nvent TOUCH 1500 Installation guide

Type
Installation guide

This manual is also suitable for

TOUCH 1500
installed in a panel
TOOLS REQUIRED
Masking tape #16 (3/16) drill bit
Metal file Phillips screwdriver
Jig saw (recommend using carbon steel blade with 24TPI)
ADDITIONAL MATERIALS (TO BE ORDERED SEPARATELY)
Qty Description Manufacturer Manufacturer PN
2 9 pin D-Sub to 10 pin terminal block PCB Phoenix Contacts 2315162
2 Serial Communication cable L-COM "CSMN9MF-xx
xx=Length in Ft."
11 Terminal Blocks Weidmuller 163205
1 Type ZS1 Fuse Block Weidmuller 161649
4 PE Terminal (Earth Ground) Weidmuller 1632080000
6 End plates / Partition Weidmuller 1632090000
1 End plate / Partition Weidmuller 1896330000
6 End Plate Stops Weidmuller 38356
2 Jumpers, 2 Position Weidmuller 1608950000
2 Jumpers, 3 Position Weidmuller 1608960000
1 Fuse, 1 amp, 250 V Square D MLD-1
1 Power Supply, 24 Vdc, 2.5 Amp Mean Well DR-120-24
1 Push to test alarm light; Idec 24 Vdc Idec ALW29911-D-R-24
FIRE HAZARD: The Touch 1500 must not be used in
hazardous locations. Electrical components within the unit
could ignite flammable gases. Do not install the unit where it
may be exposed to flammable gases.
The TOUCH 1500 is an electronic unit. During installation, take
the following precautions to avoid damage to its electronic
components.
Handle with care to avoid mechanical damage.
Keep electronics dry.
Avoid exposure to static electricity.
Avoid contamination with metal filings, liquids, or other
foreign matter.
Use agency-approved conduit bushings, adapters, and cable
glands to keep the enclosure protected from dust and fluids.
WARNING:
IMPORTANT:
Network Connection
Local/
Remote Port
* RS-232/RS-485 ports may be used to communicate
with host computers DTS (nVent RAYCHEM Supervisor
Software) or DCS
Local RS-232 A non-isolated, 9 pin D sub male
Remote RS-485 2-wire isolated, 9 pin D sub male
Data rate 9600 to 57600 baud
Maximum cable
length
For RS-485 not to exceed 1200 m (4000 ft). Cable to be
shielded twisted pair.
Field Port RS-485, 2-wire isolated. Used to communicate with
external devices, such as nVent RAYCHEM
NGC-40-BRIDGE. Maximum cable length not to exceed
1200m (4000 ft). Cable to be shielded twisted pair.
Signals 2-wire isolated, 9 pin D sub male
Data rate To 9600 baud
LAN 10/100 Base-T Ethernet port with Link and Activity Status
LEDs (X2)
USB Ports USB 2.0 Host port Type A receptacle (X4)
KIT CONTENTS
Qty Description
1 TOUCH 1500 display
10 Mounting clips
1 ADAM 4069-CID2 relay module
1 5-ft 9-pin RS-232 (null modem) cable
APPROVALS/CERTIFICATIONS
E180881
I.T.F.
Nonhazardous Locations
TOUCH 1500
User Interface Terminal for
RAYCHEM
NGC
Systems Installation Instructions
DESCRIPTION
The nVent RAYCHEM TOUCH 1500 is a panel mounted touch screen display used in
conjunction with nVent RAYCHEM NGC-40 and NGC-20 (Europe only) control and monitoring
devices. The TOUCH 1500 is rated IP 65 (NEMA 4) and is approved for nonhazardous indoor
locations. The TOUCH 1500 kit includes all hardware required for mounting in a suitable
electrical panel. These instructions describe how to mount the TOUCH 1500 in an electrical
panel and are intended only for personnel experienced in panel construction.
General
Area of use Nonhazardous, Indoors (IP65, NEMA 4)
Supply voltage 10 – 30 Vdc
Amperage rating
Steady state
1.8 A
Surge current 16 A
Operating
temperature
0°C to 50°C (32°F to 122°F) w/o space heater, –30°C to 50°C
(–22°F to 122°F) using space heater and screen cover
Storage
temperature
–20°C to 60°C (–4°F to 140°F)
Dimensions 449.9 mm W X 315.6 mm H X 141.7 mm D
(17.74 in. W X 12.44 in. H X 5.58 in. D)
Alarm Outputs
Relay output One Form C relay rated at 3 A @ 250 Vac.
Relay is used as a common alarm.
LCD Display
Display LCD is a 15-in XGA, color TFT transective device with
integral CCFL backlight
Touch Screen 4-wire resistive touch screen interface for user entry
C1
CB19
CB17
CB15
CB13
CB3
CB9
CB11
CB7
CB5
CB1
CB16
CB42
CB20
CB18
CB4
CB14
CB12
CB10
CB8
CB6
CB2
C2 C3 C4 C5 C6 C7 C8 C9 C10
CB23
CB25
CB27
CB29
CB21
CB26
CB28
CB30
CB22
CB24
CB31
CB33
CB35
CB37
CB39 CB40
CB36
CB32
CB34
CB38
1
3
5
7
9
19
17
15
13
11
29
27
25
23
21
39
37
35
33
31
2
4
6
8
10
12
14
16
18
20
30
28
26
24
22
32
34
36
38
40
PanelTouch 1500
assembly location
Panel
door
Alarm
light
Provide Suitable Panel Enclosure, and Determine Locations for TOUCH 1500 Assembly in Panel X
1. Provide suitable panel enclosure
To protect its electronic components, the TOUCH 1500
must be mounted in a non-hazardous location panel with
a minimum IP32 (NEMA 1) enclosure. An IP52 (NEMA 12)
or better enclosure is recommended. The TOUCH 1500
assembly comes with a sealing gasket and hardware to
mount the enclosure.
Note: The RAYCHEM TOUCH 1500 is designed for
operation in ambient temperatures from 0°C to 50°C (32°F
to 122°F). If the ambient temperature is outside this range,
a space heater with screen window kit and/or cooling fan
will be required in the panel.
2. Determine locations for the TOUCH 1500 assembly in the
electrical panel
The TOUCH 1500 should be located on the front of the
panel near eye level (for convenient viewing). The TOUCH
1500 assembly is an electronic unit and must not be
located where it will be exposed to strong magnetic fields
or excessive vibration.
2 | nVent.com
Cut Opening and Mount TOUCH 1500 on Front of Panel
1. Locate the TOUCH 1500 on front of panel
Locate the TOUCH 1500 assembly on the front of the panel
at a level convenient for viewing. Make sure the cover on
the back of the assembly will not interfere with existing
panel hardware.
2. Prepare and mark the position of the display opening and
mounting holes
Use the cut-out directions to lay out the opening for the
TOUCH 1500 display.
Apply two layers of masking tape around the outer pe-
rimeter of the intended opening to prevent scratching the
panel surface with the jigsaw.
3. Cut the display opening
Cut the opening for the TOUCH 1500 with a jigsaw using
a 24 TPI blade. Take care not to damage the panel door.
Remove all rough edges and burrs with a metal file before
proceeding.
Note: The following steps are most easily accomplished if
the panel door is on a horizontal surface.
4. Mount the user interface assembly onto the panel door
Place the TOUCH 1500 assembly in position. Secure the
screen to the enclosure with the 10 mounting clips.
Place the supplied mounting clips in each slot along the
sides of the TOUCH 1500. Fasten only hand tight.
Look at the front of the panel, and align the TOUCH 1500
assembly so it is level (loosen clips if necessary to reposi-
tion the assembly).
After the display is properly positioned, tighten the mounting
clips. Do not overtighten and risk damage to hardware.
Cutting
Area
Panel Door
422 mm
16.6 in.
292 mm
11.5 in.
Note: Cutting the opening for the display is a craft sensi-
tive procedure; if it is not done correctly, the panel door
can be damaged. The procedure for laying out and cutting
the opening for the display must be undertaken with
care, and by personnel qualied and experienced in panel
construction.
+ –
G
Panel door
TOUCH 1500 display
with sealing gasket
Inside of
panel door
+ –
G
TOUCH 1500 display
+ –
G
TOUCH 1500 display
Mounting clips
nVent.com | 3
292 mm
(11.5 in)
Panel Cut Out Area
Top of Display
Drawing
NOT TO SCALE
Drawing
NOT TO SCALE
422 mm
(16.6 in)
Panel Cut Out
Panel Cut Out
TOUCH 1500 Cut Out Dimensions
4 | nVent.com
+ G
Ethernet
Remote Port
RS-485
Com 4
Remote Port
RS-485
Com 3
Field Port
USB port (X4)
RS-232
Com 1
Compact flashKeyboardMouse
Reset
Switch
Incoming
power
Ethernet
Field Port
+ G
Incoming
power
G
10 – 30 Vdc
+
TOUCH 1500 Connection Diagram
Connect Power
Communication
Connect 10 – 30 Vdc to the male power connection tting
located on the bottom side of the TOUCH 1500. Note the polarity
of the wires.
The TOUCH 1500 has two isolated RS-485 ports located at the
bottom.
Field Side Port (RS-485)
The RS-485 port labeled “Com 3” is the eld side port that
is used to communicate with ModBus devices (ie. NGC-40-
BRIDGE and NGC-20).
*Remote Port (RS-485) – Optional
The RS-485 port labeled “Com 4” is the Remote side port
that is used to communicate with to a host computer DTS
(using RAYCHEM Supervisory Software) or to a DCS.
*Local Host Port (RS-232) – Optional
The RS-232 port can be used as local Host port that is used
to communicate with to a host computer (using RAYCHEM
Supervisory Software).
nVent.com | 5
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2NC
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NC
RL7COM
RL7NC
NC
INT+
(Y) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
ADAM-4069-CID2
Shield
Shield
Jumpers
Jumpers
Serial communication
cable to Field Port/Com 3
(RS-485)
120/230 Vac
+ G
+
Ground
2
1
Alarm
Lamp
24 V Lamp
Idec Switch/Lamp
4
3
Alarm Lamp
TOUCH 1500
RS-485
RS-485
To Remote Port/Com 4 (RS-485)
Data +
Data –
Field
Port
Com 3
Field port (to Bridge, NGC-20)
Data +
Data –
To host computer
Door mounted
Remote
Port
Com 4
5 4 3 2 1
T 9 8 7 6
5 4 3 2 1
T 9 8 7 6
5 4 3 2 1
T 9 8 7 6
Remote
Port
Com 4
(See wiring below)
Field Port Communication RS-485 Common Alarm Light and Alarm Relay
Mount the supplied ADAM 4069-CID2 module, 9-pin D sub to 10
pin terminal block and 4 terminal block (with 2 position jumpers)
on a DIN rail inside the panel enclosure. Mount the alarm light on
the panel's door below the touch screen.
Wire per the schematic below.
Remote Port Connection
* Mount the supplied 9-pin D sub to 10-pin terminal block on a
DIN rail inside the panel enclosure.
Wire per schematic to the right.
6 | nVent.com
Door mounted
+ G
RL4NO
RL4COM
RL3NO
RL3COM
RL2NC
RL2COM
RL2NC
RL1NC
RL1COM
RL1NO
RL0NC
RL0COM
RL0NO
RL5NO
RL5COM
RL6NO
RL6COM
RL7NC
RL7COM
RL7NC
NC
INT+
(Y ) DATA +
(G) DATA –
(R) +Vs
(B) GND 10
ADAM-4069-CID2
Shield
Common alarm relay
Remote
Port
Com 4
Incoming
Power Terminal
Block
Data +
Data –
Ø
G
Ø or N
Data +
Data –
Field
Port
Com 3
Remote Port
Field Port
+
Ground
TOUCH 1500
Jumpers
Jumpers
2
1
Alarm
Lamp
24 V Lamp
Idec Switch/Lamp
4
3
Alarm Lamp
5 4 3 2 1
T 9 8 7 6
5 4 3 2 1
T 9 8 7 6
Overview of Wiring
nVent.com | 7
+ G
Reset
Switch
Servicing
Cleaning
Reset Switch
The TOUCH 1500 contains no user-serviceable parts. Contact your
nVent representative for service and an authorization number if
required.
The touch screen area of the TOUCH 1500 may be cleaned with a
damp or dry cloth. Typical window cleaning agents may be applied
to aid in the removal of dirt, dust and grease. Do not use abrasive
cleaners.
The Reset switch can be
found on the bottom of the
TOUCH 1500.
North America
Tel +1.800.545.6258
Fax +1.800.527.5703
Europe, Middle East, Africa
Tel +32.16.213.511
Fax +32.16.213.604
Asia Pacific
Tel +86.21.2412.1688
Fax +86.21.5426.3167
Latin America
Tel +1.713.868.4800
Fax +1.713.868.2333
nVent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its aliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specications without notice.
Raychem-IM-H58559-INSTALL170-Touch1500-EN-1805
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

nvent TOUCH 1500 Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI