Frick AcuAir Quantum LX Operating instructions

Category
Thermostats
Type
Operating instructions
OPERATION – SERVICE
(SESSION LEVEL 2)
FRICK® QUANTUM™ LX
AcuAir®
CONTROL PANEL
Version 3.0x
Form S90-512 O (JUL 2006)
File: SERVICE MANUAL - SECTION 90
Replaces: NOTHING
Dist: 3, 3a, 3b, 3c
OPERATION - SERVICE
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 2 OPERATION - SERVICE
Table of Contents
OVERVIEW OF OPERATOR INTERFACE ............................................................................... 4
OPERATOR ACCESS........................................................................................................................4
To Change Setpoints .................................................................................................................................... 4
Menu Structure.............................................................................................................................................. 5
Initial Setup Procedure.................................................................................................................................. 6
GRAPHIC SCREENS ................................................................................................................ 7
OPERATING STATUS .......................................................................................................................7
OPERATING VALUES
User Defined Operating Status ..................................................................................................................... 8
Operating Status 2 ........................................................................................................................................ 9
Defrost......................................................................................................................................................... 11
Desiccant Wheel .........................................................................................................................................12
SAFETIES
Current Safeties .......................................................................................................................................... 13
Safety History..............................................................................................................................................14
SYSTEM STATUS
Trending
Trending Setup ..................................................................................................................................... 15
Real Time Trending .............................................................................................................................. 16
History Trending ...................................................................................................................................17
Ral Time Data Log................................................................................................................................18
History Data Log................................................................................................................................... 19
Maintenance................................................................................................................................................ 20
Event Log .................................................................................................................................................... 21
SETPOINTS
Temperature
Cooling.................................................................................................................................................. 22
Supply Burner....................................................................................................................................... 23
Heating ................................................................................................................................................. 24
Dehumidification
Cooling.................................................................................................................................................. 25
Desiccant Wheel
Wheel/Regen Fan .......................................................................................................................... 26
Regen Burner................................................................................................................................. 27
Supply Air Flow ...........................................................................................................................................28
Defrost
Defrost Setpoints .................................................................................................................................. 30
Defrost Schedule .................................................................................................................................. 31
Scheduling .................................................................................................................................................. 32
PID Setup
Page 1 ..................................................................................................................................................33
Page 2 ..................................................................................................................................................35
Communications ......................................................................................................................................... 36
Auxiliaries
Analog Inputs
Page 1............................................................................................................................................ 38
Page 2............................................................................................................................................ 39
Digital Inputs.........................................................................................................................................40
Digital Outputs ...................................................................................................................................... 41
Panel ........................................................................................................................................................... 42
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 3
CALIBRATION
Temperature................................................................................................................................................ 43
Pressure...................................................................................................................................................... 44
Miscellaneous ............................................................................................................................................. 45
Auxiliaries.................................................................................................................................................... 46
Analog Outputs ........................................................................................................................................... 47
CONFIGURATION
Control
Page 1 .................................................................................................................................................. 49
Page 2 .................................................................................................................................................. 50
Graphics...................................................................................................................................................... 51
Internet ........................................................................................................................................................ 52
Security ....................................................................................................................................................... 53
SESSION ..........................................................................................................................................54
SERVICE
Digital .......................................................................................................................................................... 55
Analog ......................................................................................................................................................... 55
Communications
Log........................................................................................................................................................ 56
Loop-Back Test .................................................................................................................................... 57
Software Maintenance ................................................................................................................................ 58
ABOUT.............................................................................................................................................59
Warnings/Shutdowns Messages...........................................................................................60
Index........................................................................................................................................62
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 4 OPERATION - SERVICE
The AcuAir® Quantum™ LX has the capability of being
modified by the user/owner in order to obtain different
performance characteristics. Any modification to the
standard default settings may have a severe negative
impact on the operation and performance of the
equipment. Any modification to these control settings is
the sole responsibility of the user/owner and Frick®
disclaims any liability for the consequences of these
modifications. It is possible that the modification of these
settings may cause improper operation and performance
that results in property damage, personal injury or death.
