5
© Danfoss, AC-MCI/MWA, 12-2011
Refrigerants
Applicable to HCFC, non ammable HFC, R717
(Ammonia) and R744 (CO
2
).
For further information please refer to
installation instruction for ICF.
Use of the ICF valve station with ammable
hydrocarbons is not recommended.
For further information please contact the
local Danfoss sales company.
Temperature range
–60/+120°C (–76/+248°F).
If the ICM module is going to be used in liquid
refrigerant with a temperature above +75°C
(+167°F), please contact Danfoss.
Ambient temperature for ICF with ICAD:
–30°C/+50°C (–22°F/122°F)
The valve train of the
Future since 2005
The ICF valve station is an innovative solution
that provides the full functionality of a
conventional valve station in a single compact
unit.
Eliminate project bottleneck:
Conventional valve stations of six or more
individual components and up to twelve welds.
ICF means two welds directly at the job site
Down time during service is reduced to a fraction
compared to conventional valve trains. The
unique design of the ICF ensures a quick pump
down and faster access to valve modules.
The ICF valve is a compact valve train ready for
the jobsite.
This solution provides you with a variety of
benets:
Designed for Industrial Refrigeration
Supplied fully assembled. No need to
disassembly prior to installation under normal
welding procedures
Standard side ports to t service valves,
pressure transmitters, sight glasses.
Applicable to HCFC, non ammable HFC, R717
(Ammonia) and R744 (CO
2
).
Direct Weld Connections (No leaks through
anges)
Compact design, faster service
Available with dierent connection types
including ANSI and DIN, Socket weld
High capacities low pressure drop
Low weight design
Approvals
ICF valve station
Nominal bore
DN ≤ 25 (1 in.)
DN 32-40 (1¼ - 1½”)
Classied for Fluid group I
Category Article 3, paragraph 3 II
Technical data
Surface protection
The external surface is zinc-chromated to
provide corrosion protection according to
EN 12284:2003 8.13.
Additional on-site corrosion protection is
recommended.
Pressure
The ICF is designed for:
Max. working pressure: 52 bar g (754 psig)
Opening dierential pressure
Please refer to the individual function module
data.
CRN
Application Guide ICF Valve Station
DKRCI.PA.FT0.A3.02 / 520H4507