Frick Quantum AcuAir Control Panel Installation guide

Type
Installation guide
COMMUNICATIONS SETUP
FRICK QUANTUM
ACUair
CONTROL PANEL
VERSION 1.3x
S90-500 CS/APR 2001
File: SERVICE MANUAL - SECTION 90
Replaces: NOTHING (New Manual)
Dist: 3, 3a, 3b, 3c
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 2 ACUair COMMUNICATIONS SETUP
Table of Contents
Setting Up the Quantum for Communication______________________________________________3
Checklist for Setting Up Communication_________________________________________________3
Frick Protocols_____________________________________________________________________4
Quantum’s Protocol Specifications __________________________________________________4
Allen-Bradley Communication _________________________________________________________8
SLC-500 - Suggested Setup_______________________________________________________9
Channel Configuration ___________________________________________________________9
Read Message Setup Example_____________________________________________________9
Write Message Setup Example____________________________________________________10
PLC-5/30 - Suggested Setup _____________________________________________________10
Channel Configuration __________________________________________________________10
Read Message Setup Example____________________________________________________10
Modbus Communication ____________________________________________________________11
Quantum Data Table _______________________________________________________________11
Allen-Bradley and Modbus Data Access_____________________________________________11
Alarms/Shutdowns Message Codes ___________________________________________________42
HyperTerminal Setup_______________________________________________________________42
Converting an RS-232 Serial Port to RS-422 or RS-485____________________________________42
Opto 22 AC7A/B _______________________________________________________________42
Quantum Main Board (Quantum 3) ____________________________________________________43
History and Identification_________________________________________________________43
Com-2 Links (Jumpers)__________________________________________________________44
RS-485 Communications ________________________________________________________46
RS-422 Communications ________________________________________________________46
Warning
The Quantum has the capability of being modified by the user/owner in order to obtain different
performance characteristics. Any modification to the standard default settings may have a severe
negative impact on the operation and performance of the equipment. Any modification to these control
settings is the sole responsibility of the user/owner and Frick disclaims any liability for the
consequences of these modifications. It is possible that the modification of these settings may cause
improper operation and performance that results in property damage, personal injury or death. It is the
responsibility of the user/owner to evaluate and assess the consequences of their actions prior to
modifying the controls for this unit.
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 3
Setting Up the Quantum for
Communication
Data communication to and from the Quantum can be
through a modem, remote data communications terminal,
programmable controller, or leader computer via either
RS-422, RS-232, or RS-485 connections to the Quantum’s
Com-2 port. Reference the “Main Board Communications
Com-2” section for the correct jumpering of RS-422, RS-
232, or RS-485. Also reference the “Quantum Main
Board” section in this manual to identify wiring and
jumpering locations for Comm2.
Following is the RS-422, RS-485, and the RS-232 pin
descriptions for communications port 2 (also referred to as
Com-2 or Comm2):
Quantum Panel
Com-2
RS-422 Pinout
Quantum Panel
Com-2
RS-485 Pinout
1 - RX (Receive) 1 - RX / - TX
2 + RX (Receive) 2 + RX / + TX
3 - TX (Transmit)
4 + TX (Transmit)
Quantum Panel, Com-2 RS-232 Pinout
1 Data Communication Device
2 Data Set Ready
3 Received Data
4 Request to Send
5 Transmit Data
6 Clear to Send
7 Data Terminal Ready
8 Ring Indicator
9 Ground
10 Not Used
Reference the “Quantum Main Board” section in this
manual for the location and positioning of the 10-pin RS-
232 connector.
Following is the pin connections showing how to wire a
standard 9-Pin RS-232 connector directly to the 10-Pin
RS-232 connector on the Quantum:
Note: The TX2 and RX2 are I/O communication activity
lamps on the Quantum Main Processor Board that can be
monitored to see if the Com-2 port is receiving (RX2) and
transmitting (TX2) data.
The use of communication protocols permit data
transmission between devices. Protocol determines how
contact is established and how the query and response
takes place. The information in a message command
requires an identity of the intended receiver, what the
receiver is to do, data needed to perform an action, and a
means of checking for errors.
When using Comm2 for communication, check what
communication protocol, if any, has been selected from
the Panel Setup – “Change Communications” display. For
example; “A-B Comm” should be selected when using
Allen-Bradley’s communication protocol. The baud rate of
Comm2 and the panel ID number are also changed from
this display and should coincide with the setup of the other
device.
Note: The data communication protocols are continuously
being expanded and improved. Therefore, you should
consult Frick Company for the exact details on your
particular unit(s) before developing system software to
interface with the panel.
Checklist for Setting Up Communication
1. Decide which Quantum protocol you can
communicate with and want to use.
2. Setup your device’s communication port for the
Quantum‘s protocol and select a baud rate.
3. Next, setup the Quantum for the desired
communication protocol. Select the protocol from the
Panel Setup – “Change Communications” display.
For example; “A-B Comm” should be selected when
using Allen-Bradley’s communication protocol.
4. Setup the baud rate of Comm2 to coincide with the
setup of the your device’s communication port.
5. Enter the Quantum’s ID. This will be used to identify
commands that are sent to it.
6. Wire to the first panel via RS-232, RS-422, or RS-485
connections to the Quantum’s Com-2 port.
If you are communicating to more than one panel
then you will not be able to use RS-232. You can
however convert RS-232 to either RS-422 or RS-
485 with an adapter card. Reference the
“Converting an RS-232 Serial Port to RS-422 or
RS-485” section for information about an adapter
card.
Reference the “Quantum Main Board” section in
this manual to identify wiring and jumpering
locations for Comm2.
Reference the “Main Board Communications
Links” in this manual for the correct jumpering of
RS-232, RS-422, or RS-485.
7. Send a single command to read data from this
Quantum using it’s ID.
8. Check if you received a data response at your device.
9. Troubleshooting when you don’t receive a data
response:
Check if Comm2 on the “Operating Status”
display is showing “ACTIVE” or “OFF”.
“ACTIVE” is shown only when the Quantum
understands it is receiving a properly
composed message to itself.
Check that the RX2 I/O communication activity
lamp on the Quantum Main Processor Board is
blinking as it receives the instruction from your
device.
A steadily lit RX2 LED or one that isn’t
lighting are signs of improper wiring.
1
6
2
7
3
8
4
9
5
12
DCD DCD
DSR DSR
RXD RXD
RTS RTS
TXD TXD
CTS CTS
DTR DTR
RI RI
COM COM 10
Quantum 10-Pin
Connector
9-Pin
Connector
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 4 ACUair COMMUNICATIONS SETUP
If the RX2 LED is properly blinking, then check if
the TX2 LED is blinking in response.
If the TX2 is not blinking, then check the
communication protocol setup at the panel,
the panel’s ID and the Comm2 baud rate
setting.
If the TX2 is blinking, then check that the
Comm2 communication jumpers are correct.
If you are sure that the wiring and Quantum
setup is correct, then select the [Show
Comms] key from the “Service Screen”
display to see what is being received and
transmitted from Comm2.
Note: A useful tool for troubleshooting is Windows
“HyperTerminal”. Using “HyperTerminal” can help you
determine if you are wired correctly. Reference the
“HyperTerminal Setup” (page 35) section in this
manual.
10. If you properly receive data and you need to
communicate to more than one panel, then setup and
wire to another panel. Reference the wiring diagram
drawings in the back of this manual. Send a single
command to read data from this Quantum using it’s ID
and troubleshoot as above, if necessary.
11. To prevent noise feedback which is possible when
communicating over a long distance, only the last
panel should have the transmit and receive pull-down
for long communications lines jumpered.
Frick Protocols
All commands for Frick protocols must be in ASCII to be
recognized. The data should be setup as an 8 bit Word
with either no Parity or even Parity, and a Stop Bit. The
commands can be in upper or lower case letters. An
ACUair panel with an ID code of [00] is considered
disabled. ID codes from [01] through [99] are valid and
recognized by the microprocessor.
Quantum’s Protocol Specifications
Quantum’s (“$”) protocol commands have been added
specifically for the Quantum. Unless otherwise shown, 9
characters are returned from the Quantum for a data
value. The data value includes two decimal fields and the
first character position is either; “-“ if the value is negative,
or it is “+” if the value is positive. For example, if the
data’s value is 25.5; then the value +00002550 is sent. All
temperatures are in degrees C and all pressures are in
PSIA. A mode such as “Current ACUair Mode” is returned
as an integer value that represents the mode it is in. For
example, a +00000000 is sent if it is in “Process Mode” or
a +00000100 is sent if it is in “Cleanup Mode”. The value
zero +00000000 is used to represent an “OFF” status and
a “DISABLED” option. The value one +00000100, which
is received as a 1, is used to represent an “ON” status and
an “ENABLED” option. Setpoints are only changed if the
value sent is within the acceptable range. The checksum
is the 2 byte hexadecimal sum of each character within the
command or returned answer, excluding the command
type identifier, ”$”. If the command’s checksum is
replaced with “??”, the Quantum returns a response
without using checksum error checking on the received
command. If the Quantum detects a checksum error, a
“N” (Not Acknowledged), the ACUair ID code, “02”,
Carriage return, and Linefeed are returned.
With the ACUair control system, all Unit-specific
setpoints are stored at the GCU board and are only loaded
to the Quantum panel as needed. As a result, delays will
be encountered when reading or writing these setpoints as
the values are sent between the Quantum and GCU
board. To properly read or change setpoints it is
necessary to follow certain procedures. First, the
command should be sent to change the Panel Control
Status to Remote. The Quantum screen will immediately
move to the Unit Overview screen and the Panel Control
Status will be set to Remote. At this point, a command
may be sent to read or write setpoint values. Expect to
wait a second or two while the required values are
downloaded from the GCU board. When reading values
from the GCU that may change periodically, such as the
Alarm List, send the Refresh Setpoints command before
reading the values to verify that current settings are being
read. Also be aware, if a person presses the "Login to
Unit" button on the Quantum, the Panel Control Status will
be set to Manual. This will prevent a remote system from
reading or writing setpoints stored at the GCU board until
the Panel Control Status is reset to Remote.
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 5
The following is a complete list of available “$” command
types:
COMMAND CODE and DESCRIPTION
F1 = Alarms/Shutdowns Annunciation Page 1.
F2 = Alarms/Shutdowns Annunciation Page 2.
F3 = Alarms/Shutdowns Annunciation Page 3.
CA= Clear Alarms
T1 = Read a value from the Table.
CS = Change a setpoint in the Table.
T3 = Change Quantum panel status.
T4 = Reload setpoints from ACUair unit.
I(x) = Unit's Current Status
Z(x) = Unit's Current Status
The following is a detailed description of each command:
RETURN Alarms & Shutdowns - Page 1 data: $01F1
$ Start of command sequence.
01 Quantum ID code.
F1 Failure Annunciation command Page 1.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character
Position Description of returned data
1 “A” Acknowledge
2 “01” Quantum ID code.
4 Message Code 1
7 Date 1 as mm/dd/yy
15 Time 1 as hh:mm:ss
23 Space
24 Message Code 2
27 Date 2 as mm/dd/yy
35 Time 2 as hh:mm:ss
43 Space
44 Message Code 3
47 Date 3 as mm/dd/yy
55 Time 3 as hh:mm:ss
63 Space
64 Message Code 4
67 Date 4 as mm/dd/yy
75 Time 4 as hh:mm:ss
83 Space
84 Message Code 5
87 Date 5 as mm/dd/yy
95 Time 5 as hh:mm:ss
103 Space
104 Message Code 6
107 Date 6 as mm/dd/yy
115 Time 6 as hh:mm:ss
123 Space
124 CS (Checksum followed by Carriage return,
Line feed. )
RETURN Alarms & Shutdowns - Page 2 data:
$01F2
$ Start of command sequence.
01 Quantum ID code.
F2 Failure Annunciation command Page 2.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character
Position Description of returned data
1 “A” Acknowledge
2 “01” Quantum ID code.
4 Message Code 7
7 Date 7 as mm/dd/yy
15 Time 7 as hh:mm:ss
23 Space
24 Message Code 8
27 Date 8 as mm/dd/yy
35 Time 8 as hh:mm:ss
43 Space
44 Message Code 9
47 Date 9 as mm/dd/yy
55 Time 9 as hh:mm:ss
63 Space
64 Message Code 10
67 Date 10 as mm/dd/yy
75 Time 10 as hh:mm:ss
83 Space
84 Message Code 11
87 Date 11 as mm/dd/yy
95 Time 11 as hh:mm:ss
103 Space
104 Message Code 12
107 Date 12 as mm/dd/yy
115 Time 12 as hh:mm:ss
123 Space
124 CS (Checksum followed by Carriage return,
Line feed. )
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 6 ACUair COMMUNICATIONS SETUP
RETURN Alarms & Shutdowns - Page 3 data:
$01F3
$ Start of command sequence.
01 Quantum ID code.
F3 Failure Annunciation command Page 3.
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character
Position Description of returned data
1 “A” Acknowledge
2 “01” Quantum ID code.
4 Message Code 13
7 Date 13 as mm/dd/yy
15 Time 13 as hh:mm:ss
23 Space
24 Message Code 14
27 Date 14 as mm/dd/yy
35 Time 14 as hh:mm:ss
43 Space
44 Message Code 15
47 Date 15 as mm/dd/yy
55 Time 15 as hh:mm:ss
63 Space
64 Message Code 16
67 Date 16 as mm/dd/yy
75 Time 16 as hh:mm:ss
83 Space
84 Message Code 17
87 Date 17 as mm/dd/yy
95 Time 17 as hh:mm:ss
103 Space
104 Message Code 18
107 Date 18 as mm/dd/yy
115 Time 18 as hh:mm:ss
123 Space
124 CS (Checksum followed by Carriage return,
Line feed. )
RETURN DATA VALUE FROM TABLE
$IDT1
$ Start of command sequence.
ID ACUair ID code.
T1 Return the value of a Table address.
0000 Frick Address of first data value in Table
00 Number of subsequent values to return
(up to 25 values can be requested)
CS Checksum
CR Carriage Return
RETURNED ANSWER,
Starting
Character
Position Description of returned data
1 “A” Acknowledge
2 “01” Quantum ID code.
4 Value(s) of requested data.
CS (Checksum followed by Carriage
return, Line feed.)
CHANGE SETPOINT COMMAND: $IDCS
$ Start of command sequence.
ID ACUair ID code.
CS Change Table address’s setpoint value.
0000 Frick Table address of the setpoint.
0000000
00 New setpoint scaled x100.
CS Checksum
CR Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
and 1 “CR”, “LF” if successful.
and 0 “CR”, “LF” if unsuccessful.
CLEAR ALARMS COMMAND: $IDCA
followed by the “CS”,”CR”
RETURNED ANSWER, “A” followed by the “ID”,
“CR”, “LF” if successful.
CHANGE PANEL STATUS COMMAND: $IDT3
$ Start of command sequence.
ID Quantum ID code.
T3 Change Quantum Panel Status
0 Status: 0-Manual, 1-Remote
CS Checksum
CR Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
and 1 “CR”, “LF” if successful.
and 0 “CR”, “LF” if unsuccessful.
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 7
REFRESH SETPOINTS COMMAND: $IDT4
$ Start of command sequence.
ID Quantum ID code.
T4 Reload setpoint from GCU board
0000 Frick Table address of the setpoint.
CS Checksum
CR Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
and 1 “CR”, “LF” if successful.
and 0 “CR”, “LF” if unsuccessful.
REFRESH ALL SETPOINTS COMMAND: $IDT5
$ Start of command sequence.
ID Quantum ID code.
T5 Force all setpoints to be reloaded from
GCU board, as they are being read
CS Checksum
CR Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
and 1 “CR”, “LF” if successful.
and 0 “CR”, “LF” if unsuccessful.
CHANGE STATUS COMMAND: $IDAS
$ Start of command sequence.
ID Quantum ID code.
AS Change Unit Status
0 Unit Id (1-4)
0 Status Command
0 - Stop
1 - Start
CS Checksum
CR Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
And 1 “CR”, “LF” if successful.
And 0 “CR”, “LF” if unsuccessful.
CHANGE MODE COMMAND: $IDAM
$ Start of command sequence.
ID Quantum ID code.
AM Change Unit Mode
0 Unit Id (1-4)
0 Mode Command
0 - Process
1 - Cleanup
CS Checksum
CR Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
And 1 “CR”, “LF” if successful.
And 0 “CR”, “LF” if unsuccessful.
CHANGE CONTROL MODE COMMAND: $IDAC
$ Start of command sequence.
ID Quantum ID code.
AC Change Unit Control Mode
0 Unit Id (1-4)
0 Mode Command
0 - Local
1 - Remote
CS Checksum
CR Carriage Return
RETURNED ANSWER, “A” followed by the “ID”,
And 1 “CR”, “LF” if successful.
And 0 “CR”, “LF” if unsuccessful.
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 8 ACUair COMMUNICATIONS SETUP
RETURN Unit Status - Units1-4 data: $01IA
$ Start of command sequence.
01 Quantum ID code.
I(A-D) Unit Status Command
Unit 1=A; Unit 2=B; Unit 3=C; Unit 4=D
CS Checksum
CR Carriage Return
RETURNED ANSWER,
A Acknowledge
01 Quantum ID code.
I(A-D) Unit Status Command
F Digital Input Channels 1-4 (right to left)
Bit 0 - Air Flow Switch (1)
Bit 1 - Remote Process/Cleanup (2)
Bit 2 - Remote Start/Stop (3)
Bit 3 - Burner Status (4)
F Digital Input Channels 5-8 (right to left)
Bit 0 - Flame Failure (5)
Bit 1 - Aux #1 (6)
Bit 2 - Aux #2 (7)
Bit 3 - Aux #3 (8)
F Digital Output Channels 1-4 (right to left)
Bit 0 - Supply Fan Motor (1)
Bit 1 - Exhaust Fan #1 (2)
Bit 2 - Exhaust Fan #2 (3)
Bit 3 - Burner Command (4)
F Digital Output Channels 5-8 (right to left)
Bit 0 - Cooling Stage #1 (5)
Bit 1 - Cooling Stage #2 (6)
Bit 2 - Spare (7)
Bit 3 - Spare (8)
F Digital Output Channels 9-12 (right to left)
Bit 0 - Alarm (9), Bit 1 - Spare (10)
Bit 2 - Spare (11), Bit 3 - Spare (12)
F Digital Output Channels 13-16 (right to left)
Bit 0 - Spare (13), Bit 1 - Spare (14)
Bit 2 - Spare (15), Bit 3 - Cleanup (16)
000 Analog Output 1- Outside/Return Air Dampers
000 Analog Output 2- Exhaust Command
000 Analog Output 3- Burner Output
000 Analog Output 4- Heat Profile
+000 Analog Input 1 - Outside Air Temperature
+000 Analog Input 2 - Discharge Air Temp.
+000 Analog Input 3 - Room/Return Air Temp
+000 Analog Input 4 - Spare Temperature
000 Analog Input 5 - Damper Position
000 Analog Input 6 - Exhaust Fan 1 Position
000 Analog Input 7 - Exhaust Fan 2 Position
00000 Analog Input 8 - Ammonia Detector
000 Analog Input 9 - Humidity
+000 Analog Input 10 - Room Pressure Sensor
+000 Analog Input 11 - Pre-Heat Air Temperature
0 Unit Status: 0-Off; 1-Running; 2-Starting
0 Unit Air Handling Mode:0-Process; 1-Cleanup
0 Unit Control Mode: 0-Local; 1-Remote
0 Control Value: 0-None; 1-Return Air; etc.
0 Control Setpoint: 0-None; 1-Process; etc.
0 Alarm: 0-None; 1-Alarm; 2-Shutdown
CS Checksum
CR Carriage Return
RETURN Unit Status - Units1-4 data: $01Z1
$ Start of command sequence.
01 Quantum ID code.
Z (1-4) Unit Status Command
Unit 1=1; Units 1,2=2; Unit 1-3=3; Unit 1-4=4
CS Checksum
CR Carriage Return
RETURNED ANSWER,
A Acknowledge
01 Quantum ID code.
Z(1-4) Unit Status Command
F Digital Input Channels 1-4 (right to left)
Bit 0 - Air Flow Switch (1)
Bit 1 - Remote Process/Cleanup (2)
Bit 2 - Remote Start/Stop (3)
Bit 3 - Burner Status (4)
F Digital Input Channels 5-8 (right to left)
Bit 0 - Flame Failure (5)
Bit 1 - Aux #1 (6)
Bit 2 - Aux #2 (7)
Bit 3 - Aux #3 (8)
F Digital Output Channels 1-4 (right to left)
Bit 0 - Supply Fan Motor (1)
Bit 1 - Exhaust Fan #1 (2)
Bit 2 - Exhaust Fan #2 (3)
Bit 3 - Burner Command (4)
F Digital Output Channels 5-8 (right to left)
Bit 0 - Cooling Stage #1 (5)
Bit 1 - Cooling Stage #2 (6)
Bit 2 - Spare (7)
Bit 3 - Spare (8)
F Digital Output Channels 9-12 (right to left)
Bit 0 - Alarm (9), Bit 1 - Spare (10)
Bit 2 - Spare (11), Bit 3 - Spare (12)
F Digital Output Channels 13-16 (right to left)
Bit 0 - Spare (13), Bit 1 - Spare (14)
Bit 2 - Spare (15), Bit 3 - Cleanup (16)
000 Analog Output 1- Outside/Return Air Dampers
000 Analog Output 2- Exhaust Command
000 Analog Output 3- Burner Output
000 Analog Output 4- Heat Profile
+000 Analog Input 1 - Outside Air Temperature
+000 Analog Input 2 - Discharge Air Temp.
+000 Analog Input 3 - Room/Return Air Temp
+000 Analog Input 4 - Spare Temperature
000 Analog Input 5 - Damper Position
000 Analog Input 6 - Exhaust Fan 1 Position
000 Analog Input 7 - Exhaust Fan 2 Position
00000 Analog Input 8 - Ammonia Detector
000 Analog Input 9 - Humidity
+000 Analog Input 10 - Room Pressure Sensor
+000 Analog Input 11 - Pre-Heat Air Temp.
0 Unit Status: 0-Off; 1-Running; 2-Starting
0 Unit Air Handling Mode:0-Process; 1-Cleanup
0 Unit Control Mode: 0-Local; 1-Remote
0 Control Value: 0-None; 1-Return Air; etc.
0 Control Setpoint: 0-None; 1-Process; etc.
0 Alarm: 0-None; 1-Alarm; 2-Shutdown
… *********
Above Data repeated for Units 2, 3, 4
CS Checksum
CR Carriage Return
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 9
Allen-Bradley Communication
To provide for the reading and writing of data to Quantum
panels using Allen-Bradley communication, the Quantum
has an Allen-Bradley DF1 communication driver that
recognizes both half-duplex and full duplex SLC 500
protected typed logical read and write commands. This is
a Leader / Follower multi-drop communication method.
The Quantum talks Allen-Bradley SLC protocol and is
setup to be an Allen-Bradley SLC500 follower station. The
customer’s PLC or DCS must be setup to initiate the
reading and writing of data to a Quantum. The Quantum’s
ID number is used as it’s station address and the target
node. With the AB PLC, the MSG (Message) instruction
is used to send read and write requests. A DCS
(Distributed Control System) will use a SLC 500 DF1
protocol driver to send protected typed logical read and
protected typed logical write requests to a Quantum.
Fifty (50) data elements can be read with one read.
Setpoints are changed by sending a write command to
one element. Be careful not to continuously request
a setpoint change. Keeping the Quantum busy
writing to an individual GCU board will interfere with
the Quantum's polling of all the GCU boards. Control
commands are also sent with a write command. For
more detail and a list of the data, reference the
“Quantum Data Table” section. For details about the
actual protocol, reference the AB publication 1770-6.5.16
“DF1 Protocol and Command Set Reference Manual”.
The Quantum can be connected to the Data Highway (DH)
by wiring the Quantum’s serial port (Com-2) to a serial
device on the DH such as an internal port of a PLC that
supports the Data Highway protocol like the SLC 5/04.
Quantum's can be on a multi-drop link (wired to other
Quantum's). If RS-422 or RS-485 is used as in a multi-
drop link, an adapter card can be used to convert an
RS-232 to an RS-422 or RS-485 serial port.
Because overrun can occur and result in the Quantum
periodically missing characters, the baud rate and
commands should be setup to produce the most desired
throughput. The leader station should have the Stop Bit
set to 1, Parity set to none, Duplicate Detect disabled, and
Error Detect set for BCC.
When communication is between either your programming
software and a Quantum or an Allen-Bradley PLC and a
Quantum on a multi-drop link, the devices depend on a
DF1 Leader to give each of them polling permission to
transmit in a timely manner. As the number of Quantum
followers increase on the link, the time between when
the Quantum is polled also increases. This increase, in
time, may become larger if you are using low baud
rates. As these time periods grow, the timeouts,
such as the message timeout, poll timeout, and
reply timeout may need to be changed to avoid loss of
communication.
ACK Timeout - The amount of time in 20 milliseconds
increments that you want the processor to wait for an
acknowledgment to the message it has sent before the
processor retries the message or the message errors out.
Reply Message Wait Time - Define the amount of time in
20 millisecond increments that the leader station will wait
after receiving an ACK (to a leader-initiate message)
before polling the remote station for a reply. Choose a
time that is, at minimum, equal to the longest time that a
remote station needs to format a reply packet. Some
remote stations can format reply packets faster than
others.
Message Timeout - Defines the amount of time in
seconds that the message will wait for a reply. If this time
elapses without a reply, the error bit is set, indicating that
the instruction timed out. A timeout of 0 seconds means
that there is no timer and the message will wait indefinitely
for a reply. Valid range 0-255 seconds.
Note: Make sure the Allen-Bradley PLC and the
programming software is the most recent software
revision. Some revisions have been made that affect
doing the SLC Typed Logical Read/Write Message
Command.
SLC-500 - Suggested Setup
Channel Configuration
Configure the communication channel – Channel 0:
Current Communication Mode: System
Communication Driver: DF1 Half-Duplex Leader or DF1
Full-Duplex
Baud Rate: 4800 (suggested)
Stop Bits: 1
Duplicate Detect: Disabled
ACK Timeout (x20ms): 30
Message Retries: 3
Parity: None
Station Address (Source ID): 5 (Leader's DF1 selected
ID#)
Error Detect: BCC
RTS off Delay (x20ms): 0
RTS Send Delay (x20ms): 0
Pre-Send Time Delay (x1 ms): 0
Control Line: No Handshaking
Polling Mode: Message Based (do not allow follower to
initiate messages)
Priority Polling Range - Low: 255, High: 0
Normal Polling Range - Low: 255, High: 0
Normal Poll Group Size: 0
Reply Message Wait Time (x20ms): 20
System Mode Driver: DF1 Half-Duplex Leader or DF1 Full-
Duplex
User Mode Driver: Generic ASCII
Write Protect: DISABLED
Mode Changes: DISABLED
Mode Attention Character: \0x1b (default)
System Mode Character: S (default)
User Mode Character: U (default)
Edit Resource/File Owner Timeout (Sec): 60
Passthru Link ID (decimal): 1
Read Message Setup Example
Read/Write Message
Type: Peer-To-Peer
Read/Write: Read
Target Device: 500 CPU
Local/Remote: Local
Control Block: N11:0
Control Block Length: 14
Channel: 0
Target Node: 2 (002) (this is Quantum’s Panel ID)
Local File Address: N12:0
Target File Address/Offset: N10:0
Message Length in Elements: 50
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 10 ACUair COMMUNICATIONS SETUP
Message Time-out (seconds): 15
Write Message Setup Example
Read/Write Message
Type: Peer-To-Peer
Read/Write: Write
Target Device: 500 CPU
Local/Remote: Local
Control Block: N11:0
Control Block Length: 14
Channel: 0
Target Node: 2 (002) (this is Quantum’s Panel ID)
Local File Address: N12:0
Target File Address/Offset: N55:3
Message Length in Elements: 1
Message Time-out (seconds): 15
PLC-5/30 - Suggested Setup
Channel 0 - 25-pin D-shell serial port; supports standard
EIA RS-232C and RS-423 and is RS-422A compatible.
NOTE: Channel 0 is optically-coupled (provides high
electrical noise immunity) and can be used with most
RS-422A equipment as long as:
termination resistors are not used
the distance and transmission rate are reduced to
comply with RS-423 requirements
The PLC-5’s switch 2 is used to select RS-232C, RS-
422A, or RS-423. Channel 0 can be wired for RS-422.
Following is the pin connections showing how to wire the
PLC-5 channel 0 connector to the Quantum for RS-422
communication:
PLC-5 CH0 Quantum Com-2
Pin 2 (TXD.OUT+) Pin 1 (-RX)
Pin 3 (RXD.IN+) Pin 3 (-TX)
Pin 14 (TXD.OUT-) Pin 2 (+RX)
Pin 16 (RXD.IN-) Pin 4 (+TX)
Channel 0 Setup:
Port Maximum Cable
length
RS-232C 15 m (50 ft)
RS-422A 61 m (200 ft)
RS-423 61 m (200 ft)
Important guidelines:
When channel 0 is configured for RS-422A
compatibility, do not use terminating resistors
anywhere on the link.
When channel 0 is configured for RS-422A
(compatible) and RS-423, do not go beyond 61 m
(200 ft). This distance restriction is independent from
the transmission rate.
Channel Configuration
Channel 0 = System (Leader) for half-duplex or
System (Point-To-Point) for full-duplex
Remote Mode Change: DISABLED
Mode attention Char: \0x1b
System mode char: S
User mode char: U
Baud rate: 4800
Stop bits: 1
Parity: None
Station address: 5 (this devices ID#)
Control line: No Handshaking
Reply Msg Wait (20ms):
ACK timeout (20ms):
DF1 retries: 3
Msg appl timeout(30 secs):2
Error detect: BCC
RTS send delay (20ms): 0
RTS off delay (20ms): 0
Polling mode: Message Based (Do Not Allow Follower
to initiate messages)
Leader Message Transmit: Between Station Polls
System (Point-To-Point) additional setup:
Duplicate Detect: OFF
NAK Receive:0
DF1 ENQS:0
Read Message Setup Example
Instruction Entry for Message Block MG14:0:
Communication Command: SLC Typed Logical
Read PLC-5 Data Table Address: N9:3
Size in Elements: 20
Local/Remote: Local
Local Node Address: 004 (Quantum Panel’s ID)
Destination Data Table Address: N10:1
Port Number: 0
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 11
Modbus Communication
The Quantum provides the capability to interface with
other devices that support serial data communications
using the Modbus ASCII protocol. This is a Leader /
Follower multi-drop communication method. The
Quantum is setup to be a Modbus ASCII Follower.
The customer’s PLC or DCS must be setup as a
Modbus ASCII Leader. The Leader initiates the
reading and writing of data to a Quantum. The
Quantum’s ID number is used as the Modbus
Follower address. The Leader uses Function Code 3
(Read Holding Registers) to read data from the
Quantum and Function Code 6 (Load Register) to change
a setpoint or to send a command such as the “Clear
Alarms” command. Fifty (50) data elements can be read
with one read request. The address references are
numbered relative to the Frick addresses in the Quantum
Data Table. For example, to reference Frick data address
128 enter the decimal value 128 for the Modbus
Follower Address. The Quantum only excepts one
value with a Load Register request. Be careful not to
continuously request a setpoint change. Keeping the
Quantum busy writing to an individual GCU board will
interfere with the Quantum's polling of all GCU boards.
For more detail and a list of the data, reference the
“Quantum Data Table” section. For details about the
actual protocol, reference the Gould publication PO-
MBUS-300 Gould Modbus Protocol Reference
Manual”.
Port Configuration of the Leader:
7 Bits per Character
No Parity
1 Stop Bit
No Handshake
Quantum Data Table
Allen-Bradley and Modbus Data Access
Data passed to and from the Quantum are integer values
with one decimal field assumed unless shown otherwise or
the command is sent to select two decimal fields. For
example, if the data’s value is 25.5 then the value 255 is
sent. All temperatures are in degrees C and all pressures
are in PSIA, unless the command is sent to select the
units of the panel. A mode such as “Current ACUair Mode”
is sent as an integer value that represents the mode it is
in. For example, a 0 is sent if it is in “Process Mode”, or a
10 is sent if it is in “Cleanup Mode”. The value zero (0) is
used to represent an “OFF” status and a “DISABLED”
option. The value one (1), which is received as a 10, is
used to represent an “ON” status and an “ENABLED”
option. Only data values that are designated as
setpoints are modifiable. “Read Only” is used to help
identify what data is not modifiable. The setpoint range is
checked to see if it is an allowed setting. If it is not
allowed, the setting is not changed. Reference the “Frick
ACUair Quantum Control Panel Setpoints Data Sheets” for
the setpoint's default settings and ranges. Reference the
“Quantum Data Table” for the address listing and
description of data.
A command has been provided that selects whether data
to and from the Quantum will be integer values with either
one or two decimal fields assumed. Another command has
been provided that selects whether data to and from the
Quantum will be returned in the units that are the default
(pressure in PSIA and temperature in Degree C) or in the
units that are selected to display at the panel.
With the ACUair control system, all unit-specific setpoints
are stored at the GCU board and are only loaded to the
Quantum panel as needed. As a result, delays will be
encountered when reading or writing these setpoints as
the values are transferred between the Quantum and GCU
board. Setpoints whose Frick addresses are in the
following ranges should be considered unit-specific: 200-
569, 700-1069, 1200-1569 and 1700-2069.
To properly read or change the unit-specific setpoints
stored at the GCU, it is necessary to follow certain
procedures. First, a command should be sent to change
the Panel Control Status to “Remote”. The Quantum
screen will immediately move to the Unit Overview display
and the Panel Control Status will be set to Remote. At this
point, a command may be sent to read or write setpoint
values.
When using the Modbus protocol, expect to wait a up to
several seconds while the required values are downloaded
from the GCU board. With the Allen-Bradley protocol, the
first time a value or set of values are requested, no data is
returned, but the data is downloaded from the GCU board.
The same data request should be sent several seconds
later, and the downloaded data will now be returned.
When setpoints are changed, the Quantum will reply to the
Allen-Bradley or Modbus command and then write the
change to the GCU board. After sending a write
command, wait approximately a second before sending
the next command. These operational methods, when
used properly, allow a person to make a large number of
setpoint changes without stalling communications.
When reading values from the GCU board that may
change periodically, such as the Alarm List, send the
Refresh Setpoints command before reading the values to
verify that current settings are being read. Also be aware,
if a person presses the "Login to Unit" button at the
Quantum, the Panel Control Status setting will be set to
Manual. This will prevent a remote system from reading or
writing the setpoints until the Panel Control Status is reset
to Remote.
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 12 ACUair COMMUNICATIONS SETUP
Calculated/Status:
Frick
Address AB
Address Read
Only Description of Data Value Codes
5 N10:5 X Language 0=English
1=Spanish
6 N10:6 X Temperature 0=Fahrenheit
1=Celsius
7 N10:7 X Pressure 0=PSIA
1=PSIG
2=BarA
3=KPAA
4=Bar
8 N10:8 X Baud rate for Comm1 (Read Only)
13 N10:13 X Program Version ####.## x100
14 N10:14 X Battery
15 N10:15 X Board Temperature
21 N10:21 X Screen Saver on / off
22 N10:22 Number of minutes before Screen Saver
enabled
25 N10:25 X External Communications through Comm 1 0=Frick
26 N10:26 X External Communications through Comm 2 0=Frick
1= AB
2 = Modbus
27 N10:27 ID Number
28 N10:28 X Month Version was released
29 N10:29 X Day Version was released
30 N10:30 X Year Version was released
31 N10:31 X Panel Control Status 0=Manual
1=Remote
32 N10:32 History Trending Interval
33 N10:33 Real Time Trending Interval
34 N10:34 X Screen Blink on Shutdown (Enable/Disable)
80 N10:80 X Unit Id Number 1 - 4
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 13
Unit 1 Settings:
Frick
Address AB
Address Read
Only Description of Data Value Codes
100 N10:100 X Unit 1 Id 1
110 N10:110 X Unit 1 Cooling Demand 0 - 100%
111 N10:111 X Unit 1 Heating Demand 0 - 100%
112 N10:112 X Unit 1 Dehumidification Demand 0 - 100%
113 N10:113 X Unit 1 Humidification Demand 0 - 100%
114 N10:114 X Unit 1 Exhaust Demand 0 - 100%
115 N10:115 X Unit 1 Damper Demand 0 - 100%
116 N10:116 X Unit 1 Room Pressure Demand 0 - 100%
117 N10:117 X Unit 1 Pre-Heat Demand 0 - 100%
118 N10:118 X Unit 1 Economizer Demand 0 - 100%
119 N10:119 X Unit 1 Mechanical Cooling Demand 0 - 100%
120 N10:120 X Unit 1 Supply Fan Motor Digital Output 0 - Off, 1 - On
121 N10:121 X Unit 1 Exhaust Fan 1 Digital Output 0 - Off, 1 - On
122 N10:122 X Unit 1 Exhaust Fan 2 Digital Output 0 - Off, 1 - On
123 N10:123 X Unit 1 Burner Command Digital Output 0 - Off, 1 - On
124 N10:124 X Unit 1 Cooling Stage 1 Digital Output 0 - Off, 1 - On
125 N10:125 X Unit 1 Cooling Stage 2 Digital Output 0 - Off, 1 - On
126 N10:126 X Unit 1 Cooling Stage 3 Digital Output 0 - Off, 1 - On
127 N10:127 X Unit 1 Cooling Stage 4 Digital Output 0 - Off, 1 - On
128 N10:128 X Unit 1 Alarm Digital Output 0 - Off, 1 - On
129 N10:129 X Unit 1 Pre-Heat Digital Output 0 - Off, 1 - On
130 N10:130 X Unit 1 Suction Digital Output 0 - Off, 1 - On
131 N10:131 X Unit 1 Hot Gas Digital Output 0 - Off, 1 - On
132 N10:132 X Unit 1 Bleed Digital Output 0 - Off, 1 - On
133 N10:133 X Unit 1 Spare 14 Digital Output 0 - Off, 1 - On
134 N10:134 X Unit 1 Spare 15 Digital Output 0 - Off, 1 - On
135 N10:135 X Unit 1 Cleanup Digital Output 0 - Off, 1 - On
140 N10:140 X Unit 1 Air Flow Digital Input 0 - Off, 1 - On
141 N10:141 X Unit 1 Mode Select Digital Input 0 - Process, 1 - Cleanup
142 N10:142 X Unit 1 On/Off Select Digital Input 0 - Off, 1 - On
143 N10:143 X Unit 1 Burner Status Digital Input 0 - Off, 1 - On
144 N10:144 X Unit 1 Flame Failure Digital Input 0 - Off, 1 - On
145 N10:145 X Unit 1 Demand Defrost Digital Input 0 - Off, 1 - On
146 N10:146 X Unit 1 Auxiliary 1 Digital Input 0 - Off, 1 - On
147 N10:147 X Unit 1 Auxiliary 2 Digital Input 0 - Off, 1 - On
150 N10:150 X Unit 1 Outside Air Dampers Analog Output 0 - 100%
151 N10:151 X Unit 1 Exhaust Dampers Analog Output 0 - 100%
152 N10:152 X Unit 1 Burner Analog Output 0 - 100%
153 N10:153 X Unit 1 Heat Profile Analog Output 0 - 100%
154 N10:154 X Unit 1 Pre-Heat Analog Output 0 - 100%
155 N10:155 X Unit 1 Cooling Analog Output 0 - 100%
156 N10:156 X Unit 1 Spare 1 Analog Output 0 - 100%
157 N10:157 X Unit 1 Humidification Analog Output 0 - 100%
158 N10:158 X Unit 1 Outside Air Temperature Analog Input
159 N10:159 X Unit 1 Discharge Air Temperature Analog Input
160 N10:160 X Unit 1 Return Air Temperature Analog Input
161 N10:161 X Unit 1 Spare Temperature Analog Input
162 N10:162 X Unit 1 Damper Position Analog Input
163 N10:163 X Unit 1 Exhaust Fan 1 Position Analog Input
164 N10:164 X Unit 1 Exhaust Fan 2 Position Analog Input
165 N10:165 X Unit 1 Ammonia Detector Analog Input
166 N10:166 X Unit 1 Return Air Relative Humidity Analog Input
167 N10:167 X Unit 1 Return Air Pressure Sensor Analog Input
168 N10:168 X Unit 1 Coil Air Temperature Analog Input
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 14 ACUair COMMUNICATIONS SETUP
Unit 1 Settings: (Continued)
Frick
Address AB
Address Read
Only Description of Data Value Codes
260 N15:10 X Unit 1 Status 0 - Off
1 - Running
2 - Starting
261 N15:11 X Unit 1 Air Handling Mode 0 - Process, 1 - Cleanup
262 N15:12 X Unit 1 Control Mode 0 - Local, 1 - Remote
263 N15:13 X Unit 1 Control Value 0 - (none)
1 - Return Air Temp
2 - Discharge Air Temp
3 - Humidity
264 N15:14 X Unit 1 Control Setpoint 0-(none)
1-Process Control
2-Cleanup Control
3-Dehumidification
4-Economizer Switchover
5-Cleanup Heating
265 N15:15 X Unit 1 Economizer Enabled 0 - Disabled, 1 - Enabled
266 N15:16 X Unit 1 Cooling Lockout 0 - Disabled, 1 - Enabled
267 N15:17 X Unit 1 Alarm 0 - (none)
1 - Alarm
2 - Shutdown
268 N15:18 X Unit 1 Defrost
269 N15:19 X Unit 1 Defrost Stage 0 - Off
1 - Pump Out
2 - Hot Gas
3 - Bleed
4 - Fan Delay
270 N15:20 X Unit 1 Defrost Initiated By 0 - (none)
1 - Defrost Button
2 - Digital Input
3 - Defrost Schedule
4 - Liquid Counter
280 N15:30 X Unit 1 Cooling Setup 0 - Disabled
1 - Single Stage
2 - Two Stage
3 - Three Stage
4 - Four Stage
5 - Single Modulated Valve
281 N15:31 X Unit 1 Heating Setup 0 - Disabled
1 - Single Stage
2 - Direct Fire
3 - Indirect Fire
4 - Single Modulated Valve
5 - Two-Pos. Valve with Mod. Output
282 N15:32 X Unit 1 Pre-Heat Setup 0 - Disabled
1 - Single Stage
2 - Direct Fire
3 - Indirect Fire
4 - Single Modulated Valve
5 - Two-Pos. Valve with Mod. Output
283 N15:33 X Unit 1 Dehumidification Setup 0 - Disabled
1 - Return Air Dehumidification Control
284 N15:34 X Unit 1 Supply Fan Setup 0 - No Motor
2 - Constant Air Volume
285 N15:35 X Unit 1 Exhaust Fan Setup 0 - Disabled
1 - Two-Stage from Outside Air Damper Position
3 - Modulated from Outside Air Damper Position
286 N15:36 X Unit 1 Temperature Control Setup 0 - Return Air Control
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 15
Unit 1 Settings: (Continued)
Frick
Address AB
Address Read
Only Description of Data Value Codes
287 N15:37 X Unit 1 Damper Control Setup 1 - Mixed Air with Dry Bulb Economizer and
Cleanup
288 N15:38 X Unit 1 Humidification Setup 0 - Disabled
1 - Return Air Humidification Control
289 N15:39 X Unit 1 Suction Setup 0 - Process Mode Always
1 - Process Mode with Liquid
2 - Flooded Coil
290 N15:40 X Unit 1 Ammonia Sensor Setup 0 - Disabled, 1 - Enabled
291 N15:41 X Unit 1 Room Pressure Setup 0 - Disabled, 1 - Enabled
292 N15:42 X Unit 1 Process Heating Setup 0 - Disabled, 1 - Enabled
293 N15:43 X Unit 1 Process Pre-Heat Setup 0 - Disabled, 1 - Enabled
294 N15:44 X Unit 1 Defrost Setup 0 - Disabled
1 - Basic Defrost
2 - Time of Day
3 - Time with Liquid Override
4 - Liquid Counter
Unit 1 Setpoints:
Frick
Address AB
Address Read
Only Description of Data
309 N15:59 Unit 1 Process Control Setpoint
311 N15:61 Unit 1 Cooling Command Proportional Band
312 N15:62 Unit 1 Cooling Command Dead Band
313 N15:63 Unit 1 Cooling Command Integration Time
314 N15:64 Unit 1 Cooling Differential
315 N15:65 Unit 1 Cooling CV Maximum
316 N15:66 Unit 1 Cooling CV Minimum
317 N15:67 Unit 1 Process Cooling Lockout
318 N15:68 Unit 1 Cleanup Cooling Temperature
319 N15:69 Unit 1 Cleanup Cooling Lockout
320 N15:70 Unit 1 Cooling Stage #1 Demand Setpoint
321 N15:71 Unit 1 Cooling Stage #1 Minimum On Time
322 N15:72 Unit 1 Cooling Stage #1 Minimum Off Time
323 N15:73 Unit 1 Cooling Stage #2 Demand Setpoint
324 N15:74 Unit 1 Cooling Stage #2 Minimum On Time
325 N15:75 Unit 1 Cooling Stage #2 Minimum Off Time
326 N15:76 Unit 1 Cooling Stage #3 Demand Setpoint
327 N15:77 Unit 1 Cooling Stage #3 Minimum On Time
328 N15:78 Unit 1 Cooling Stage #3 Minimum Off Time
329 N15:79 Unit 1 Cooling Stage #4 Demand Setpoint
330 N15:80 Unit 1 Cooling Stage #4 Minimum On Time
331 N15:81 Unit 1 Cooling Stage #4 Minimum Off Time
332 N15:82 Unit 1 Cooling Interstage Delay
336 N15:86 Unit 1 Heating Command Proportional Band
337 N15:87 Unit 1 Heating Command Dead Band
338 N15:88 Unit 1 Heating Command Integration Time
340 N15:90 Unit 1 Process Heating Lockout
341 N15:91 Unit 1 Process Heating CV Maximum
342 N15:92 Unit 1 Process Heating CV Minimum
343 N15:93 Unit 1 Heating Differential
344 N15:94 Unit 1 Cleanup Heating Temperature
345 N15:95 Unit 1 Cleanup Heating Lockout
346 N15:96 Unit 1 Cleanup Heating CV Maximum
347 N15:97 Unit 1 Cleanup Heating CV Minimum
350 N15:100 Unit 1 Heating Minimum On Time
351 N15:101 Unit 1 Heating Minimum Off Time
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 16 ACUair COMMUNICATIONS SETUP
Unit 1 Setpoints: (Continued)
Frick
Address AB
Address Read
Only Description of Data
370 N15:110 Unit 1 Pre-Heat Proportional Band
371 N15:111 Unit 1 Pre-Heat Dead Band
372 N15:112 Unit 1 Pre-Heat Integration Time
373 N15:113 Unit 1 Process Pre-Heat Lockout
374 N15:114 Unit 1 Process Pre-Heat Setpoint
375 N15:115 Unit 1 Process Pre-Heat CV Maximum
376 N15:116 Unit 1 Process Pre-Heat CV Minimum
377 N15:117 Unit 1 Pre-Heat Differential
378 N15:118 Unit 1 Pre-Heat Minimum On Time
379 N15:119 Unit 1 Pre-Heat Minimum Off Time
380 N15:120 Unit 1 Cleanup Pre-Heat Lockout
381 N15:121 Unit 1 Cleanup Pre-Heat CV Maximum
382 N15:122 Unit 1 Cleanup Pre-Heat CV Minimum
396 N15:146 Unit 1 Dehumidification Setpoint
397 N15:147 Unit 1 Dehumidification Proportional Band
398 N15:148 Unit 1 Dehumidification Dead Band
399 N15:149 Unit 1 Dehumidification Integration Time
406 N15:156 Unit 1 Humidification Setpoint
407 N15:157 Unit 1 Humidification Proportional Band
408 N15:158 Unit 1 Humidification Dead Band
409 N15:159 Unit 1 Humidification Integration Time
434 N15:184 Unit 1 Exhaust Fan Stage 1 Start Enable
435 N15:185 Unit 1 Exhaust Fan Stage 2 Start Enable
436 N15:186 Unit 1 Exhaust Fan Stage 1 Start
437 N15:187 Unit 1 Exhaust Fan Stage 2 Start
438 N15:188 Unit 1 Exhaust Fan Stage 1 Differential
439 N15:189 Unit 1 Exhaust Fan Stage 2 Differential
446 N15:196 Unit 1 Economizer Lockout
447 N15:197 Unit 1 Room Pressure CV Maximum
448 N15:198 Unit 1 Room Pressure Alarm
449 N15:199 Unit 1 Room Pressure Alarm Delay
450 N15:200 Unit 1 Room Pressure Shutdown
451 N15:201 Unit 1 Room Pressure Shutdown Delay
452 N15:202 Unit 1 Minimum Outside Air Damper Position
453 N15:203 Unit 1 Economizer Switchover
454 N15:204 Unit 1 Economizer Proportional Band
455 N15:205 Unit 1 Economizer Dead Band
456 N15:206 Unit 1 Economizer Integration Time
457 N15:207 Unit 1 Cleanup Outside Air Damper Position
458 N15:208 Unit 1 Economizer Differential
465 N15:215 Unit 1 Room Pressure Setpoint
466 N15:216 Unit 1 Room Pressure Proportional Band
467 N15:217 Unit 1 Room Pressure Dead Band
468 N15:218 Unit 1 Room Pressure Integration Time
469 N15:219 Unit 1 Cleanup Coil Purge Time
470 N15:220 Unit 1 Heat Profile Minimum Damper Position
471 N15:221 Unit 1 Heat Profile CV Minimum
472 N15:222 Unit 1 Heat Profile CV Maximum
475 N15:225 Unit 1 Ammonia Alarm Setpoint
476 N15:226 Unit 1 Ammonia Alarm Delay
477 N15:227 Unit 1 Ammonia Shutdown Setpoint
478 N15:228 Unit 1 Ammonia Shutdown Delay
479 N15:229 Unit 1 Digital Auxiliary 1 Delay
480 N15:230 Unit 1 Digital Auxiliary 2 Delay
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 17
Unit 1 Setpoints: (Continued)
Frick
Address AB
Address Read
Only Description of Data
482 N15:232 X Unit 1 Digital Auxiliary 1 Type
483 N15:233 X Unit 1 Digital Auxiliary 2 Type
488 N15:238 X Unit 1 Analog Auxiliary 1 Type
501 N16:1 X Unit 1 GCU's Comm 2 Enable/Disable
502 N16:2 X Unit 1 GCU's Comm 2 Active/Failed
504 N16:4 X Unit 1 Refrigeration Counter
505 N16:5 Unit 1 Defrost Time 1
506 N16:6 Unit 1 Defrost Time 2
507 N16:7 Unit 1 Defrost Time 3
508 N16:8 Unit 1 Defrost Time 4
509 N16:9 Unit 1 Defrost Time 5
510 N16:10 Unit 1 Defrost Time 6
511 N16:11 Unit 1 Defrost Time 7
512 N16:12 Unit 1 Defrost Time 8
513 N16:13 Unit 1 Defrost Pump Out
514 N16:14 Unit 1 Defrost Hot Gas
515 N16:15 Unit 1 Defrost Bleed
516 N16:16 Unit 1 Defrost Fan Delay
517 N16:17 Unit 1 Refrigeration Counter Setpoint
518 N16:18 Unit 1 Max Days between Defrosts
519 N16:19 Unit 1 Max Consecutive Defrosts
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 18 ACUair COMMUNICATIONS SETUP
Unit 2 Settings:
Frick
Address AB
Address Read
Only Description of Data Value Codes
600 N16:100 X Unit 2 Id 2
610 N16:110 X Unit 2 Cooling Demand 0 - 100%
611 N16:111 X Unit 2 Heating Demand 0 - 100%
612 N16:112 X Unit 2 Dehumidification Demand 0 - 100%
613 N16:113 X Unit 2 Humidification Demand 0 - 100%
614 N16:114 X Unit 2 Exhaust Demand 0 - 100%
615 N16:115 X Unit 2 Damper Demand 0 - 100%
616 N16:116 X Unit 2 Room Pressure Demand 0 - 100%
617 N16:117 X Unit 2 Pre-Heat Demand 0 - 100%
618 N16:118 X Unit 2 Economizer Demand 0 - 100%
619 N16:119 X Unit 2 Mechanical Cooling Demand 0 - 100%
620 N16:120 X Unit 2 Supply Fan Motor Digital Output 0 - Off, 1 - On
621 N16:121 X Unit 2 Exhaust Fan 1 Digital Output 0 - Off, 1 - On
622 N16:122 X Unit 2 Exhaust Fan 2 Digital Output 0 - Off, 1 - On
623 N16:123 X Unit 2 Burner Command Digital Output 0 - Off, 1 - On
624 N16:124 X Unit 2 Cooling Stage 1 Digital Output 0 - Off, 1 - On
625 N16:125 X Unit 2 Cooling Stage 2 Digital Output 0 - Off, 1 - On
626 N16:126 X Unit 2 Cooling Stage 3 Digital Output 0 - Off, 1 - On
627 N16:127 X Unit 2 Cooling Stage 4 Digital Output 0 - Off, 1 - On
628 N16:128 X Unit 2 Alarm Digital Output 0 - Off, 1 - On
629 N16:129 X Unit 2 Pre-Heat Digital Output 0 - Off, 1 - On
630 N16:130 X Unit 2 Suction Digital Output 0 - Off, 1 - On
631 N16:131 X Unit 2 Hot Gas Digital Output 0 - Off, 1 - On
632 N16:132 X Unit 2 Bleed Digital Output 0 - Off, 1 - On
633 N16:133 X Unit 2 Spare 14 Digital Output 0 - Off, 1 - On
634 N16:134 X Unit 2 Spare 15 Digital Output 0 - Off, 1 - On
635 N16:135 X Unit 2 Cleanup Digital Output 0 - Off, 1 - On
640 N16:140 X Unit 2 Air Flow Digital Input 0 - Off, 1 - On
641 N16:141 X Unit 2 Mode Select Digital Input 0 - Process, 1 - Cleanup
642 N16:142 X Unit 2 On/Off Select Digital Input 0 - Off, 1 - On
643 N16:143 X Unit 2 Burner Status Digital Input 0 - Off, 1 - On
644 N16:144 X Unit 2 Flame Failure Digital Input 0 - Off, 1 - On
645 N16:145 X Unit 2 Demand Defrost Digital Input 0 - Off, 1 - On
646 N16:146 X Unit 2 Auxiliary 1 Digital Input 0 - Off, 1 - On
647 N16:147 X Unit 2 Auxiliary 2 Digital Input 0 - Off, 1 - On
650 N16:150 X Unit 2 Outside Air Dampers Analog Output 0 - 100%
651 N16:151 X Unit 2 Exhaust Dampers Analog Output 0 - 100%
652 N16:152 X Unit 2 Burner Analog Output 0 - 100%
653 N16:153 X Unit 2 Heat Profile Analog Output 0 - 100%
654 N16:154 X Unit 2 Pre-Heat Analog Output 0 - 100%
655 N16:155 X Unit 2 Cooling Analog Output 0 - 100%
656 N16:156 X Unit 2 Spare 1 Analog Output 0 - 100%
657 N16:157 X Unit 2 Humidification Analog Output 0 - 100%
658 N16:158 X Unit 2 Outside Air Temperature Analog Input
659 N16:159 X Unit 2 Discharge Air Temperature Analog Input
660 N16:160 X Unit 2 Return Air Temperature Analog Input
661 N16:161 X Unit 2 Spare Temperature Analog Input
662 N16:162 X Unit 2 Damper Position Analog Input
663 N16:163 X Unit 2 Exhaust Fan 1 Position Analog Input
664 N16:164 X Unit 2 Exhaust Fan 2 Position Analog Input
665 N16:165 X Unit 2 Ammonia Detector Analog Input
666 N16:166 X Unit 2 Return Air Relative Humidity Analog Input
667 N16:167 X Unit 2 Return Air Pressure Sensor Analog Input
668 N16:168 X Unit 2 Coil Air Temperature Analog Input
FRICK QUANTUM CONTROL PANEL S90-500 CS
ACUair COMMUNICATIONS SETUP Page 19
Unit 2 Settings: (Continued)
Frick
Address AB
Address Read
Only Description of Data Value Codes
760 N17:10 X Unit 2 Status 0 - Off
1 - Running
2 - Starting
761 N17:11 X Unit 2 Air Handling Mode 0 - Process, 1 - Cleanup
762 N17:12 X Unit 2 Control Mode 0 - Local, 1 - Remote
763 N17:13 X Unit 2 Control Value 0 - (none)
1 - Return Air Temp
2 - Discharge Air Temp
3 - Humidity
764 N17:14 X Unit 2 Control Setpoint 0-(none)
1-Process Control
2-Cleanup Control
3-Dehumidification
4-Economizer Switchover
5-Cleanup Heating
765 N17:15 X Unit 2 Economizer Enabled 0 - Disabled, 1 - Enabled
766 N17:16 X Unit 2 Cooling Lockout 0 - Disabled, 1 - Enabled
767 N17:17 X Unit 2 Alarm 0 - (none)
1 - Alarm
2 - Shutdown
768 N17:18 X Unit 2 Defrost
769 N17:19 X Unit 2 Defrost Stage 0 - Off
1 - Pump Out
2 - Hot Gas
3 - Bleed
4 - Fan Delay
770 N17:20 X Unit 2 Defrost Initiated By 0 - (none)
1 - Defrost Button
2 - Digital Input
3 - Defrost Schedule
4 - Liquid Counter
780 N17:30 X Unit 2 Cooling Setup 0 - Disabled
1 - Single Stage
2 - Two Stage
3 - Three Stage
4 - Four Stage
5 - Single Modulated Valve
781 N17:31 X Unit 2 Heating Setup 0 - Disabled
1 - Single Stage
2 - Direct Fire
3 - Indirect Fire
4 - Single Modulated Valve
5 - Two-Pos. Valve with Mod. Output
782 N17:32 X Unit 2 Pre-Heat Setup 0 - Disabled
1 - Single Stage
2 - Direct Fire
3 - Indirect Fire
4 - Single Modulated Valve
5 - Two-Pos. Valve with Mod. Output
783 N17:33 X Unit 2 Dehumidification Setup 0 - Disabled
1 - Return Air Dehumidification Control
784 N17:34 X Unit 2 Supply Fan Setup 0 - No Motor
2 - Constant Air Volume
785 N17:35 X Unit 2 Exhaust Fan Setup 0 - Disabled
1 - Two-Stage from Outside Air Damper Position
3 - Modulated from Outside Air Damper Position
786 N17:36 X Unit 2 Temperature Control Setup 0 - Return Air Control
S90-500 CS FRICK QUANTUM CONTROL PANEL
Page 20 ACUair COMMUNICATIONS SETUP
Unit 2 Settings: (Continued)
Frick
Address AB
Address Read
Only Description of Data Value Codes
787 N17:37 X Unit 2 Damper Control Setup 1 - Mixed Air with Dry Bulb Economizer and
Cleanup
788 N17:38 X Unit 2 Humidification Setup 0 - Disabled
1 - Return Air Humidification Control
789 N17:39 X Unit 2 Suction Setup 0 - Process Mode Always
1 - Process Mode with Liquid
2 - Flooded Coil
790 N17:40 X Unit 2 Ammonia Sensor Setup 0 - Disabled, 1 - Enabled
791 N17:41 X Unit 2 Room Pressure Setup 0 - Disabled, 1 - Enabled
792 N17:42 X Unit 2 Process Heating Setup 0 - Disabled, 1 - Enabled
793 N17:43 X Unit 2 Process Pre-Heat Setup 0 - Disabled, 1 - Enabled
794 N17:44 X Unit 2 Defrost Setup 0 - Disabled
1 - Basic Defrost
2 - Time of Day
3 - Time with Liquid Override
4 - Liquid Counter
Unit 2 Setpoints:
Frick
Address AB
Address Read
Only Description of Data
809 N17:59 Unit 2 Process Control Setpoint
811 N17:61 Unit 2 Cooling Command Proportional Band
812 N17:62 Unit 2 Cooling Command Dead Band
813 N17:63 Unit 2 Cooling Command Integration Time
814 N17:64 Unit 2 Cooling Differential
815 N17:65 Unit 2 Cooling CV Maximum
816 N17:66 Unit 2 Cooling CV Minimum
817 N17:67 Unit 2 Process Cooling Lockout
818 N17:68 Unit 2 Cleanup Cooling Temperature
819 N17:69 Unit 2 Cleanup Cooling Lockout
820 N17:70 Unit 2 Cooling Stage #1 Demand Setpoint
821 N17:71 Unit 2 Cooling Stage #1 Minimum On Time
822 N17:72 Unit 2 Cooling Stage #1 Minimum Off Time
823 N17:73 Unit 2 Cooling Stage #2 Demand Setpoint
824 N17:74 Unit 2 Cooling Stage #2 Minimum On Time
825 N17:75 Unit 2 Cooling Stage #2 Minimum Off Time
826 N17:76 Unit 2 Cooling Stage #3 Demand Setpoint
827 N17:77 Unit 2 Cooling Stage #3 Minimum On Time
828 N17:78 Unit 2 Cooling Stage #3 Minimum Off Time
829 N17:79 Unit 2 Cooling Stage #4 Demand Setpoint
830 N17:80 Unit 2 Cooling Stage #4 Minimum On Time
831 N17:81 Unit 2 Cooling Stage #4 Minimum Off Time
832 N17:82 Unit 2 Cooling Interstage Delay
836 N17:86 Unit 2 Heating Command Proportional Band
837 N17:87 Unit 2 Heating Command Dead Band
838 N17:88 Unit 2 Heating Command Integration Time
840 N17:90 Unit 2 Process Heating Lockout
841 N17:91 Unit 2 Process Heating CV Maximum
842 N17:92 Unit 2 Process Heating CV Minimum
843 N17:93 Unit 2 Heating Differential
844 N17:94 Unit 2 Cleanup Heating Temperature
845 N17:95 Unit 2 Cleanup Heating Lockout
846 N17:96 Unit 2 Cleanup Heating CV Maximum
847 N17:97 Unit 2 Cleanup Heating CV Minimum
850 N17:100 Unit 2 Heating Minimum On Time
851 N17:101 Unit 2 Heating Minimum Off Time
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46

Frick Quantum AcuAir Control Panel Installation guide

Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI