlwaysuseaGDSCorpcalibrationcupthatcompletelysurroundsthesensorhead.
BesuretouseZEROAIR,amixtureof21%oxygenand79%nitrogen,asazeroreferenceunlessyouare
certainthatnotargetgasexistsinthearea.Ambientgasmayresultinan‘elevatedzero’conditionthat
willcauseaFAULTtooccuroncetheambientgasisnolongerpresent.
GDSCorprecommendsusingaspangasthatisbetween25%and75%offullscale.GDSCorpdoesnot
recommendusingfullscaleasthespansetpoint.
Alwayscalibrateanewsensorbeforedependingonthedeviceforpersonnelorequipmentsafety
Calibrateonaregularschedule.GDSCorprecommendsafullcalibrationevery3months,withperiodic
‘bumptests’onamorefrequentbasistoensurethatthesensorhasnotbeenaffectedbytemperature
extremesorthepresenceofincompatiblegases.
Ingeneral,calibrationinvolvesapplyingazeroreferencegasandtellingthereceivingdevicetoacceptthatoutput
as‘zero’,followedbytheapplicationofaspanreferencegasandthentellingthereceivingdevicetoacceptthe
newoutputas‘spanoncetheoutputhasstabilized.Thisisgenerallyperformedbytwopersons,oneatthesensor
transmitterandoneatthereceivingdevice.Actualprocedures,timeintervalsandtechniquesforindicatingzero
andspanvaluesdependonthespecificreceivingdevice.AllGDSCorpdisplayandalarmcontrollersprovidethe
necessarylocalcalibrationcapability.
GENERALIZEDCALIBRATIONPROCEDURE
Beforebeginningcalibration,makesureyouhavethefollowingitems:Acylinderofcalibrationgas,fixedflow
regulatorandanappropriatecalibrationcupconnectedtotheregulatorviaalengthofflexibletubing.Ifnecessary,
acylinderof‘zeroair’maybenecessaryiftheabsenceoftargetgascannotbeconfirmed.GDSCorprecommends
aflowrateof0.5liters/minute.
InthecaseofPIDsensors,itmaybedesiredtosubstituteasurrogategasforthetargetgas,especiallyifthetarget
gasisdangerousorunavailableinacalibrationgascylinder.Formoreinformationonsurrogategasesandrelative
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 12 [email protected]
responsefactorsforcommonvolatileorganiccompounds,contactGDSCorpforalistofavailablegasesand
responsefactors.
Theactualstepsinvolvedincalibrationvarydependingonthereceivingdevice,butcanbegeneralizedasfollows:
1. SelecttheappropriatechannelonthecontrollerorreceiverandenableCalibrationMode.Thisshould
disablealarmsduringthecalibrationprocess.Makesurethatthecontroller’sCalSpanvaluematchesthe
cylinderofcalibrationgas.
2. ApplyzeroairtothesensorasshowninFig.61orconfirmtheabsenceofanytargetgas.
3. Atthecontrollerorreceiver,pressthe“SetZero”buttontoconfirmthatthecurrentreadingis‘zero’.
4. ApplyspangastothesensorasshowninFig61.
5. Atthecontrollerorreceiver,monitortheoutputuntilitstabilizes.Whenstable,pressthe“SetSpan”
buttontoconfirmthatthecurrentreadingcorrespondstotheSpanvalue.
6. Turnofftheregulatorandremotethecalibrationcupfromthesensorhead.
7. Atthecontrollerorreceiver,exitCalModeandresumenormaloperation.
Figure 5-1: Applying Calibration Gas to GDS-48
CylinderofCalibrationGas
FixedFlowRegulator
CalibrationCup
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 13 [email protected]
6 OPERATIONANDMAINTENANCE
Inthenormaloperatingmode,themillivoltleveloutputcorrespondstothedetectedgasconcentration.Inthe
eventofasignificantgasrelease,theGDS48willindicateanoverrangeconditionifthesensor’soutputcontinues
toincreasebeyondthefullscalevalue.Intheeventthatthesensoroutputdropsbelowzeroduetointerference
gasesorsensorfailure,theoutputwilldroptozero,indicatingaFAULTconditiontotheremotereceiveror
controller.Ifthesensorisremoved,theoutputwillalsodroptozero.
