Danfoss Menu operation via AKM, Evaporator controller AKC 151R User guide

Type
User guide

Danfoss Menu operation via AKM, Evaporator controller AKC 151R with software version 1.2x can be used together with system software type AKM. It enables you to control cooling and defrosting processes in refrigeration systems. You can use it to set up and adjust various parameters, such as thermostat cut-out and cut-in values, defrost times and temperatures, and fan operation during defrost. The device also features an alarm system to notify you of any issues or malfunctions.

Danfoss Menu operation via AKM, Evaporator controller AKC 151R with software version 1.2x can be used together with system software type AKM. It enables you to control cooling and defrosting processes in refrigeration systems. You can use it to set up and adjust various parameters, such as thermostat cut-out and cut-in values, defrost times and temperatures, and fan operation during defrost. The device also features an alarm system to notify you of any issues or malfunctions.

REFRIGERATION AND AIR CONDITIONING
Evaporator controller
- AKC 151R
Menu operation via AKM
Refrigeration and Air Conditioning Controls
Software version 1.2x
ADAP-KOOL
®
Refrigeration Control systems
2 Menu operation RC.8B.H1.02 © Danfoss 06/2003 AKC 151R Version 1.2x
Menu list This menu function can be used together with system software type AKM. The description is
divided up into function groups that can be displayed on the PC screen. Within each group it
is now possible to show the measured values, or settings. Regarding the use of AKM,
reference is made to the AKM Manual.
Measurements The various measurements can be read directly. If a graphic display of the measurements is
required, up to eight of them can be shown. Select the required measurements and push
“Trend”.
Settings There are four kinds of settings, ON/OFF settings, settings with a variable value, time settings
and “reset alarms”.
Enter the new value or move the sliding scale up or
down. The new value will apply, when “OK” is pushed.
Set the required value and push
“OK”
Application This menu operation (dated June 2003), applies to controller type AKC 151R, code
number 084B6195 with programme version 1.2x.
The operation is divided up into several
function groups. When a selection has
been made, push “OK”, and you may
continue to the next display. By way of
example, “
Thermostat
” has been
selected here.
From the measure line the different
values can be read. The values are
constantly updated.
In the list of settings the set values can
be seen. If a setting has to be changed,
select the parameter and proceed via
“OK”.
Function groups
AKC 151R 1.2x Menu operation RC.8B.H1.02 © Danfoss 06/2003 3
Go through the individual functions one by one and make the required settings. When settings
have been made for one controller, the set values may be used as basis in the other
controllers
of the same type
and
with the same software version
. Copy the settings by using
the copy settings function in the AKM programme, and adjust subsequently any settings where
there are deviations.
NB! If a list is required for noting down the individual settings, a printout can be made of it
with a function in the AKM programme. Read the next section, “Documentation”.
Documentation Documentation of the settings of the individual controllers can be made with the print function
in the AKM programme. Select the controller for which documentation of the settings is re-
quired and select the “Print Settings” function (cf. also the AKM Manual).
Functions Shown below are function groups with corresponding measurements and settings. A printout
of the given settings can be made using the AKM function “Print Settings” (see above).
Alarms
Thermostat
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
CutOut °C Actual thermostat cut-out value
CutIn °C Actual thermostat cut-in value
RunTime Actual thermostat cut-in time or duration of the latest finished cut-in
Settings MainSwitch Main switch: 1: Regulation
0: Controller stopped
-1: Service function
Ther. Mode Thermostat mode
0: Continuous cooling (thermostat not active)
1: Thermostat active
Ther. Sx Definition of thermostat sensor(s)
1: S3 sensor is used
2: S4 sensor is used
3: Weighted value of S3 and S4 is used
CutOut °C Setting of thermostat cut-out value
MUST BE SET.
S4 % S4 contribution to weighted value of S3 and S4
Day/Night Choose day-/night operation function ON/OFF
Dt Night K Night set back value
See page 15.
4 Menu operation RC.8B.H1.02 © Danfoss 06/2003 AKC 151R Version 1.2x
Air temperature control
Measurements AKC Error When "ON", there is an alarm message. See page 15.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
Settings Main Switch Main switch: 1: Regulation
0: Controller stopped
-1: Service function
Alarm Mode Definition of alarm thermostat
0: No alarm thermostat
1: S3 used as alarm sensor
2: S4 used as alarm sensor
3: Thermostat temperature is used as alarm sensor
(see TherAir ).
High Lim°C High air temperature alarm limit (absolute value).
When there is night setback operation, the alarm limit is raised by the night
setback value.
High1Del m Time delay of high air temperature alarm during pull-down.
This value will apply until the actual air temperature has dropped below the
“upper alarm limit”.
Thereafter shift to the time delay “High2Del m”.
High2Del m Time delay of high air temperature alarm during normal regulation.
Low Lim°C Low air temperature alarm limit (absolute value)
Low Del m Time delay for low air temperature alarm
Injection control
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
AKV OD % Actual opening degree
Settings Main Switch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
AKV/EVR Definition of valve type connected to output terminals 14-15
1: AKVA injection valve
2: EVRA solenoid valve
OD % Opening degree of cooling
Start OD % Opening degreee of cooling
Start del. Operating time for "Start OD%" (minutes)
AKC 151R 1.2x Menu operation RC.8B.H1.02 © Danfoss 06/2003 5
Defrost control
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
Def. Cond. Defrost condition
0: Defrost not started 5: Draining of evaporator
1: HP float by-pass 6: Delayed injection
3: Defrost 7: Delayed fan start
8: Start up delay
S5 °C Defrost sensor temperature
DefTime m Actual defrost cut-in time or duration of the latest finished defrosting period.
MDefTime m Average value of the latest 4 defrosting periods.
Settings Main Switch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
Def. Ctrl. Choose defrost function ON/OFF
Man. Def. Manual defrost is activated when ON (changes automatically to OFF)
Hotgas Def Define defrost form
OFF: Electric defrost
ON : Gas defrost
Fan run Choose fan operation during defrost ON/OFF
Temp/Time 1: Temperature stop (time as security)
2: Stop on time
MaxDefTime Max. permissible defrost time in minutes (Security time on Temperature stop)
Def.Stop°C Temperature value of defrost stop
HPbypDel m Setting the time the by-pass valve has to be open at the beginning of a defrost
sequence.
SucV.Del m Setting the time the main valve in the suction line use to close
DrainDel m Delay time when defrost completed. The evaporator is drained of condensed
refrigerant through the drain valve.
Inj.Del m Liquid injection delay time
FanOnDel m Fan start delay time after defrosting
Fan On °C Setting of temperature at fan start after defrost
Fans will start when all S5 temperatures are below the value.
(FanOnDel still remains active as a precautionary measure)
6 Menu operation RC.8B.H1.02 © Danfoss 06/2003 AKC 151R Version 1.2x
Extended defrost control
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
Settings Main Switch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
FanStopS4 Define if there should be fan stop during defrost
ON: Fans stops
Function may only be used if "Fan run" is set ON
FanStop °C Temperature limit for stop of fans
Stops when S4 temperature is higher than “FanStop °C”
Starts when S4 temperature is lower than “FanStop°C” - 2 K
Compr. run Define if compressor must run during defrost.
(Only if “Hotgas Def” = ON)
The compressor output is cut-in during defrost, but open i the periods “Drain
Del m” and “inj.Del.m”.
ON: compressor output is cut-in during the whole defrost
Defrost schedules
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
Settings Main Switch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
No.Per Day Help function for setting of defrost times
The defrost periods are distributed evenly during a defined period of time
within a 24-hour period.
Number of defrosts/24 hours
FirstDef Setting of time the 1st defrost begins
LastDef Setting of time the last defrost begins
Auto Set Transfer the values to the three subsequent defrost programmes.
In pos. ON they are entered in “Schedule 1”, “Schedule 2” and “Schedule 3”.
If the three defrost programmes are not to be identical, corrections
subsequent must be made in the individual programmes.
AKC 151R 1.2x Menu operation RC.8B.H1.02 © Danfoss 06/2003 7
Mon Sched. Choose defrost programme for Mondays
Tue Sched. Choose defrost programme for Tuesdays
Wed Sched. Choose defrost programme for Wednesdays
Thu Sched. Choose defrost programme for Thursdays
Fri Sched. Choose defrost programme for Fridays
Sat Sched. Choose defrost programme for Saturdays
Sun Sched. Choose defrost programme for Sundays
No. Per Day Number of defrosts/24 hours for defrost programme 1
Def1 Sc1 Setting of time the 1st defrost begins
Def2 Sc1 Setting of time the 2nd defrost begins
Def3 Sc1 Setting of time the 3rd defrost begins
Def4 Sc1 Setting of time the 4th defrost begins
Def5 Sc1 Setting of time the 5th defrost begins
Def6 Sc1 Setting of time the 6th defrost begins
Def7 Sc1 Setting of time the 7th defrost begins
Def8 Sc1 Setting of time the 8th defrost begins
No. Per Day Number of defrosts/24 hours for defrost programme 2
Def1 Sc2 Setting of time the 1st defrost begins
Def2 Sc2 Setting of time the 2nd defrost begins
Def3 Sc2 Setting of time the 3rd defrost begins
Def4 Sc2 Setting of time the 4th defrost begins
Def5 Sc2 Setting of time the 5th defrost begins
Def6 Sc2 Setting of time the 6th defrost begins
Def7 Sc2 Setting of time the 7th defrost begins
Def8 Sc2 Setting of time the 8th defrost begins
No. Per Day Number of defrosts/24 hours for defrost programme 3
Def1 Sc3 Setting of time the 1st defrost begins
Def2 Sc3 Setting of time the 2nd defrost begins
Def3 Sc3 Setting of time the 3rd defrost begins
Def4 Sc3 Setting of time the 4th defrost begins
Def5 Sc3 Setting of time the 5th defrost begins
Def6 Sc3 Setting of time the 6th defrost begins
Def7 Sc3 Setting of time the 7th defrost begins
Def8 Sc3 Setting of time the 8th defrost begins
Display/Fan
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
Fan Forced operation of fan outlet
Settings Main Switch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
Disp. Ctrl Choose read-out for display
0: No display function
1: S3 read-out
2: S4 read-out
3: Ther.Air read-out
Offset °C Off-set adjustment of display signal.
Fan On % Setting of the fans’ ON period in percent of the “FanCycl m” time (the function is
only active in the cutout period)
FanCycl m Period time for total ON / OFF time
8 Menu operation RC.8B.H1.02 © Danfoss 06/2003 AKC 151R Version 1.2x
Forced operation
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
Settings Main Switch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
ON-mode Function of controller outputs when "ON-input" (terminals 32 - 33) and “DI-
input” (terminals 40-41)
“ON-input” controls the forced closing function. (OFF: forced closing)
“DI-input” controls the forced cooling function. (ON : forced cooling)
(Please note that the ON mode can be overridden from AKM)
0: “ON-input” not active
“DI-input” has priority
“DI-input”= OFF means normal operation
“DI-input” =ON means forced cooling
1: “ON-input” active and has priority over “DI-input”
In other words, if “ON-input”=OFF this always means forced cooling
whatever the “DI-input”
If ”ON-input”=ON
“DI-input”=OFF means normal operation
“DI-input”=ON means forced cooling
2: “DI-input” has priority over “ON-input”
In other words, if “DI-input”=ON this always means forced cooling
whatever the “ON-iput”
If “DI-input”=OFF
“ON-input”=ON means normal operation
“ON-input”=OFF means forced closing
3: Used for override functions via AKA gateway
OuttputCtrl Fan output function when cooling is forced off
1: Fan outlet is ON
2: Fan outlet is OFF
Forced Cl. Forced closing
ForcedCool Forced cooling
AKC 151R 1.2x Menu operation RC.8B.H1.02 © Danfoss 06/2003 9
Alarm destinations
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
Settings MainSwitch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
Network ON: When alarms are registered via PC or Gateway printer
OFF: When alarms are registered via AKA 21, only
Set the priority for the following alarm texts (choose between 1, 2, 3 or 0. They have the following
meaning:)
1: Alarm at relay output + DANBUSS message
2: DANBUSS message only
3: Alarm at relay output + DANBUSS
message, but the DO2
output on a master gateway will not be activated
0: No alarm and no DANBUSS message
The individual alarms are explained in more detail on page 12
Standby Mode (Regulation has stopped)
ChClock settings (Power failure)
HighAirTem (Air Temp. too high)
LowAirTem (Air temp. too low)
DefPerExce (Defrost period exceeded)
230VDefInp (Wrong defrost demand)
Saux1 Err (Faulty Ssux1 sensor)
Saux2 Err (Faulty Saux2 sensor)
S3 Err (Faulty S3 sensor)
S4 Err (Faulty S4 sensor)
S5 Err (Faulty S5 sensor)
10 Menu operation RC.8B.H1.02 © Danfoss 06/2003 AKC 151R Version 1.2x
Extended functions
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
AccRtime m Accumulated refrigeration time in minutes
AccDTime m Accumulated defrost time in minutes
Settings MainSwitch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
Language Selection of language. One language has been entered in the controller.
0: English
NB! If this setting is changed, another “Upload” must be made of the controller's
data for the AKM programme. You do it this way:
- Select one of the available languages.
- Close the menu
- Proceed to menu “Configuration” - “Advanced Configuration”- “Delete
description file”
- Push file type “Default”
- Select controller's code number and software version
- Push “OK”
- Proceed to menu “Configuration” - “Upload”
- Complete the fields “Network”, “Net configuration” and “AKC description”
- Push “OK”
Texts will now be obtained from the controller in the required language.
Saux1 Corr Correction of signal from "Saux1" sensor
Saux2 Corr Correction of signal from "Saux2" sensor
S3 Corr. Correction of signal from "S3" sensor
S4 Corr. Correction of signal from "S4" sensor
S5 Corr. Correction of signal from "S5" sensor
FanStopS5 Define fan stop function ON or OFF
FanStop °C Temperature limit for fan stop (the fans are stopped when the S5 temperature is
higher than this value. The fans will start again when S5 is lower than
"FanStop°C" - 2K)
Suct.Valve Define suction valve to be open or closes during the thermostat cutout
ResAccTime Counter resettings of accumulated refrigerant and defrost time
AKC 151R 1.2x Menu operation RC.8B.H1.02 © Danfoss 06/2003 11
Service Mode
Measurements AKC Error When "ON", there is an alarm message. See page 12.
RegCond. Regulating condition
0: No cooling
1: Cooling
2: Forced cooling
4: Defrost
5: Start after defrost
6: Forced closing
8: Emmergency cooling (sensor failure)
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
Ther. Air Actual air temperature
Alarm Air Actual air temperature for the alarm function
Saux1 °C Temperature at Saux1 sensor
Saux2 °C Temperature at Saux2 sensor
S3 °C Air temperature at S3 sensor
S4 °C Air temperature at S4 sensor
S5 °C Temperature at defrost sensor
S6 Statement of S6 inlet (terminal 60 - 61)
Def. Start Statement of defrost start signal (terminal 30 - 31)
ON input Statement of forced closing input (terminal 32 - 33)
DI Statement of DI input (terminal 40 - 41)
Fan Statement of fan outlet (terminal 10-11)
HP Bypass Statement of bypass valve (terminal 12-13)
AKV/EVR % Statement of AKV / EVR valve (terminal 14-15)
Suct.Valve Statement of suction valve (terminal 16-17)
Compressor Statement of compressor outlet (terminal 18-19)
AlarmRelay Statement of alarm outlet (terminal 20 - 21)
ON: Relay switch closed (no alarm)
OFF: Relay switch interrupted (alarm)
Defrost Statement of defrost outlet (terminal 22-23)
Settings MainSwitch Main switch: 1: Regulation
0:Controller stopped
-1:Service function
Manual Ctrl. ON: Manual control permitted
PLEASE NOTE! No monitoring
When manual setting has been concluded, the setting must be changed to OFF
Fan Forced operation of fan outlet (terminal 10-11)
HP Bypass Forced operation of bypass valve (terminal 12-13)
AKV/EVR % Forced operation of AKV / EVR valve (terminal 14-15)
Suct.Valve Forced operation of suction valve (terminal 16-17)
Compressor Forced operation of compressor outlet (terminal 18-19)
AlarmRelay Forced operation of alarm outlet (terminal 20 - 21)
ON: Relay switch closed (no alarm)
OFF: Relay switch interrupted (alarm)
Defrost Forced operation of defrost outlet (terminal 22-23)
AKM menu "For DANFOSS only"
This menu contains data and setting values for special internal controller functions.
Do not chage the stated values.
12 Menu operation RC.8B.H1.02 © Danfoss 06/2003 AKC 151R Version 1.2x
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
RC-ET
Alarms
Alarms may be acknowledged one by one by
selecting one, and then pushing "OK". An Alarm
message will now appear, e.g.:
Push "OK" to acknowledge.
The following alarm messages may occur:
Alarm message Meaning Action/cause
S_ Error S_ sensor error Check sensor connection / sensor resistance
Saux_ Error Saux_ sensor error Check sensor connection / sensor resistance
High air temp Too high air temperature
Low air temp Too low air temperature
Low S4 Temp Too low S4 temperature
Max. Def. period exceeded Max. defrosting period Defrosting finished according to time not as selected
exceeded according to temperature
230 Volt on Def. Start input Wrong defrost demand Active defrost signal on terminal 30-31 contrary to just
finished defrosting
Check Clock settings Power failure After power failure, timer must be set.
NB! If Network = ON, resetting will take place automatically
from the gateway
Standby mode Regulation has stopped The Main switch is either set in the position
"Controller stop" or "Service".
The menu display for alarms shows the active alarms. Dots will appear at the top of the menu for as long as
data is being obtained.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Danfoss Menu operation via AKM, Evaporator controller AKC 151R User guide

Type
User guide

Danfoss Menu operation via AKM, Evaporator controller AKC 151R with software version 1.2x can be used together with system software type AKM. It enables you to control cooling and defrosting processes in refrigeration systems. You can use it to set up and adjust various parameters, such as thermostat cut-out and cut-in values, defrost times and temperatures, and fan operation during defrost. The device also features an alarm system to notify you of any issues or malfunctions.