Danfoss EVRF 3-W, NO - 032R9511 Installation guide

Type
Installation guide
INSTRUCTIONS
EVRF 3-W, NO
032R9511
032R9511
RI.3A.G2.02 01-1999
Coil: 10 W a.c. type 018Z
Min. ambient temperature: –40°C (–40 °F)
Max. ambient temperature: +80 °C (+175 °F)
Min. medium temperature: –40 °C (–40 °F)
Max. medium temperature: +130 °C (+265 °F)
Max. working pressure: PB = 28 bar / MWP = 405 psig
Max. opening diff. pressure: MOPD = 25 bar (360 psig)
NO = Normally open
With coil de-energized,
port "In" is open to A and "Out" is closed.
© Danfoss A/S (AC-SP,jp)