12
Section 4
DISPLAY, BUTTON FUNCTIONS &
ENERGY SAVING CONTROL
Display Panel Simple Start Instructions:
COMP/AGIT Starts agitator after
a 30 second delay.
Compressor starts after a
further 180 second delay
CARB A Switches on the carbonator
ll pump control circuit
CARB B (not applicable to this unit)
CIRC A Starts re-circulation pump
CIRC B (not applicable to this unit)
The LED’s positioned directly above the
buttons are either o , ashing or on
constantly. If the LED is ashing, this
indicates the motor is running. If on
constantly, this indicates the control circuit is
switched on but the motor is on standby.
Example: The CARB A LED is constantly
on, this is indicating the control circuit is
switched on but the carbonator bowl probes
are not calling for the bowl to ll. When the
carbonator bowl probes call for the bowl to
ll the motor will start and the LED will ash.
Energy Saving Mode - Description
The control board monitors the carbonator
ll pump and if a carbonator ll cycle has
not been detected after 30 minutes, energy
saving mode will be entered.
During energy saving mode the Agitator and
re-circulation pump switch o .
The refrigeration control will continue to
operate independently of energy saving
mode, switching on & o , when required, by
the ice bank probe.
The temperature of the re-circulating water
at the point of entering energy saving mode
determines the duration of the energy
saving “o cycle”, either 2 min, 4 min or 6 min
(see detailed description for temperature
thresholds).
At the point of entering energy saving mode
the recirculation water temperature is logged
by the software. This temperature is used as
the re-circ. pump cut in temperature for as
long as the unit stays in energy saving mode.
If the re-circulation temperature is >3.3°C
energy saving will not be entered
Energy savings cycle mode is exited when:
- Any carbonator pump cycle occurs
- Any error code occurs
- Re-circulating temperature exceeds 3.3°C
Control Programming
COMP
AGIT
CARB
A
CARB
B
CIRC
A
CIRC
B
SER
PGM
CIRC
A
CIRC
B
LED Display
17
Section 5
INSTALLATION INSTRUCTIONS
NOTE: The unit should be installed and
serviced by a suitably trained person.
NOTE: Sealed plugs may be tted to new units.
1. Unpack the unit from its transportation
packing and visually check for any signs
of damage.
2. Site the unit in a convenient location in the
cellar or room on a level surface where it is
to be located and make sure that a mains
electricity supply is within 2 meters and
in an area allowing free circulation of air.
The unit should be tted with a correctly
fused and wired 13 amp plug tted with
the correct fuse as below or alternatively a
standard Euro Plug to IEC83:1975.
Fuses for standard UK plug:
Pulsar 60 Integral & Water Cooled
10 AMP FUSE
Pulsar 80 Integral & Water Cooled
13 AMP FUSE
Installation procedure for units with self
priming soda recirculation pumps
3. Connect the dispense head to the unit
using suitable ttings and python,
referring to the connection diagram on
the lid of the cooler and those supplied
with the dispense head.
4. Connect a mains water supply of 2.5 bar
to 4 bar to the tube labelled ‘WATER IN’
(do not turn on yet).
5. Connect all products to the unit as labelled
(do not connect to the syrup containers yet).
6. Connect CO2 gas supply of 5 bar to 6.3
bar to the cooler using the tube labelled
‘CO2 IN’ (do not turn on yet).
7. Fill the water bath with fresh clean COLD
water until the over ow level is reached.
8. Connect the unit to the mains electricity
supply (do not turn on yet).
9. Turn on the CO2 supply and vent
the carbonator bowl using the relief
valve located on the top of the bowl.
Additionally, operate the dispense valve
until the air in the python lines is purged.
10. Turn on the mains water supply.
11. Check for obvious leaks and rectify
before proceeding any further.
12. Ensure that the soda recirculation pump
and carbonator pump are switched o .
13. Switch on the unit at the mains power
supply and allow ice bank to build. Mains
plug must be accessible.
14. Switch on the carbonator pump and
soda recirculation pump.
15. Prime the dispense head by operating
the valves and ensure all pockets of CO2
are removed from system.
16. Reconnect/switch on the soda pump.
17. Connect the syrup containers and operate
dispense valves until syrup is dispensed.
18. Re t the top cover to the base unit.
19. The dispense head can now be brixed
and the system will be ready to use.