TheGDS48shouldbecheckedregularlyfordamage,wateringressorflamearrestorcloggingduetoexcessivedust
ordirt.Iftheflamearrestorhasbecomecontaminatedbydust,dirtormoisture,removethesensorheadcover
(afterfirstmakingsuretodeclassifythearea)andcarefullycleanwithcompressedair.Useofsolventis
discouragedasremnantsofthesolventmaterialmayaffectthesensor.Therearenouserserviceablecomponents
andmaintenanceislimitedtocleaningand/orsensorreplacement.
SomeGDSCorpcontrollersandgasdetectorsmonitor‘sensorlife’bycalculatingavaluebetween0and100%
basedonthecurrentresponsetocalibrationgasascomparedtotheinitialresponsewhenthesensorwasfirst
installed.Toensurethatthecalculationsareaccurate,pleasemakecertaintofollowthe‘newsensor’installation
instructionsintheappropriatedevicemanual.
SENSORREPLACEMENT
IfasensorshowsFAULT,doesnotrespondtogasorcannolongerbecalibrated,itshouldbereplaced.GDS48
sensortransmittersuseGDSCorptype1095XXsensors,wheretheXXisthegastypeshowninSection3.The
rangevalueshouldalsobespecifiedwhenorderingreplacementsensors.Forexample,areplacementSmartIR
infraredforcombustiblegas,0100%LELwouldbe“109550R0100”.
Toreplaceasensor,reviewFig.61andfollowthesesteps:
1. DeclassifytheareaorremovepowertotheGDS48.
2. Unscrewthesensorheadcover.Ifunabletoopenthecoverbyhand,useaSensorHeadReplacement
Tool(p/n100187).
3. Removetheoldsensorbypullingstraightdown.
NOTE:PULLSTRAIGHTDOWN.DONOTTRYTOUNSCREWTHESENSOR.
4. Carefullyinstallthereplacementsensorbyaligningthearrowonthesensorwiththearrowengravedon
thesensorhead.Pushstraightupuntilthesensorconnectorseatsfirmlyintothesensorconnector.
5. ReinstallthesensorheadcoverbyCAREFULLYscrewingthecoverontothesensorhead.
NOTE:IFTHESENSORFALLSOUTOFTHESENSORHEADDURINGTHISSTEP,ITCANBEDAMAGED.USE
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 14 [email protected]
CAUTIONWHENREINSTALLINGTHESENSORHEADCOVER.
Figure 6-1: Sensor Replacement
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 15 [email protected]
7 SPAREPARTS
GRAYENCLOSURE
YELLOWENCLOSURE
SENSORHEADACCESSORIES
3.5
3.5
8.0
5.5
Enclosure+SensorHead(Nosensor):
200126Fullassemblylesssensor(gray)
Enclosure/JunctionBoxOnly:
200099Grayjunctionboxenclosurew/PCB
SensorHead Only:
100247Remotebridgestylesensor(Type14)
Note:Doesnotincludesensor
Enclosure+SensorHead(Nosensor):
200153Fullassemblylesssensor(yellow)
SensorHead:
100247Toxic(Type14)
Note:Doesnotincludesensor
Sensor:
1095xxGDSCorpbridgesensor
Sensor:
1095xxGDSCorpbridgesensor
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 16 [email protected]

SplashGuardFlowCell
SensorHeadSplashGuard
100198SplashGuard(Fitsallsensorheads)
SensorHeadFlowCell
100205FlowCell(1/8”NPTcompressionfittings)
200205SOther(specify)
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 17 [email protected]
8 DRAWINGSANDDIMENSIONS
Figure 8-1: GDS-48 Yellow Enclosure
5.0”
7.75”
GDS-48 Remote Bridge Sensor Operation and Maintenance Manual, Revision 1.0
GDS Corp Page 18 [email protected]
Figure 8-2: GDS-48 (Gray Enclosure)
3.5”
3.5”
5.5”
8.0”
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10