It is the responsibility of the user/owner to evaluate and
assess the consequences of their actions prior to
modifying the controls for this unit.
OVERVIEW OF OPERATOR INTERFACE
There are two possible methods of viewing and accessing
the user interface. One of these methods is in the form of
an optional Operator Interface Touch screen, and the
other is in the form of the standard Web Browser.
Web Browser: The Web Browser interface can be
viewed from any Windows® based desktop or laptop
computer, which has access to the network that the
AcuAir® panel is attached to. To change screens,
setpoints, etc., you simply use a mouse and the
keyboard to view and change data.
Touch Screen: This user interface has been
designed to allow an operator to efficiently access and
control the operation of all units from a single access
point. The touch screen control panel is used for
graphic displays. By touching an active area of the
display, a data entry box will appear, allowing the
operator to enter different setpoint values, via a
keyboard overlay, that will appear on the screen:
Keyboard Overlay (Touch screen only)
OPERATOR ACCESS
Operator access to this system is through various screens.
A screen is the physical representation of data on the
display. Icons have been used to help an operator quickly
identify functions. An icon is a small graphic symbol
representation. Each screen has a title area. The title is
descriptive of the screen. The current date and time is
shown in this title area. The day of the week, Sunday
(Sun.) through Saturday (Sat.) is displayed. The month of
the year from January (Jan.) to December (Dec.) is
displayed. The day of the month from 1 to 31 and the year
from 0001 to 9999 is displayed. The time displayed is the
current time in 24 hours (military) format. The hours,
minutes and seconds are displayed.
Some screens are for informational purposes only, and
cannot be modified. These screens typically show analog
values such as temperature and humidity, which are
strictly functions of an associated sensor, and as such,
cannot be modified. Other screens show setpoint values
that allow the operator to change, in order modify the units
operating characteristics. For easier viewing, related
information is separated into boxes. To further assist the
operator, an on-line help is provided. Sometimes
selections appear differently (a box may be dimmed) to
indicate that the feature is unavailable.
TO CHANGE SETPOINTS
The setpoints define the operation and limits of each air
unit. Adjustable setpoints are setpoints that an operator
can easily change in the field. These setpoints are stored
in EPROM (non-volatile memory).
NOTE: Adjustable Setpoints are not lost after power is
interrupted. However, we suggest that a list of Adjustable
Setpoints be recorded and stored safely to facilitate
reentry, in case there is a need to return to the original
settings.
1. The data entry fields are identified by a black box
with a white interior. The data is shown in black
text. When on a screen that has adjustable
setpoints, select the setpoint box that you wish to
modify (either by touching that box if a touch
screen, or selecting it with a mouse for a web
browser). Once the data field has been selected,
the background turns blue, and the text turns
white.
2. The current value of that setpoint is shown. Use
the keyboard to enter the new value. Typing a
new value will completely erase the old value.
3. Press the keyboard [ENTER] key to input the
new data in the data entry field and to move to
the next data entry field.
4. If the data entered into the setpoint box is valid,
then once you have press the keyboard [ENTER]
key, the [SUBMIT] box in the lower left hand side
of the viewing screen will turn from a grey
background, to a red background. Press the
[SUBMIT] button to load the changed setpoint to
the controller.
5. If the value is out of bounds, an error message
box displays the proper range of values. Press
the [OK] button to acknowledge the error
message. Re-enter the correct value.
When finished making any changes to the data on an
adjustable setpoint display press the [SUBMIT] key to
accept all changes.
Warnin
g
!
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 5
MENU STRUCTURE
The above graphic represents the menu structure, or tree,
of the AcuAir® Quantum™ LX screens. Refer to this tree
when accessing the various screens. Please note that this
screen list is complete, and that certain screens may not
be available as shown here, depending upon the enabled
options.
Home
Operating Values…
Safeties…
System Status…
Setpoints…
Calibration …
Configuration…
Session
Service …
Help
About
Trending …
Maintenance
Event Log
User Defined
Operating Status 2
Defrost
Desiccant Wheel
Current
Hi
s
t
o
r
y
Temperature …
Dehumidification …
Supply Air Flow
Defrost …
Scheduling
PID Setup …
Communications
Auxiliaries …
Panel
Digital
Analog
Communications Log
Communications Loop Back Test
Software Maintenance
Temperature
Pressure
Miscellaneous
Auxiliaries …
Analo
g
Out
p
uts
Control …
Graphics
Internet
Digital I/O …
Security
Trending Setup
Real Time Trending
History Trending
Real Time Data Log
History Data Log
Page 1
Page 2
Page 3
Cooling
Supply Burner
Heating
Cooling
Desiccant Wheel
Page 1
Page 2
Defrost Setpoints
Defrost Schedule
Analog Inputs …
Digital Inputs
Digital Outputs
Page 1
Page 2
Page 1
Page 2
Page 1
Page 2
Wheel / Regen Fan
Regen Burner
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 6 OPERATION - SERVICE
INITIAL SETUP PROCEDURE
The following is a basic guide to unit setup.
1. Configuration is performed first. Although there
are four different Configuration screens, only the
Control Configuration needs to be setup for unit
operation.
To gain access to Control Configuration, User
Level 2 must be set. The following items are
setup on the two Control Configuration pages:
Mode Configuration
Control Temperature
Control Source
Cooling
Supply Burner
Heating
Dehumidification
Damper
Exhaust
Supply Fan
Room Pressure
Suction
Pre-Coil Override
Discharge Temperature
Defrost
Defrost Initiation
Air Defrost
Suction Valve
Smoke Detector
2. Setpoints are established next. Each unit must be
setup to the customer specific control features
and options to be used by a unit controller board.
This setup should not need to be changed by
operators. Setpoints are intended to be accessed
and performed only by a Factory Representative
or Distributor. Only those setpoints that will be
utilized for unit operation need be set. The
following is the list of available setpoint screens:
Temperature
Cooling
Burner Supply
Heating
Dehumidification
Cooling
Desiccant Wheel
Wheel / Regen Fan
Regen Burner
Supply Air Flow
Defrost
Defrost Setpoints
Defrost Schedule
Scheduling
PID Setup
Page 1
Page 2
Communications
Auxiliaries
Analog Inputs
Page 1
Page 2
Digital Inputs
Digital Outputs
Panel
3. Calibrate the control devices. Each sensor or
transducer that is utilized by the unit must have
its operating characteristics defined. This is
where the controller is told what each devices
high and low operating ranges are, as well as
offsets. The offsets are used to fine tune the
device with reference to a known external
calibration device:
Temperature
Pressure
Miscellaneous
Auxiliaries
Analog Outputs
4. From Security Setup, establish the desired
access rights of the operators.
The panel now provides quick access to the most
important information and controls of the units and their
subsystems.
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 7
- GRAPHIC SCREENS -
OPERATING STATUS
The most important information about the unit is displayed
here. In the middle of the screen is a diagram of an AcuAir® air
handling unit that shows the current state of the unit. The
Graphic Simulation shown on the screen will vary depending
upon the installed options. The following items may be shown:
The supply fan and both exhaust fans spin.
A flame is displayed when the burner is on.
The cooling coils are colored blue when they are on
and white when they are off.
The following information is shown on this screen:
DATE - The actual date will be displayed in this box. The
date must first be set correctly on the Configuration screen.
Once set, the date will be automatically adjusted for at the
end of each month, much like the calendar feature of most
modern watches. The primary use of the date feature is to
provide a date stamp for Warnings and Shutdowns.
TIME - The actual time will be displayed in this box. The time
must first be set correctly on the Configuration screen. The time
will also need to be adjusted for those locations which observe
Daylight Savings Time. The primary use of the time feature is to
provide a time stamp for Warnings and Shutdowns.
SCREEN TITLE - This is the title for the screen that is
showing. Each screen will have a title. The Quantum™ LX
manuals will extensively refer to screens by these names.
When referred to in these manuals, screen names will be
shown in bold italic print, such as Operating Status.
MODE OF OPERATION – The present mode of the
unit, either Cleanup or Process.
Process 1 and Process 2 – The unit is
maintaining optimum air conditions for
processing product.
Cleanup - The unit is modifying air
conditions to support the cleanup procedure.
PROCESS ROOM READINGS – Values related to
current mode will be shown here:
Room Air Temperature
Room Air Humidity
Room Pressure
STATUS BOX
Off – The unit is neither running nor is starting.
Running – The unit is in a normal run
condition, air flow has been detected.
Starting - The unit has turned on but air flow
has not been detected.
SETPOINT VALUE - This is the setpoint maintained
by the control.
ACTUAL VALUE - The actual reading of the
temperature that was chosen as the control input.
ID - The number that has been assigned to this
particular unit on the Communications Setup screen.
RUN HOURS – The total number of hours that the Air
Handler has run since the unit was installed.
ALARM MESSAGE - Warnings and Shutdown
messages are displayed in the lower left corner of the
screen. This area will be blank if there are no current
Warnings or Shutdowns.
ANALOG READINGS BOX - The following analog
input readings are possible. They are shown if they
were enabled during setup:
Outside Air Temperature
Discharge Air Temperature
Outdoor Air Damper
Screen Title
Analog
Readin
g
s
Time
Graphic
Simulation
Date
Process Room
Readings
Panel ID of the
unit being
dis
p
la
y
ed
Status Box
Unit
Run Time
Mode of
O
p
eration
Setpoint
Value
Actual
Value
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 8 OPERATION - SERVICE
OPERATING VALUES – USER DEFINED OPERATING STATUS
SCREEN NAME: User Defined.
ACCESSING:
DESCRIPTION: The purpose of this screen is to allow the user to assign additional analog channels to be more readily
viewable. Since the main Operating Status (Home) screen is capable of only showing a limited number of pre-assigned
analog values, it may be desirable for the user to have a method of viewing additional information that they can select, on a
common screen. They may even select values that are already being displayed on the Operating Status screen, as well
as values that are not shown there.
This screen is provided to allow the user to view up to 20
different analog channels of their choosing.
As an example of how this screen works, assume that in
addition to the data that is shown on the Operating Status
screen, the user would like to monitor the Outside Air
Temperature, Room Air Humidity and Pre-coil Air
Temperature, all on the same screen (this one). Notice
that Outside Air Temperature and Room Air Humidity are
already shown on the Operating Status (Home) screen,
but the Pre-coil Air Temperature is shown on the
Operating Status 2 screen. In order to set this screen up
to show these three values, the user would highlight the
Enable User Defined Channel 1 (or whatever channel they
wish to use), by selecting it with the mouse. Once the box
is highlighted, click on it to cause the possible settings for
the channel to appear. Use the mouse to scroll through the
list. When the selection that you want to use has been
highlighted, click on it to select it. Once selected, a value
will appear to the right of the list, which corresponds to the
analog value for that channel.
The following selections may be shown on this screen:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1
User defined analog input #2
User defined analog input #3
User defined analog input #4
User defined analog input #5
User defined analog input #6
User defined analog input #7
User defined analog input #8
User defined analog input #9
User defined analog input #10
User defined analog input #11
User defined analog input #12
User defined analog input #13
User defined analog input #14
User defined analog input #15
User defined analog input #16
User defined analog input #17
User defined analog input #18
User defined analog input #19
User defined analog input #20
None
O
p
eratin
g
ValuesUser Defined
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 9
OPERATING VALUES – OPERATING STATUS 2
SCREEN NAME: Operating Status 2.
ACCESSING:
DESCRIPTION: The Operating Status 2 screen shows additional unit information.
The Operating Status 2, displays additional information
that cannot be shown on the first Operating Status
screen. Along the sides of the page are labels identifying
the various areas of the screen.
The following information is shown on this screen:
DATE - The actual date will be displayed in this box.
The date must first be set correctly on the
Configuration screen. Once set, the date will be
automatically adjusted for at the end of each month,
much like the calendar feature of most modern
watches. The primary use of the date feature is to
provide a date stamp for Warnings and Shutdowns.
TIME - The actual time will be displayed in this box.
The time must first be set correctly on the
Configuration screen. The time will also need to be
adjusted for those locations which observe Daylight
Savings Time. The primary use of the time feature is
to provide a time stamp for Warnings and Shutdowns.
SCREEN TITLE - This is the title for the screen that is
showing. Each screen will have a title. The
Quantum™ LX manuals will extensively refer to
screens by these names. When referred to in these
manuals, screen names will be shown in bold italic
print, such as Operating Status.
ID - The number that has been assigned to this
particular unit on the Communications Setup screen.
RUN HOURS – The total number of hours that the Air
Handler has run since the unit was installed.
WARNING/SHUTDOWN STATUS BOX - The
Warning/Shutdown Status is displayed below the
Mode of Operation status box. This status box is
blank with no message if there are no warnings or
shutdowns present.
If a Warning or Shutdown occurs, a message will be
shown, identifying the type of warning or shutdown.
The definitions for the two types of messages are as
follows:
WARNING - A specific warning message will be
shown when a warning is present. A warning is a
condition that requires operator
acknowledgement but allows the Unit to continue
to run if it is already running. A Warning message
indicates that a warning setpoint has been
reached, or exceeded.
SHUTDOWN - This specific shutdown message
will be shown when a shutdown is present. A
shutdown is a condition that requires an operator
to acknowledge, and causes the Unit to shut
down. A Shutdown message indicates that a
shutdown setpoint has been reached, or
exceeded.
To clear a Warning or Shutdown, the operator must
access the Current Safeties screen, and
O
p
eratin
g
ValuesOperating Status 2
Temperature
Readings
Screen Title
Additional
Analog
Readings
I/O
Status Box
Time
Run Status
Run Time
Date
Setpoint
Value
Mode of
Operation
Panel ID
Actual
Value
Warning /
Shutdown
Status
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 10 OPERATION - SERVICE
acknowledge the Warnings/Shutdowns by pressing
the [Clear Safeties] button. If the conditions that
originally caused the Warning or Shutdown have not
been corrected, the Warning or Shutdown will
continue to re-occur until the problem has been
identified and corrected.
I/O STATUS BOX:
The present operating status of the digital I/O is shown.
One of the following messages is displayed:
On – The channel is energized or turned on.
Off - The channel is de-energized or turned off.
The following inputs are shown in the first block (if they
were enabled during the board setup).
Supply Fan Motor
Supply Air Flow Switch
Exhaust Fan #1
Exhaust Fan #2
Unit High Pressure
Cooling Stage #1
Cooling Stage #2
Cooling Stage #3
Cooling Stage #4
Heating
Supply Burner
Supply Burner Status
Supply Flame Failure
Supply Burner Safeties
Smoke Detector
Remote Start/Stop
Remote Process/Cleanup
Remote Process 1/Process 2
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 11
OPERATING VALUES – DEFROST
SCREEN NAME: Desiccant Wheel.
ACCESSING:
DESCRIPTION: The Defrost screen shows information pertaining to Defrost.
This screen is for informational purposes only. There are
no setpoints or data to be modified from here, only viewed.
The status of the following conditions can be viewed here:
Defrost
Stage
Coil
Stage Time Remaining
Initiated By
Demand Defrost
Cooling 1
Hot Gas 1
Cooling 2
Hot Gas 2
Cooling 3
Hot Gas 3
Cooling 4
Hot Gas 4
Suction 1
Bleed 1
Suction 2
Bleed 2
Suction 3
Bleed 3
Suction 4
Bleed 4
O
p
eratin
g
ValuesDefrost
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 12 OPERATION - SERVICE
OPERATING VALUES – DESICCANT WHEEL
SCREEN NAME: Desiccant Wheel.
ACCESSING:
DESCRIPTION: The Desiccant Wheel screen shows information relating to operation of the Desiccant Wheel.
This screen is for informational purposes only. There are
no setpoints or data to be modified from here, only viewed.
The status of the following conditions can be viewed here:
Desiccant Wheel
Status
Input
Regen Fan Status
Regen Burner
Status
Control Input
Burner Output
Command
Room Air Humidity
Command
Input
Setpoint
Pre-Wheel Regen Air Temperature
Command
Input
Setpoint
Post-Wheel Regen Air Temperature
Command
Input
Setpoint
O
p
eratin
g
ValuesDesiccant Wheel
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 13
SAFETIES - Current Safeties
SCREEN NAME: Current Safeties.
ACCESSING:
DESCRIPTION: The Current Safeties screen shows the Warnings and Shutdowns that have recently occurred (up to 50).
When a warning or shutdown is triggered, a blue descriptive message shows on this screen. The date and time of the
warning or shutdown occurrence is shown to the right of its description. The most recent message will appear on the top
line of the screen with the oldest appearing at the bottom. When a Warning or Shutdown is logged to this screen, it will
also be logged to the Safety History screen.
The following Current Safeties screen key is provided:
[Clear Safeties] - Selecting this key will clear all
warnings and/or shutdowns from this screen. This will
also place a date/time stamp for the corresponding
entry on the Safety History screen showing that the
particular Warning or Shutdown was cleared. Clearing
the entry on the Current Safeties screen, will not
clear it from the Safety History screen.
To resume normal operation it will be necessary to go
through the following steps:
1. Correct the condition(s) causing the warning.
2. Press the [ALARM SILENCE] key. (This action
may precede correcting the condition(s) causing
the warning). Or, go to step 3.
3. To clear or reset the Warnings/Shutdowns
screen and turn off any warning annunciation
device, from the screen, press the [Clear
Safeties] key. This will also clear the WARNING
or SHUTDOWN message from the Operating
Status screen.
4. If the conditions causing the warning have not
been corrected or a new fault has occurred, a
new WARNING or SHUTDOWN message will
appear. The Safety History screen keeps a
record of the warnings and shutdowns. This
information will help troubleshoot persistent
operational problems.
Refer to the Warnings/Shutdowns Message section for a
list of all the possible conditions.
SafetiesCurrent
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 14 OPERATION - SERVICE
SAFETIES - Safety History
SCREEN NAME: Safety History.
ACCESSING:
DESCRIPTION: The Safety History screen shows the warnings and shutdowns that have recently occurred (up to 50
maximum). When a warning or shutdown is triggered, a blue descriptive message shows on this screen. The date and
time of the warning or shutdown occurrence is shown to the right of its description, followed by the date and time that the
safety was cleared. The most recent message will appear on the top line of the screen with the oldest appearing at the
bottom.
It is possible to view the conditions that existed on the
Operating Status screen at the exact moment that a
condition occurred. Use the mouse to select (highlight) a
warning or shutdown and then click on it to view its
associated Freeze (Operating Status) screen.
Freeze Screen Description
This Freeze screen provides a snapshot of the values that
were current at the time of the latest shutdown. The
information on the Freeze screen can help the user to
identify the cause of a fault, which occurred when no one
was present. The Freeze screen freezes the information
of the Operating Status screen AT THE MOMENT OF A
AIR HANDLER WARNING OR SHUTDOWN. The Freeze
screen has the same appearance and contains the same
information as the Operating Status screen. (For a
description of the information presented by the Freeze
screen, refer to the Operating Status screen). The
Freeze screen will retain the information generated by a
warning or shutdown. The last fifty warnings/shutdowns
Freeze screens are saved. This data is saved during a
power outage.
Safeties History
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 15
SYSTEM STATUS - Trending - Trending Setup
SCREEN NAME: Trending Setup.
ACCESSING:
DESCRIPTION: This is the Trending Setup screen. Up to eight channels can be monitored in real time trending, and up to
eight channels monitored in history trending.
Real Time Trending - is a method by which the user can
set the Quantum™ LX to map real-time events to a
graphic chart format. Using this feature allows for a live
snap-shot of recent unit process characteristics, such as
temperature, pressure and humidity readings. The events
that occur will scroll across the screen from left to right, at
a speed that is determined by the recording interval. Real
Time trending information is also stored to a log file, which
provides a time/date stamp for each of the selected
channels, as well as the value of the reading for that
channel. This log file can be viewed on the Real Time
Data Log screen. Trending data is lost upon power cycle.
The following setpoints are provided:
Real Time Recording Interval – The time interval
that defines how often the real time trending data
values are updated. This value may be set for any
time duration between 1.0 second and 86,400.0
seconds (24 hours).
History Trending - is a method by which the user can set
the Quantum™ LX to record historical events to a graphic
chart format. This feature is similar to Real Time trending,
except that the data points can be set separately, the rate
at which the graphic chart is updated can be set to a
different rate, and the data is not lost at power cycle. Using
this feature allows for the recording of recent event
characteristics, such as temperature, pressure and
humidity readings. The events that occur will scroll across
the screen, at a speed that is determined by the recording
interval.
History Recording Interval – The time interval that
defines how often the history trending data values are
updated. This value may be set for any time duration
between 1.0 minute and 60.0 minutes (1 hour).
To program this screen with the data you wish to trend,
highlight the Enable Real Time Trend Channel 1 (or
whatever channel you wish to use), by selecting it with the
mouse. Once the box has been selected, a drop down
menu will appear for that channel. On the right hand side
of the drop down box will be an arrow. Selecting the arrow
will to cause all the possible settings for the channel to
appear. Use the mouse to scroll through the list. When the
selection that you want to use appears, click on it to select
it. Once selected, the value for this channel will be
automatically trended and shown on the Real Time
Trending graph (or History Trending Graph), as well as on
the Real Time Trending Data Log (Or History Trending
Data Log).
The following screen command keys are provided:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1-20
System Status… Trending… Trending Setup
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 16 OPERATION - SERVICE
None
When in Remote Mode (not at the panel), the following key
is provided:
Download Data Trending Files – Clicking on this
button initiates a downloading of the Real Time and
History data files from the Quantum™ LX to the
remote computer (the computer that you are
monitoring from). These files can then be imported
into a database such as Excel™.
A window will appear on the computer screen,
showing two files:
Realtimexx.csv
Historyxx.csv
The xx in both of these files will be replaced with the
ID number of the Quantum™ LX. When the files
appear in the screen window, simply right click on
either file, and select from the menu “Save Target
As…”, and save the files to a convenient location. By
using Windows Explorer™, you can then double click
on the file, and it will automatically open the file in
Microsoft Excel™. The data can then be used in
whatever way the user would like.
SYSTEM STATUS - Trending – Real Time Trending
SCREEN NAME: Real Time Trending
ACCESSING:
DESCRIPTION: This is the Real Time Trending screen. This screen will display in a graphical chart format the data values
as selected on the Real Time Trending Setup screen. Each of the possible eight selectable channels will be shown at the
bottom of the screen, each in a different color. The color data values displayed in the chart correspond to the matching color
of the trending channels at the bottom of the screen. A total of 900 Realtime events can be trended. Realtime events are
lost upon each power cycle.
The following are the possible data channels that may be
shown here:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1-20
None
System Status… Trendin
g
Real Time Trending
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 17
SYSTEM STATUS - Trending – History Trending
SCREEN NAME: History Trending.
ACCESSING:
DESCRIPTION: This is the History Trending screen. This screen will display in a graphical chart format the data values
as selected on the History Trending Setup screen. Each of the possible eight selectable channels will be shown at the
bottom of the screen, each in a different color. The color data values displayed in the chart correspond to the matching
color of the trending channels at the bottom of the screen.
History trending saves 2000 recordings of the data items
selected. History data is stored in Flash memory. Flash
memory is non-volatile and all information is retained even
if the power to the panel is lost. The frequency at which
the data is saved can be selected.
The following are the possible data channels that may be
shown here:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1-20
None
S
stem Status … Trendin
g
Histor
y
Trendin
g
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 18 OPERATION - SERVICE
SYSTEM STATUS - Trending – Real Time Data Log
SCREEN NAME: Real Time Data Log.
ACCESSING:
DESCRIPTION: This screen will display in a tabular format, the numerical data values as selected on the Real Time
Trending Setup screen. Each of the possible eight selectable channels will be shown at the bottom of the screen, each in
a different color. The color data values displayed in the chart correspond to the matching color of the trending channels at
the bottom of the screen.
The following are the possible data channels that may be
shown here:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1-20
None
Only eight of these data selections may be activated for
recording at any one time. If eight items are selected, and
you wish to view one more, you will first need to de-
activate one that is already chosen first. Selected data
items will appear with an asterisk (*) in front of the data on
this listing.
S
stem Status … Trendin
g
Real Time Data Lo
g
FRICK® QUANTUM™ LX AcuAir® CONTROL PANEL S90-512 O (JUL 2006)
OPERATION - SERVICE Page 19
SYSTEM STATUS - TRENDING – HISTORY DATA LOG
SCREEN NAME: History Data Log.
ACCESSING:
DESCRIPTION: This screen will display in a tabular format, the numerical data values as selected on the History
Trending Setup screen. Each of the possible eight selectable channels will be shown at the bottom of the screen, each in
a different color. The color data values displayed in the chart correspond to the matching color of the trending channels at
the bottom of the screen.
The following are the possible data channels that may be
shown here:
Outside Air Temperature
Discharge Air Temperature
Room Air Temperature
Return Air Temperature
Pre-Coil Air Temperature
Coil Air Temperature
Room Air Humidity
Room Pressure
Outside Air Damper
User defined analog input #1-20
None
System Status… Trending… History Data Log
S90-512 O (JUL 2006) FRICK® QUANTUM™ LX AcuAir®CONTROL PANEL
Page 20 OPERATION - SERVICE
SYSTEM STATUS - MAINTENANCE
SCREEN NAME: Maintenance.
ACCESSING:
DESCRIPTION: Using this screen, the user can view up to eleven (11) pre-programmed maintenance schedules, as well
as eight (8) user definable maintenance schedules. Each of the user defined schedules may be custom named.
The usage of this screen is that the user can assign up to
nineteen different areas of air handler operation that they
would like to schedule routine maintenance for. As an
example, the above screen shows a row labeled as
General Unit Inspection. The next column (Service Every)
on the same row has a value of 168 Hrs. The last column
(Next Scheduled At) of this row has a value of 100 Hrs.
When the air handler is running, this time value is being
clocked. After 100 Hrs. of run time (the value from the
Next Scheduled At column), a message will be generated
and placed on the Event Log screen. This particular
message will read Maintenance – General Unit Inspection.
This is to notify the operator that it is time to inspect the
unit. At this point, the operator should notify the proper
maintenance personnel that the appropriate maintenance
be performed. The user should access the Event Screen
on a regular basis (perhaps once per week) to review the
information provided there.
Once the message has been entered in the Event Log,
the values for the row will be automatically updated, with
new values as predetermined by an internal programmed
maintenance schedule. The values for the Next Scheduled
at column are based upon the Air Handler Run Time hours
(shown at the bottom of this screen).
At the bottom of the left most column is the user defined
Maintenance Required column. This is where custom
names may be entered for the various items that the user
would like to track.
Modifying numerical values
To modify any of the numerical boxes on this screen,
simply use the mouse key to click in one of the boxes.
When the box that you wish to change is highlighted,
you may enter the new value using the keyboard, then
press the [Enter] key to accept the value.
Modifying Text (User Defined) Boxes
To modify any of the text boxes on this screen, simply
use the mouse to click on the box. When the box that
you wish to change is highlighted, use the keyboard to
enter the desired text. Press the [Enter] key to accept
the text. The user may type in a custom name up to
20 characters long.
The following additional information is provided on this
screen:
Run Hours - The value shown here is the total
number of hours that the air handler blower has
actually been in the running state. This value can be
reset (or changed to any value from 0 to 1,000,000
Hours) from the Panel screen.
System Status… Maintenance
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64

Frick AcuAir Quantum LX Operating instructions

Category
Thermostats
Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI