Danfoss Controller type AKC 114G for controlling evaporators. Vers. 1.0x. AKA 21 Installation guide

Category
Thermostats
Type
Installation guide
RC.8A.P1.02 01-2001
Menu operation via AKA 21
Software version 1.0x
Controller for controlling evaporators
AKC 114G
ADAP-KOOL
®
2 Menu operation RC.8A.P1.02 © Danfoss 01/2001 AKC 114G Version 1.0x
System survey
A refrigerating plant fitted with ADAP-KOOL
®
refrigeration controls will mostly consist of
several controllers where each controller will regulate its own refrigeration appliance/cold
room.
The system has been designed in such a way that contact can be made to each and
every controller via a data communication system. One specific controller is selected,
and it will now be possible to make settings and readouts for this unit.
The individual controllers can be operated in two
ways:
1. With control panel type AKA 21.
Use this document when operation takes place in
this way.
2. With PC and system software type AKM. Use
another document with literature number RC.8A.Q
Operation
Validity
This menu operation was worked out in December 2000 and applies to AKC 114G
with the code number 084B6184 that are fitted with software version 1.0x.
AKC 114G Version 1.0x Menu operation RC.8A.P1.02 © Danfoss 01/2001 3
All controllers that are connected to the same network can be operated with the
control panel. There may be as many as 125 controllers, and they are shown in
groups of 16 on the display.
A system is shown here which consists of more than 16 controllers. The meaning of
the letters is, as follows:
A: AKC controller
E: Controller with active ERROR (on addresses 2, 11 and 12 in this example)
g: Gateway (to addresses 13 and 14 in this example)
G: Gateway with connected printer
: A blank field indicates that there is no unit with this address.
Select the unit that is to be operated by using the “+/On” or “-/Off” key, and push
“Enter”. In this example you select the controller with address 4.
If the system comprises more than 16 units or units with an address code higher than
16, you may change to the next group by pushing “®”.
When a controller has been selected, you can make settings in it. This setting is
performed, as follows:
Shown in the upper right corner of the display is the setting with which the controller is
operating. Below that value a new setting may be made. Use the three keys “+/ON”,
“-/OFF” and “Digit” for setting the new value. This new value will not govern the
regulation until you push the key “Enter”.
Select a controller
Settings of a controller
5
-50 to +50 5
ON
OFF / ON ON
The functions in the controller can be protected by means of an access code.
Depending on the settings to be made, you may gain access in one of the following
ways:
User input: Gives access to:
1. Push F1 Display of alarms
2. Push F2 Reading of selected temperatures, change of
temperature in the refrigeration appliance, start of
defrost
3. Code 1 and then F1 Acknowledgement of alarms
Code 1 and then F3 Setting of selected parameters
4. Code 2 Operation of all settings of the entire menu system
(with system software type AKM there is access to
additional functions).
Pages 6 and 7 contain a description of how you gain access to the system via a code.
Access to a controller
1 < 1 > 16
AEAAAAAAAAEEgg A
1 < 4 > 16
AEAAAAAAAAEEgg A
17 < 17 > 32
AAA
4 Menu operation RC.8A.P1.02 © Danfoss 01/2001 AKC 114G Version 1.0x
A supporting text is attached to the individual functions. When such a function is
shown in the control panel’s display, the supporting text can be obtained by pushing
the key “Help”. The supporting text is intended as a help to users who no longer use
these operating instructions.
In the menus shown below functions with supporting texts are identified with the word
“Help” next to the function.
When an error appears in a system, it can be seen on the control panel’s display
which will show an “E”. If the control panel shows a text from a selected controller, the
LED at the word “Alarm” will furthermore flash.
When an error has occurred, first select the controller on which the error is registered.
When the controller has been found, push “F1”, and the error message will appear.
At the end of the document there is a list of all the error messages and a description
of how to acknowledge an alarm.
Supporting text
How to localise an error
When one controller has been selected from the total system, the following display will
appear (the display is the first one shown when you have selected an address from
the total system):
e.g.
AKC 114G Adr: 2
E Mon-11:27
From this position you can freely choose between several forms of operating levels:
1. Display of alarms - push “F1”
2. Display and setting of a few selected functions - push “F2”
3. Display and setting of several selected functions - push “F3”
The function may be protected with a code (code 1)
4. Display and setting of all allowed functions in the controller. The function may be
protected with a code (code 2).
Operation of the individual levels is shown below:
When you push “F1” the alarm messages from the controller in question appear. Only
active alarms are shown. With a push on “¯” you can see whether there are more alarm
messages, and if so, their texts.
When an alarm has been localised and corrected, the alarm is acknowledged
(removed from the system, so that it no longer appears). In large systems where a
gateway is also connected this acknowledgement will take place automatically. In
other systems it has to be done manually, cf. end of the document.
Prior to the acknowledgement of the alarm, the keying of a code is required, see page
6.
Leave the F1 function by pushing “¬”.
Functions of a
controller
1 < 2 > 16
AEAAAAAAAAAAgg A
AKC 114G Adr: 2
E Mon-11:27
Standby Mode
1. F1
AKC 114G Version 1.0x Menu operation RC.8A.P1.02 © Danfoss 01/2001 5
When you push “F2” a number of functions will appear where it is possible to read or set
values.
You can move to and from the individual functions by pushing “” or “¯”. On page 3 you
can see how a setting is changed.
Man.Def. Manual defrost is activated when ON
OFF/ON (Changes automatically to OFF)
5:03:02
|
CutOut A °C Setting of thermostat cut-out value
-50 - 50 MUST BE SET. Even if the thermostat function has not been
3:05:02 selected. (The value is used by the injection function).
|
Ther.Air A Actual air temperature
3:04:01
|
RunTime A Actual thermostat cut-in time
3:04:08 or duration of the latest finished cut-in
|
Reg Cond. A Help Regulating condition
3:02:01 0: No cooling 5: Start after defrost
1: Start up 6: Forced closing
2: Adaptive control
8: Sensor errror
4: Defrosting 9: Modulating temperature control
10: Forced cutout (Melt function)
Leave the F2 function by pushing ¬.
2. F2
6 Menu operation RC.8A.P1.02 © Danfoss 01/2001 AKC 114G Version 1.0x
When you push F3, a number of functions will appear which are used when the system
is serviced.
If access code is used (code 1), key it as follows:
- Push the key
- Enter the code by using the three keys +, - and Digit (the code is mentioned
later as code 1, and the factory setting is 40. If code 2 has been set at 0,
access code 1 cannot be used).
- Push Enter
- Push F3
Move to and from the individual functions by pushing or ¯.
On page 3 you can see how a setting is changed.
Main Switch Main switch: 1: Regulation
-1 / 0 / 1 0: Controller stop
2:02:01 -1: Service
|
Def.Stop °C Temperature value of defrost stop
0 - 60
5:04:03
|
MaxDefTime Max. permissible defrost time in minutes
5 - 180 (Security time on Temperature stop)
5:04:02
|
T0 °C Evaporating temperature
3:02:05
|
Superheat A Superheat
3:02:02
|
AKV OD % A AKV valve opening degree
3:02:04
Leave the function by pushing ¬.
3. F3
AKC 114G Version 1.0x Menu operation RC.8A.P1.02 © Danfoss 01/2001 7
4. Access to all
functions
The access to the functions may be protected with a code (code 2).
If access code is used, key it as follows:
- Push the key
- Enter the code by using the three keys +, - and Digit
- Push Enter
- Push ¬
Move to and from the individual functions by pushing the four arrow keys.
On page 3 you can see how a setting is changed.
When you wish to leave the Access to all functions function, push Clear and then
¬.
List of functions on level 1:
1. Controllers access display and access to system information
2. Interruption of regulation and selection of language
3. Controller A
4. Common functions; Thermostat function, day/night Ctrl. settings, fan control, display
control, DI Alarm, Output control at forced closing, safety function, Ext. injection and
Sub cool ctrl.
5. Defrost control
6. Forced control functions for service and initial setting
Below and on the following pages the individual functions are shown together with a
brief description:
Level 1 Level 2 Level 3 Level 4 Description
AKC 114G Adr: xxx Controller access displa
y
Mon hh:mm If the code function is used, continue b
y
pushin
g
the "ke
y
" ke
y
.
Enter Code Entr
y
of access code 1 or access code 2
(
cf. also 1:07 and 1:08
)
.
0 - 255 0 Continue b
y
pushin
g
"arrow left"
1:01
AKC 114G Adr: xxx Access to s
y
stem information
Mon hh:mm If an E appears in the displa
y
, an error has been re
g
istered.
1
Code No. Readin
g
of the controllers code no. and pro
g
ramme version.
Prog. Ver.
1:02
|
Clock: Settin
g
of controller clock
(
AKC clock
)
Mon hh:mm
1:03
Clock: Da
y
. Settin
of da
1 = Monda
, 7 = Sunda
Mon
(
1
)
Sun
(
7
)
1:03:01
|
Clock: Hou
r
Settin
g
of hours
0 - 23
1:03:02
|
Clock: Min. Settin
g
of minutes
0 - 59
1:03:03
|
S
y
stem Address Readin
g
of the controllers s
y
stem address
Addr.
yyy
xxx
yyy
=network no. and xxx=address.
1:04 The s
y
stem address can onl
y
be set via PC
|
Alarm report to Readin
g
of the alarm address
(
end receiver
)
the alarms are to be
Addr.
yyy
xxx sent to.
1:05 The alarm address can onl
y
be set via PC.
8 Menu operation RC.8A.P1.02 © Danfoss 01/2001 AKC 114G Version 1.0x
|
Gatewa
y
Address Readin
g
of the address on the nearst
g
atewa
y
which has to
xxx effect alarms
(
see 1:05
)
1:06 The address can onl
y
be set via PC
|
Ch
g
. Code1 Chan
g
e of code 1. The code
g
ives access to acknowled
g
ement
0 - 255 of active alarm b
y
means of the F1 ke
y
.
1:07 Also access to the selected settin
g
s/readouts via the F3 ke
y
.
|
(
Factor
y
settin
g
= 40
)
(
See also code 2
)
Ch
g
. Code2 Chan
g
e of code 2. The code
g
ives access to the whole menu
0 - 255 s
y
stem.
1:08
(
Factor
y
settin
g
= 0. Settin
g
= 0 offers free access where
neither code 1 not code 2 is re
q
uired
)
|
Main Function Main function
2
Alarm Messa
g
e
(
s
)
In case of alarm, an E is shown on the displa
y
2:01
(
Error lo
g
becomes visible
)
See pa
g
e 15, check of error lo
g
2:01:01
|
Main Function Access to the main switch
Settin
g
s
2:02
Main Switch Main switch: 1: Re
g
ulation
-1 / 0 / 1 Help 0: Controller stop
2:02:01 -1: Service
|
Lan
g
ua
g
e Selection of lan
g
ua
g
e. Three lan
g
ua
g
es have been entered
0 - 2 Help in the controlle
r
2:02:02 0: En
g
lish
1: German
2: French
NB! This function must be set prior to an
y
uploadin
g
to s
y
stem
software t
y
pe AKM.
When the lan
g
ua
g
e code has been chan
g
ed, push "ENTER"
and then "Clear".
|
Rf
g
. T
y
pe R Readin
g
of set refri
g
erant t
y
pe
2:02:03
|
Rf
g
. T
y
pe Refri
g
erant selection: 0: No refri
g
erant selection. 12: R142b
0 - 23 Help 1: R12 13: User de
f
2:02:04 2: R22 14: R32
3: R134a 15: R227
4: R502 16: R401A
5: R717
(
ammonia
)
17: R507
6: R13 18: R402A
7: R13b1 19: R404A
8: R23 20: R407C
9: R500 21: R407A
10: R503 22: R407B
11: R114 23: R410A
|
Controller A Section A
3 In case of alarm, an E is shown on the displa
y
Alarm messa
g
e
(
s
)
(
Error lo
g
becomes visible
)
3:01
See pa
g
e 15, check of error lo
g
3:01:01
|
In
j
ection A Read-out of measurin
g
values
Measurements
3:02
Re
g
Cond. A Re
g
ulatin
g
condition
3:02:01 Help 0: No coolin
g
5: Start after defrost
1: Start up 6: Forced closin
g
2: Adaptive control
8: Sensor errro
r
4: Defrostin
g
9: Modulatin
g
temperature control
10: Forced cutout
(
Melt function
)
AKC 114G Version 1.0x Menu operation RC.8A.P1.02 © Danfoss 01/2001 9
|
Superheat A Superheat
3:02:02
|
SH Ref K A Actual superheat reference of the re
g
ulation
3:02:03
|
AKV OD % A AKV valve openin
g
de
g
ree
3:02:04
|
T0 °C Evaporatin
g
temperature
3:02:05
|
S2 A °C Gas temperature at evaporator outlet.
3:02:06
|
In
j
ection A Settin
g
of expansion valve function
Settin
g
s
3:03
In
j
. Ctrl. A Choose expansion valve function ON/OFF
OFF / ON
3:03:01
|
Thermostat Read.out of measurin
g
values related to thermostat function.
Measurements
3:04
Ther.Air A Actual air temperature
3:04:01
|
AlarmAir A Actual air temperature for the alarm function
3:04:02
|
S3 A °C Air temperature at evaporator inlet
(
air on
)
3:04:03
|
S4 A °C Air temperature at evaporator outlet
(
air off
)
3:04:04
|
CutOut A °C Actual thermostat
(
s
)
cut-out value
3:04:05
|
CutIn A °C Actual thermostat
(
s
)
cut-in value
3:04:06
|
Ni
g
ht Cond. Status of da
y
-/ni
g
ht operation
(
ON/OFF
)
3:04:07
|
RunTime A Actual thermostat cut-in time
3:04:08 or duration of the latest finished cut-in
|
Thermostat Settin
g
s for thermostat function
Settin
g
s
3:05
Ther. Sx A Definition of thermostat sensor
(
s
)
1 - 3 Help 1: S3 in use
3:05:01 2: S4 in use
3: S3, S4 in use. CPT
(
calculated product temperature
)
|
CutOut A °C Settin
g
of thermostat cut-out value
-50 - 50 MUST BE SET. Even if the thermostat function has not been
3:05:02 selected.
(
The value is used b
y
the in
j
ection function
)
.
|
Diff. A K Settin
g
of thermostat differential
0.5 - 10.0
3:05:03
|
S4A % S4 wei
g
htin
g
0 - 100 S3 is automaticall
y
wei
g
hted. Must onl
y
be set if "Ther.Sx" = 3
3:05:04
10 Menu operation RC.8A.P1.02 © Danfoss 01/2001 AKC 114G Version 1.0x
|
Air Temp. Alarm Settin
g
s for alarm function
Settin
g
s
3:06
Alarm ModeA Definition of alarm thermostat
0 - 3 Help 0: No alarm thermostat
3:06:01 1: S3 used as alarm senso
r
2: S4 used as alarm senso
r
3: TherAir used as alarm senso
r
|
Hi
g
h LimA °C Hi
g
h air temperature alarm limit
(
absolute value
)
.
-50 - 50 When there is ni
g
ht setback operation, the alarm limit is raised
3:06:02 b
y
the ni
g
ht setback value.
|
Hi
g
h1Del A Time dela
y
of hi
g
h air temperature alarm durin
g
pull-down.
0 - 240 Help This value will appl
y
until the actual air temperature has dropped
3:06:03 below the "upper alarm limit".
Thereafter shift to the time dela
y
"Hi
g
h2Del m".
|
Hi
g
h2Del A Time dela
y
of hi
g
h air temperature alarm durin
g
normal re
g
ulatio
n
0 - 60 Help
3:06:04
|
Low LimA °C Low air temperature alarm limit
(
absolute value
)
-50 - 50
3:06:05
|
Low Del A Time dela
y
for low air temperature alarm
0 - 60
3:06:06
|
Common Functions
Controlle
r
4
Alarm messa
g
e
(
s
)
In case of alarm, an E is shown on the displa
y
4:01
(
Error lo
g
becomes visible
)
See pa
g
e 15, check of error lo
g
4:01:01
|
Thermostat
Mode
4:02
Ther. Mode Definition of thermostat function
0 - 3 Help 0: No thermostat function
4:02:01 1: ON/OFF thermostat
2: ON/OFF thermostat
3: Modulatin
g
temperature re
g
ulation
|
Da
y
/Ni
g
ht Ctrl. Settin
g
s of da
y
/ni
g
ht function
Settin
g
s
4:03
Da
y
/Ni
g
ht Choose da
y
-/ni
g
ht operation function
0 3 Help 0: No ni
g
ht setback
4:03:01 1: Chan
g
e between da
y
and ni
g
ht operation accordin
g
to
si
g
nal on S6 input
2: Chan
g
e between da
y
and ni
g
ht operation accordin
g
to
internal time clock
3: Chan
g
e between da
y
and ni
g
ht operation accordin
g
to the
si
g
nal from the master controller
(
Si
g
nal via DANBUSS
)
|
Dt Ni
g
ht K Ni
g
ht set back value
-25 - 25
4:03:02
|
Fan Pulsin
g
Settin
g
of fan pulsin
g
durin
g
cut out operation
(
CutOut
)
4:04
Fan On % Settin
g
of the fans ON period in percent of the "FanC
y
cl m" time
0 - 100
(
the function is onl
y
active in the cutout period
)
4:04:01
|
FanC
y
cl m Period time for total ON / OFF time
0.0 - 60.0
4:04:02
AKC 114G Version 1.0x Menu operation RC.8A.P1.02 © Danfoss 01/2001 11
|
Displa
y
Ctrl. Settin
g
s for external temperature displa
y
t
y
pe AKA 14 /15
Settin
g
s
4:05
Disp. Ctrl. Choose read-out for displa
y
0 - 3 Help 0: No displa
y
function
4:05:01 1: S3 read out
2: S4 read out
3: Ther.Air read out
|
Offset K A Offset ad
j
ustment of displa
y
si
g
nal
-10.0 10.0
4:05:02
|
DI Alarm Settin
g
s for DI alarm function
4:06
DI Alarm Choose alarm function ON / OFF
OFF / ON
4:06:01
|
DI Text Select the alarm text
0 - 4 Help 0: DI alarm
4:06:02 1: Door alarm
2: Safet
y
cutout
3: Fan failure
4: Leak alarm
|
DI Dela
y
m Time dela
y
from the alarm is re
g
istered until executed
0 - 180
4:06:03
|
Output Ctrl. at Definition of controller outputs at forced control si
g
nal
Forced Closin
g
(
when the "ON" inlet is cut-out
(
terminal 32 - 33
))
4:07
Output Ctrl. Output functions when there is forced control
1 - 3 Help 1: Fan outlet is ON
4:07:01 2: Fan outlet is OFF
3: All outlets are OFF and alarm thermostat function is stopped.
|
ON-InpMode Definition of AKC-ON input
(
terminals 32-33
)
0 - 1 0: Connection not used, as the re
g
ulation is controlled b
y
the
4:07:02
g
atewa
y
s override function
1: Connection must be made
(
when the volta
g
e is interrupted, th
e
valve closes
)
|
Safet
y
Function Settin
g
s for fan stop function
Fan Stop b
y
S5
4:08
FanStopS5 Choose Fan stop function ON / OFF
OFF/ON Help
4:08:01
|
FanStop °C Temperature limit for fan stop
(
the fans are stopped when the
-50 - 50 S5A temperature is hi
g
her than this value. The fans will start
4:08:02 a
g
ain when S5A is lower than "FanStop °C" - 2K
)
|
Extended In
j
ect. Extended settin
g
s for in
j
ection function
Ctrl. Settin
g
s
4:09
SH Max K Max. superheat reference value
3.0 - 15.0
4:09:01
|
SH Min K Min. superheat reference value
3.0 - 10.0
4:09:02
12 Menu operation RC.8A.P1.02 © Danfoss 01/2001 AKC 114G Version 1.0x
|
SubCool Ctrl. Comin
g
settin
g
for sub-coolin
g
controller.
Settin
g
s Settin
g
has no effect at present
4:10
|
|
|
|
Defrost Control Defrost function
5:00
Alarm messa
g
e
(
s
)
In case of alarm, an E is shown on the displa
y
5:01
(
Error lo
g
becomes visible
)
See pa
g
e 15, check of error lo
g
5:01:01
|
Defrost Read-out of measurin
g
values related to defrost function
Measurements
5:02
Def. Cond. Defrost condition
5:02:01 Help 0: No defrost 4: Not used
1: Pump down 5: Drainin
g
2: Not used 6: In
j
ection dela
y
3: Defrostin
g
7: Fan dela
y
|
S5 A °C Defrost sensor temperature
5:02:02
|
DefTime m Actual defrost cut-in time or duration of the latest finished
5:02:03 defrostin
g
period.
|
MDefTime m Avera
g
e value of the latest 4 defrostin
g
periods.
5:02:04
|
Defrost Ctrl. Definition of defrostin
g
method
Settin
g
s
5:03
Def. Ctrl. Choose defrost function ON/OFF
OFF/ON
5:03:01
|
Man.Def. Manual defrost is activated when ON
OFF/ON
(
Chan
g
es automaticall
y
to OFF
)
5:03:02
|
Fan run Choose fan operation durin
g
defrost ON/OFF
OFF/ON
5:03:03
|
Defrost Stop. Definitions of defrost stop
Temp
(
1
)
/Time
(
2
)
5:04
Temp/Time 1: Temperature stop
(
time as securit
y)
1 - 2 2: Stop on time
5:04:01
|
MaxDefTime Max. permissible defrost time in minutes
5 - 180
(
Securit
y
time on Temperature stop
)
5:04:02
|
Def.Stop °C Temperature value of defrost stop
0 - 60
5:04:03
|
DefStop Sx Definition of sensor for defrost
2 - 5 Help 2: S2 3:S3
5:04:04 4: S4 5: S5
(
default settin
g)
AKC 114G Version 1.0x Menu operation RC.8A.P1.02 © Danfoss 01/2001 13
|
Defrost Se
q
uence Defrost se
q
uence
Settin
g
s
5:05
PumpdDel m Pumpdown time before hot
g
as is activated
0 - 60
5:05:01
|
Drain Del m Time after defrost where evaporator is emptied via
0 - 60 the drain valve
5:05:02
|
In
j
.Del m Li
q
uid in
j
ection dela
y
time
0 - 60
5:05:03
|
FanOnDel m Max. permissible fan start dela
y
after defrostin
g
.
0 - 60 The dela
y
time runs from the expir
y
of the dela
y
time, if applicabl
e
5:05:04 for the li
q
uid in
j
ection.
|
Fan On °C Temperature at which the fan starts after defrost.
-15 - 0 Fans starts when all S5 temperatures are below the value.
5:05:05
|
Def. Schedules Help function for settin
g
of defrost times
Auto. pr
g
rammin
g
The defrost periods are distributed evenl
y
durin
g
a defined
5:06 period of time within a 24-hour period.
No. Per Da
y
Number of defrosts/24 hours
2 - 8
5:06:01
|
FirstDef Settin
g
of time the 1st defrost be
g
ins
00:00
5:06:02
FirstDef Hou
r
Settin
g
of hours
0 - 23
05.06.02.01
|
FirstDef Min. Settin
g
of minutes
0 - 59
05.06.02.02
|
LastDef Settin
g
of time the last defrost be
g
ins
00:00
5:06:03
LastDef Hou
r
Settin
g
of hours
0 - 23
05.06.03.01
|
LastDef Min. Settin
g
of minutes
0 - 59
05.06.03.02
|
Auto Set Transfer the values to the subse
q
uent defrost pro
g
ramme.
OFF/ON Help In pos. ON the
y
are entered in "5:07"
5:06:04
|
Schedule Settin
g
s for defrost pro
g
ramme
Def. Start Times
5:07
No. Per Da
y
Number of defrosts/24 hours
0 - 8
5:07:01
|
Defrost 1 Settin
g
of time the 1st defrost be
g
ins
00:00
5:07:02
Defrost 1 Hou
r
Settin
g
of hours
0 - 23
05:07:02:01
|
Defrost 1 Min. Settin
g
of minutes
0 - 59
05:07:02:02
14 Menu operation RC.8A.P1.02 © Danfoss 01/2001 AKC 114G Version 1.0x
|
Defrost 2 Settin
g
of time the 2nd defrost be
g
ins
00:00 See 5:07:02
5:07:03
|
Defrost 3 Settin
g
of time the 3rd defrost be
g
ins
00:00
5:07:04
|
Defrost 4 Settin
g
of time the 4th defrost be
g
ins
00:00
5:07:05
|
Defrost 5 Settin
g
of time the 5th defrost be
g
ins
00:00
5:07:06
|
Defrost 6 Settin
g
of time the 6th defrost be
g
ins
00:00
5:07:07
|
Defrost 7 Settin
g
of time the 7th defrost be
g
ins
00:00
5:07:08
|
Defrost 8 Settin
g
of time the 8th defrost be
g
ins
00:00
5:07:09
|
Service mode Service function
6
Measurements of Measurements on inlets
input terminals
6:01
P0 Ba
r
Evaporatin
g
pressure
(
measured with P0 pressure transmitter
)
6:01:01
|
To °C Evaporatin
g
temperature
6:01:02
|
S2 A °C Gas temperature at evaporator outlet
6:01:03
|
S3 A °C Air temperature at evaporator inlet
(
air on
)
6:01:04
|
S4 A °C Air temperature at evaporator outlet
(
air off
)
6:01:05
|
S5 A °C Temperature at defrost senso
r
6:01:06
|
Def. Start Statement of defrost start si
g
nal
6:01:07
(
terminal 30 - 31
)
|
ON input Statement of forced closin
g
input
6:01:08
(
terminal 32 - 33
)
|
DI input Statement of DI input
6:01:09
|
S6 Input Statement of S6 inlet
6:01:10
(
terminal 60 - 61
)
|
Comin
g
measurement for sub-coolin
g
controlle
r
|
Comin
g
measurement for sub-coolin
g
controlle
r
AKC 114G Version 1.0x Menu operation RC.8A.P1.02 © Danfoss 01/2001 15
|
Manual Control Forced operation of outlets durin
g
service
of Outputs "Main switch" must be set to be "-1"
(
see 2:02:01
)
6:02
Man Ctrl. ON: Manual control is permitted when "Main Switch"= -1.
OFF / ON NOTE: No monitorin
g
6:02:01 When manual settin
g
is finished, settin
g
must be chan
g
ed to OF
F
|
Fan Forced operation of fan outlet
OFF / ON
(
terminal 10-11
)
6:02:02
|
Tra
y
heat Forced operation of tra
y
heat
(
DEF.1
)
outlet
OFF / ON
(
terminal 12-13
)
6:02:03
|
AKV OD % A Forced operation of expansion valve openin
g
de
g
ree
0 - 100
(
terminal 14-15
)
6:02:04
(
Fans must be operatin
g
durin
g
forced control operation
)
|
Drain Valve Forced operation of Drain valve
(
DEF.2
)
outlet
OFF / ON
(
terminal 16-17
)
6:02:05
|
Suction Val Forced operation of suction valve
(
DEF.3
)
outlet
OFF / ON
(
terminal 18-19
)
6:02:06
|
Alarm Forced opertion of alarm outlet
(
terminal 20 - 21
)
OFF / ON ON: Rela
y
switch closed
(
no alarm
)
6:02:07 OFF: Rela
y
switch interrupted
(
alarm
)
|
Hot Gas Val. Forced operation of hot
g
as valve
(
DEF.4
)
outlet
OFF / ON
(
terminal 22-23
)
6:02:08
Error Log:
The followin
g
displa
y
read-outs are onl
y
visible if there is an active error.
When the error is corrected, the error messa
g
e can be removed b
y
pressin
g
ENTER.
(
If the code function has been selected, a code must also be entered
)
.
S2 sensor Erro
r
S2 sensor erro
r
Check sensor connection / sensor resistance
S3 sensor Erro
r
S3 sensor erro
r
Check sensor connection / sensor resistance
S4 sensor Erro
r
S4 sensor erro
r
Check sensor connection / sensor resistance
S5 sensor Erro
r
S5 sensor erro
r
Check sensor connection / sensor resistance
AKS 32R Erro
r
AKS 32R sensor erro
r
Check sensor connection
Hi
g
h Air Temp Too hi
g
h air temperature
Low Air Temp Too low air temperature
Overfloated Overfilled evaporato
r
evaporato
r
Max. Def. period Max. defrostin
g
period exceeded Defrostin
g
finished accordin
g
to time not as selected accordin
g
exceeded to temperature
Max. fan del time Max. fan dela
y
exceeded When defrost has been completed, the fan start will be based on
exceeded time, and not on temperature
(
5:05:05
)
16 Menu operation RC.8A.P1.02 © Danfoss 01/2001 AKC 114G Version 1.0x
230 Volt on Wron
g
defrost demand Active defrost si
g
nal on terminal 30 - 31 contrar
y
to
j
ust finished
Def. start input defrostin
g
.
Check clock After power failure, timer must be set
settin
g
s
Standb
y
mode The Main switch is either set in the position
"Controller stop" or "Service"
(
see 2:02:01
)
.
Refri
g
erant No selection of refri
g
erant Select refri
g
erant
not selected
Rf
g
. Chan
g
ed Chan
g
ed refri
g
erant Check chosen refri
g
erant. Re
g
ulation with chan
g
ed refri
g
erant
has come into force.
DI Alarm
/
Alarm on di
g
ital input Check the function
Door Alarm
/
Safet
y
cutout
/
Fan failure
/
Leak alarm
Li
q
uid suppl
y
Flash
g
as or missin
g
Check for flash
g
as / li
q
uid
fault alarm li
q
uid
Communications/messages from AKA 21
Message not sent There is no contact between Check the data communication system
control panel and a controller
Regulator message - ll - Check the data communication system
not received
No node - ll - Check the data communication system
(There is no gateway on the data communication system)
Initialisation erro
r
- ll - Check the data communication s
y
stem
(
There is a
g
atewa
y
on the data communication s
y
stem
)
The messa
g
e ma
y
be removed, if
y
ou disconnect AKA 21 briefl
y
Messa
g
e not Temporar
y
communication Wait, or if it is a newl
y
started s
y
stem, check the setup of the dat
a
understood problem or wron
g
setup communication s
y
stem
Dansett supervisin
g
Pause function When
y
ou push a ke
y
, the displa
y
disappears.
Supervising Lack of contact to a controlle
r
Check the data communication system
no answe
r
AKC AKA 21 had been disconnected Wait. The message disappears on its own after three minutes.
Occupied for a brief period
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
AC-RDT
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Danfoss Controller type AKC 114G for controlling evaporators. Vers. 1.0x. AKA 21 Installation guide

Category
Thermostats
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI