Greenheck 477252 MSxx04 & MSxx09 Series External Operating instructions

Type
Operating instructions
Tools Required:
Wrenches: (1)
3
8 in., (1)
7
16 in.
(1) Ratchet with
3
8 in. deepwell socket
(1)
1
8 in. Allen wrench
No. Qty Description
1 1 External mounting bracket
2 1 #10-24 x .375 Shoulder bolt
3 1 #10-24 nut
4 8 1/4 - 20 1/2 Spinlock bolt
5 8 1/4 - 20 Spinlock nut
6 1 Actuator
7 1 Standoff bracket
8 1 Extension pin
9 4 Retaining clip
Safety Warning
Equipment damage or electrical power hazard. Line
voltage can cause death or serious injury and short
equipment circuitry. Disconnect power supply before
installation.
6
4
2
1
3
4
7
5
5
8
9
Without Jackshaft
With Jackshaft
Actuator can be flipped
around to reverse rotation.
Note:
Actuator shaft collar
accepts
1
2 in. (13mm)
diameter shaft
Figure 1: Honeywell MSxx04 & MSxx09 series external mount (exploded view).
®
Honeywell MSXX04, MSXX09 1
®
Document 477252
Honeywell Actuators Direct Drive
MSXX04, MSXX09
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
These instructions apply to the external field installation of Honeywell actuators on Greenheck model VCD control
dampers when they are duct mounted or sleeved.
These models are direct drive actuators that rotate to their energized position when power is applied and spring
return to their fail position when power is disconnected.
Figure 2: Honeywell MS series wiring illustration
Instructions for FATPA Direct Drive
Series
These installation instructions assume the damper is
already mounted in a duct or sleeve with the damper shaft
extending beyond the duct or sleeve a minimum of 6
inches (152mm).
1. INSTALL THE STANDOFF BRACKET
Dampers with a jackshaft
1a. Remove the
1
2 in. (13mm) ball bearing from the
standoff bracket. Mount the stand-off bracket (Item
#7) with [4]
1
4-20 x
1
2 in. (M6 x 12mm) spinlock bolts
and nuts (Items #4 and 5). Orient the stand-off bracket
(Item #7) so the hole is centered on the jackshaft. See
Figure 1, With Jackshaft.
Dampers without jackshaft (Shaft Extension)
1b. Mount the stand-off bracket (Item #7) spanning
across the damper frame flanges. Fasten to the
damper frame with [4]
1
4-20 x
1
2 in. (M6 x 12mm)
spinlock bolts and nuts (Items #4 and 5). Be sure not
to run the screws into the damper linkage, which is
between the flanges.
2. MOUNT ACTUATOR BRACKET
Fasten the actuator bracket (item #1) to the standoff
bracket (Item #7) using [4]
1
4-20 x
1
2 in. (M6 x 12mm)
spinlock bolts and nuts (Items #4 and 5). Use outer
four holes of the actuator bracket (Item #2).
NOTE: The mounting bracket may be attached in three
positions: parallel with the duct, perpendicular up
from the duct, or perpendicular down from the duct.
Choose a position that offers the most clearance for
the application.
3. FAIL POSITION
If fail position is closed, make sure damper blades are
fully close and ensure blade seals are compressed
prior to tightening the actuator clamp to the damper
extension pin or jackshaft.
4. MOUNTING ACTUATOR
Install the actuator (item #6) over the damper drive
shaft and tight against the actuator bracket (Item
#1). Install [1] #10-24 x .375 shoulder bolts (Item #2)
through lugs on actuator and through the holes in the
back of the actuator bracket (Item #1). Secure with [2]
#10-24 nuts (Item #5).
5. Secure the actuator (Item #6) to the drive shaft by
tightening the set screws on the actuator collar.
5. The wiring illustration identifies actuator electrical
requirements and connection (see Figure 2). Wiring
must comply with all applicable electrical codes.
6. Apply power to the actuator. The damper blades
should fully open or close and return to the fail
position when power is disconnected.
M34624
24 VAC
BLACK
RED
GREEN
L1
( )
L2
( )
YELLOW
YELLOW
BLUE
7° AUXILIARY
SWITCH
85° AUXILIARY
SWITCH
BLUE
24 VAC wiring diagram
120 VAC wiring diagram
230 VAC wiring diagram
WHITE
BLACK
GREEN
L1
( )
L2
( )
YELLOW
YELLOW
BLUE
BLUE
7° AUXILIARY
SWITCH
85° AUXILIARY
SWITCH
120 VAC
M34625
M34626
BLUE
BROWN
GREEN
230 VAC
L1
( )
L2
( )
YELLOW
YELLOW
BLUE
BLUE
7° AUXILIARY
SWITCH
85° AUXILIARY
SWITCH
Honeywell MSXX04, MSXX092
®
Power Consumption
Model Volts Running Holding
MS4104 120 18W 9W
MS4109 120 23W 7W
MS4604 230 18W 11W
MS4609 230 23W 7W
MS8104 24 16VA 8VA
MS8109 24 23VA 7VA
Actuator Weight
5 lb. (2.3kg)
Noise Rating
Driving open: Maximum 80 dBA at 1m.
Holding: Maximum 20 dBa at 1m (no audible
noise)
Temperature Ratings
Ambient: 0°F to 130°F (-18°C to 55°C)
Shipping and storage: -40°F to 140°F
(-40°C to 60°C)
Humidity Ratings
5% to 95% RH non-condensing
Environmental Protection Ratings
NEMA 1
IP40
Approvals
Underwriters Laboratories Inc. UL 873 plenum
rating, and UL/cUL
Actuator Timing (Under Load)
Drive open: 15 seconds
Spring close: 15 seconds
FATPA Direct Drive Series
477252 • MSXX04_MSXX09 Series, Rev. 4, January 2019 Copyright 2019 © Greenheck Fan Corporation3
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature
section of the website at Greenheck.com/Resources/Library/Literature.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts : 800.355.5354 • E-mail: [email protected] • Website: www.greenheck.com
Our Commitment
  • Page 1 1
  • Page 2 2
  • Page 3 3