Automation Direct CFW100 Owner's manual

Type
Owner's manual

This manual is also suitable for

Motors | Automation | Energy | Transmission & Distribution | Coatings
Frequency Inverter
CFW100 V4.1X
Programming Manual
Programming Manual
Series: CFW100
Language: English
Document: 10008008405 / 03
Software version: 4.1X
Build 523
Publication Date: 10/2020
SUMMARY OF REVISIONS
The information below describes the reviews made in this manual.
Version Revision Description
3.0X R00 First edition.
3.1X R01
General revision.
4.0X R02
General revision.
New parameters P760, P761, P762, P763, P764, P765.
New options in the range of parameter values: P263 to P270, P310 and P312.
Inclusion of the BACnet Protocol.
Firmware update via WPS.
4.1X R03
General revision.
New parameters P042, P043.
SUMMARY
0 QUICK REFERENCE OF PARAMETERS ....................................... 0-1
1 QUICK REFERENCE OF ALARMS AND FAULTS .......................... 1-1
2 SAFETY NOTICES ...................................................... . . . . . . . . . . . . . . 2-1
2.1 SAFETY NOTICES IN THIS MANUAL .... .. .. .. .. .. .. .. .. .. .. .. .. ...................................... 2-1
2.2 SAFETY NOTICES ON THE PRODUCT ................................................................ 2-1
2.3 PRELIMINARY RECOMMENDATIONS .. .. .. .. .. .. .. .. .. .. .. .. .. .. .................................... 2-2
3 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 TERMINOLOGY AND DEFINITIONS . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ...................... 3-1
3.1.1 Terms and Definitions Used.. .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... . 3-1
3.1.2 Numerical Representation . ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... .. 3-2
3.1.3 Symbols to Describe Parameter Properties .. ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... .. 3-2
4 ABOUT THE HMI ...................................................................... 4-1
4.1 USE OF THE HMI TO OPERATE THE INVERTER .. .. .. .. .. .. .. .. .. .. .. .. .. .. ........................ 4-1
4.2 INDICATIONS ON THE HMI DISPLAY . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 4-1
4.3 OPERATING MODES OF THE HMI ..................................................................... 4-1
5 HMI ....................................................... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1 ACCESS ............................ .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 5-1
5.2 INDICATIONS ................... .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 5-3
6 FREQUENCY INVERTER IDENTIFICATION ................................... 6-1
6.1 INVERTER MODEL . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .......................................... 6-1
6.2 ACCESSORIES ..................................... .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 6-2
7 COMMAND AND REFERENCES ................................................. 7-1
7.1 REFERENCE SOURCE SELECTION . .. .. .. .. .......................................................... 7-1
7.2 SPEED REFERENCE . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ...................... 7-6
8 MOTOR CONTROL ..................................... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1 COMMON FUNCTIONS .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 8-1
8.1.1 Ramps .. ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. 8-1
8.1.2 Regulation .. ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... 8-3
8.1.2.1 DC Link Voltage . .. .. .. .. ...............................................................8-3
8.1.2.1.1 DC Link Voltage Limitation by “Ramp Hold” (P150 = 0 or 2) ...........8-3
8.1.2.1.2 DC Link Voltage Limitation by “Accelerate Ramp” (P150 = 1 or 3). .. .8-4
8.1.2.2 Output Current. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .8-7
8.1.2.2.1 Output Current Limitation by “Ramp Hold” (P150 = 2 or 3) ............8-7
8.1.2.2.2 Current Limitation Type “Decelerate Ramp” (P150 = 0 or 1) ...........8-7
8.1.2.3 Switching Frequency . .. .. .. .. .. .. .. .. .. ...............................................8-8
8.1.3 Flying Start / Ride-Through ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... ... .. ... ... 8-9
8.1.4 DC Braking ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... .8-10
8.1.5 Skip Frequency . ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... .8-12
8.1.6 Fire Mode . ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ..8-13
8.1.7 Control Configuration ... ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... .8-15
8.2 V/F. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .............................................................8-17
8.2.1 Energy Saver (EOC) .. ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ..8-23
8.3 VVW . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .......................................8-25
9 I/O .......................................................................................... 9-1
SUMMARY
9.1 ANALOG INPUTS......................................................................................... 9-1
9.2 EXTERNAL TEMP. SENSOR INPUT .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 9-4
9.3 SIGNAL POTENTIOMETER INPUT. .. .. .. .. .. .. .. .. .. .. .. .. .. .......................................... 9-5
9.4 ANALOG OUTPUTS ................... .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . 9-6
9.5 FREQUENCY INPUT . .. .. .. .. .. .. .. .. .. .. .. .. .. .......................................................... 9-8
9.6 DIGITAL INPUTS .......... .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .9-10
9.7 INPUT FOR INFRARED RECEIVER . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ...9-19
9.8 ENCODER INPUT . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ...........................................9-19
9.9 DIGITAL OUTPUTS. .. .. .. .. ..............................................................................9-20
10 FAULTS AND ALARMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ................10-1
10.1 FAULT HISTORY . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .10-1
10.2 FAULT CONTROL ........................................................................................10-2
10.3 PROTECTIONS ............................. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..10-3
10.3.1 Inverter .. ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ..10-3
10.3.1.1 DC Link Voltage Supervision ............................. .. .. .. .. .. .. .. .. .. .. .. .. .. ..10-3
10.3.1.2 Temperature control .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ...............................10-3
10.3.2 Motor... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... .10-3
11 READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-1
12 COMMUNICATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . ........................................12-1
12.1 COMMANDS AND COMMUNICATION STATUS .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..12-1
12.2 SERIAL.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ...........................12-2
12.3 BACNET ............................................... .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..12-3
12.4 CANOPEN AND DEVICENET . .. .. .. .. ..................................................................12-4
13 SOFTPLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ............................................13-1
13.1 COMMAND AND STATUS ...............................................................................13-1
13.2 USER. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..................................................................13-2
14 APPLICATIONS ........................................................................14-1
14.1 PID CONTROLLER .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .....14-1
14.1.1 Start-Up ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ..14-3
14.1.2 Academic PID Controller . ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ..14-5
14.1.3 Parameters ... ... ... .. ... ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... .14-5
14.1.4 Sleep Mode. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ...14-14
15 APPLICATION EXAMPLES .................. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15-1
15.1 ANALOG INPUT APPLICATIONS . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..................................15-1
15.1.1 Application 1 - Nominal speed . ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. .15-2
15.1.2 Application 2 - Overspeed ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ..15-3
15.1.3 Application 3 - Forward/Reverse using Analog Input . ... ... ... .. ... ... ... ... .. ... ... ... ... ... ..15-4
15.1.4 Application 4 - Analog input with dead zone .. ... ... ... .. ... ... ... ... ... .. ... ... ... ... .. ... ... ... .15-5
15.1.5 Application 5 - Reverse reference with Analog input .. ... .. ... ... ... ... .. ... ... ... ... ... .. ... ..15-6
15.2 PID CONTROLLER APPLICATION ............................ .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .15-7
0
QUICK REFERENCE OF PARAMETERS
0 QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P000 Access to Parameters 0 to 9999 1 5-1
P001 Speed Reference 0 to 9999 ro 11-1
P002 Output Speed (Motor) 0 to 9999 ro 11-1
P003 Motor Current 0.0 to 10.0 A ro 11-1
P004 DC Link Voltage 0 to 524 V ro 11-1
P005 Output Frequency (Motor) 0.0 to 400.0 Hz ro 11-1
P006 Inverter Status 0 = Ready
1 = Run
2 = Undervoltage
3 = Fault
4 = Self-Tuning
5 = Configuration
6 = DC Braking
7 = Reserved
8 = Fire Mode
ro 11-2
P007 Output Voltage 0 to 240 V ro 11-3
P009 Motor Torque -200.0 to 200.0 % ro, VVW 11-4
P011 Power Factor 0.00 to 1.00 ro 8-23
P012 DI8 to DI1 Status 0 to FF (hexa)
Bit 0 = DI1
Bit 1 = DI2
Bit 2 = DI3
Bit 3 = DI4
Bit 4 = DI5
Bit 5 = DI6
Bit 6 = DI7
Bit 7 = DI8
ro 9-11
P013
(*)
DO3 to DO1 Status 0 to 7 (hexa)
Bit 0 = DO1
Bit 1 = DO2
Bit 2 = DO3
ro 9-20
P014
(*)
AO1 Value 0.0 to 100.0 % ro 9-6
P018
(*)
AI1 Value -100.0 to 100.0 % ro 9-1
P020
(*)
Potentiometer Signal Value -100.0 to 100.0 % ro 9-5
P022 FI Value in Hz 0 to 3000 Hz ro 9-9
P023 Main SW Version 0.00 to 99.99 ro 6-1
P024
(*)
Accessory SW Version 0.00 to 99.99 ro 6-2
P027 Accessory Config. 0 = Without Accessory
1 = CFW100-HMIR
2 = CFW100-IOAR
3 = CFW100-CCAN
4 = Reserved
5 = CFW100-IODR
6 = CFW100-IOADR
7 = CFW100-IOA
8 = CFW100-IOD
9 = Reserved
10 = CFW100-IOP
ro 6-2
P029 Power HW Configuration 0 = Not identified
1 = 1.6 A/110 V
2 = 2.6 A/110 V
3 = 4.2 A/110 V
4 = 6.0 A/110 V
5 = 1.6 A/220 V
6 = 2.6 A/220 V
7 = 4.2 A/220 V
8 = 6.0 A/220 V
9 = 7.3 A/220 V
10 to 29 = Reserved
According to the
Inverter Model
ro 6-1
P030 Module Temperature -200.0 to 200.0 ºC ro 11-4
P037 Motor Overload Ixt 0.0 to 100.0 % ro 10-4
P038
(*)
Encoder Speed 0 to 270F (hexa) ro 9-19
P039
(*)
Encoder Pulses Count 0 to FFFF (hexa) ro 9-19
P042 Running Time 0.0 to 999.9 ro 11-4
P043 Running Time(h/1000) 0 to 9999 ro 11-4
P045 Fan Enabled Time 0 to FFFF (hexa) ro 11-4
CFW100 | 0-1
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P047 CONF Status 0 to 33 (Table 11.3 on page 11-5) ro 11-5
P048 Present Alarm 0 to 999 ro 10-1
P049 Present Fault 0 to 999 ro 10-1
P050 Last Fault 0 to 999 ro 10-1
P051 Current At Last Fault 0.0 to 10.0 A ro 10-1
P052 DC Link At Last Fault 0 to 524 V ro 10-1
P053 Frequency At Last Fault 0.0 to 400.0 Hz ro 10-2
P054 Temperature Last Fault 0.0 to 200.0 ºC ro 10-2
P060 Second Fault 0 to 999 ro 10-1
P070 Third Fault 0 to 999 ro 10-1
P080 Last Fault on Fire Mode 0 to 999 ro 10-2
P081 Second Fault on Fire Mode 0 to 999 ro 10-2
P082 Third Fault on Fire Mode 0 to 999 ro 10-2
P100 Acceleration Time 0.1 to 999.9 s 5.0 s 8-2
P101 Deceleration Time 0.1 to 999.9 s 10.0 s 8-2
P102 Acceleration Time 2nd Ramp 0.1 to 999.9 s 5.0 s 8-2
P103 Deceleration Time 2nd Ramp 0.1 to 999.9 s 10.0 s 8-2
P104 Ramp S 0 = Inactive
1 = Active
0 cfg 8-2
P105 1st / 2nd Ramp Selection 0 = 1st Ramp
1 = 2nd Ramp
2 = DIx
3 = Serial/USB
4 = Reserved
5 = CO/DN
6 = SoftPLC
0 8-3
P106 Emer. R. Acceleration Time 0.1 to 999.9 s 5.0 s 8-2
P107 Emer. R. Time Deceleration 0.1 to 999.9 s 5.0 s 8-2
P120 Speed Ref. Backup 0 = Inactive
1 = Active
2 = Backup by P121
1 7-7
P121 Reference via HMI 0.0 to 400.0 Hz 3.0 Hz 7-7
P122 JOG Reference -400.0 to 400.0 Hz 5.0 Hz 7-8
P124 Multispeed Ref. 1 -400.0 to 400.0 Hz 3.0 Hz 7-8
P125 Multispeed Ref. 2 -400.0 to 400.0 Hz 10.0 (5.0) Hz 7-8
P126 Multispeed Ref. 3 -400.0 to 400.0 Hz 20.0 (10.0) Hz 7-8
P127 Multispeed Ref. 4 -400.0 to 400.0 Hz 30.0 (20.0) Hz 7-8
P128 Multispeed Ref. 5 -400.0 to 400.0 Hz 40.0 (30.0) Hz 7-8
P129 Multispeed Ref. 6 -400.0 to 400.0 Hz 50.0 (40.0) Hz 7-8
P130 Multispeed Ref. 7 -400.0 to 400.0 Hz 60.0 (50.0) Hz 7-8
P131 Multispeed Ref. 8 -400.0 to 400.0 Hz 66.0 (55.0) Hz 7-8
P133 Minimum Frequency 0.0 to 400.0 Hz 3.0 Hz 7-9
P134 Maximum Frequency 0.0 to 400.0 Hz 66.0 (55.0) Hz 7-9
P135 Maximum Output Current 0.0 to 40.0 A 1.5 x I
nom
V/f 8-7
P136 Manual Torque Boost 0.0 to 30.0 % According to the
Inverter Model
V/f 8-20
P137 Automatic Torque Boost 0.0 to 30.0 % 0.0 % V/f 8-21
P138 Slip Compensation -10.0 to 10.0 % 0.0 % V/f 8-21
P139 Output Current Filter 0.000 to 9.999 s 0.050 s V/f, VVW 8-8
P140 Slip Com. Filter 0.000 to 9.999 s 0.500 s VVW 8-29
P142 Maximum Output Voltage 0.0 to 100.0 % 100.0 % cfg, V/f 8-22
P143 Intermediate Output Voltage 0.0 to 100.0 % 50.0 % cfg, V/f 8-22
P145 Field Weakening Speed 0.0 to 400.0 Hz 60.0 (50.0) Hz cfg, V/f 8-22
P146 Intermediate Frequency 0.0 to 400.0 Hz 30.0 (25.0) Hz cfg, V/f 8-22
P149 DC Link Comp. Mode 0 = Inactive
1 = Standard
2 = Overmodulation
3 = Extended
0 cfg, V/f 8-4
P150 DC/LC Regul. Type 0 = hold_Ud and decel_LC
1 = accel_Ud and decel_LC
2 = hold_Ud and hold_LC
3 = accel_Ud and hold_LC
0 cfg, V/f,
VVW
8-3
P151 DC Link Regul. Level 325 to 460 V 430 V (P296 = 1)
380 V (P296 = 2)
V/f, VVW 8-5
0-2 | CFW100
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P156 Rated Speed Overload Current 0.1 to 40.0 A 1.2 x I
nom
10-5
P157 Overl.Curr.50 % Speed 0.1 to 40.0 A 1.2 x I
nom
10-5
P158 Overl.Curr.20 % Speed 0.1 to 40.0 A 1.2 x I
nom
10-5
P178 Rated Flux 50.0 to 150.0 % 100.0 % VVW 8-29
P200 Password 0 = Inactive
1 = Active
2 to 9999 = New Password
0 cfg 5-1
P202 Type of Control 0 = V/f
1 = Quadratic V/f
2 to 4 = Not Used
5 = VVW
0 cfg 8-1
P204 Load/Save Parameters 0 to 4 = Not Used
5 = Load 60 Hz
6 = Load 50 Hz
7 = Load User
8 = Not Used
9 = Save User
10 = Not Used
11 = Load Default SoftPLC
12 to 13 = Reserved
0 cfg 5-2
P205 Main Display Parameter 0 to 999 2 5-3
P207 Bar Graph Parameter 0 to 999 3 5-3
P208 Ref. Scale Factor 1 to 9999 600 5-3
P209 Ref. Eng. Unit 0 to 1 = Without unit
2 = Volt (V)
3 = Hertz (Hz)
4 = Without unit
5 = Percent (%)
6 = Without unit
7 = Rotation/min. (rpm)
3 5-3
P210 Ref. Decimal Point 0 = wxyz
1 = wxy.z
2 = wx.yz
3 = w.xyz
1 5-4
P213 Bar Scale Factor 1 to 9999 1.0 x I
nom
5-4
P219 Red. Switch. Freq. 0.0 to 15.0 Hz 5.0 Hz cfg 8-8
P220 LOC/REM Selection Source 0 = Always Local
1 = Always Remote
2 to 3 = Not Used
4 = DIx
5 = Serial/USB (LOC)
6 = Serial/USB (REM)
7 to 8 = Not Used
9 = CO/DN (LOC)
10 = CO/DN (REM)
11 = SoftPLC
0 cfg 7-4
P221 LOC Reference Sel. 0 = HMI
1 = AI1
2 = Not Used
3 = Potentiometer
4 = FI
5 to 6 = Not Used
7 = E.P.
8 = Multispeed
9 = Serial/USB
10 = Not Used
11 = CO/DN
12 = SoftPLC
13 = Not Used
14 = AI1 > 0
15 = Not Used
16 = Potentiometer > 0
17 = FI > 0
0 cfg 7-4
P222 REM Reference Selection See options in P221 2 cfg 7-4
CFW100 | 0-3
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P223 LOC FWD/REV Selection 0 = Forward
1 = Reverse
2 to 3 = Not Used
4 = DIx
5 = Serial/USB (FWD)
6 = Serial/USB (REV)
7 to 8 = Not Used
9 = CO/DN (FWD)
10 = CO/DN (REV)
11 = Not Used
12 = SoftPLC
0 cfg 7-5
P224 LOC Run/Stop Sel. 0 = HMI Keys
1 = DIx
2 = Serial/USB
3 = Not Used
4 = CO/DN
5 = SoftPLC
0 cfg 7-5
P225 LOC JOG Selection 0 = Disabled
1 = Not Used
2 = DIx
3 = Serial/USB
4 = Not Used
5 = CO/DN
6 = SoftPLC
1 cfg 7-5
P226 REM FWD/REV Selection See options in P223 4 cfg 7-5
P227 REM Run/Stop Selection See options in P224 1 cfg 7-5
P228 REM JOG Selection See options in P225 2 cfg 7-6
P229 Stop Mode Selection 0 = Ramp to Stop
1 = Coast to Stop
0 cfg 7-6
P230 Dead Zone (AIs and FI1 ) 0 = Inactive
1 = Active
0 cfg 9-1
P231
(*)
AI1 Signal Function 0 = Speed Ref.
1 to 3 = Not Used
4 = PTC
5 to 6 = Not Used
7 = PLC Use
8 = Application Function 1
9 = Application Function 2
10 = Application Function 3
11 = Application Function 4
12 = Application Function 5
13 = Application Function 6
14 = Application Function 7
15 = Application Function 8
16 = Control Setpoint
17 = Process Variable
0 cfg 9-2
P232
(*)
AI1 Input Gain 0.000 to 9.999 1.000 9-3
P233
(*)
AI1 Input Signal 0 = 0 to 10 V / 20 mA
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
0 9-3
P234
(*)
AI1 Input Offset -100.0 to 100.0 % 0.0 % 9-4
P235
(*)
AI1 Input Filter 0.00 to 16.00 s 0.00 s 9-4
P241
(*)
Potentiometer Signal Function 0 = Speed Ref.
1 to 6 = Not Used
7 = SoftPLC
8 = Application Function 1
9 = Application Function 2
10 = Application Function 3
11 = Application Function 4
12 = Application Function 5
13 = Application Function 6
14 = Application Function 7
15 = Application Function 8
16 to 17 = Not Used
0 cfg 9-5
P242
(*)
Potentiometer Signal Gain 0.000 to 9.999 1.000 9-5
P244
(*)
Potentiometer Signal Offset -100.0 to 100.0 % 0.0 % 9-6
P245 Potentiometer and FI1 Filter 0.00 to 16.00 s 0.00 s 9-6
P246 FI1 Input Function 0 = Inactive
1 = Active in DI1
2 = Active in DI2
3 = Active in DI3
4 = Active in DI4
0 cfg 9-10
0-4 | CFW100
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P247 FI1 Input Gain 0.000 to 9.999 1.000 9-10
P248 FI1 Minimum Input 1 to 3000 Hz 100 Hz 9-10
P249 FI1 Input Offset -100.0 to 100.0 % 0.0 % 9-10
P250 FI1 Maximum Input 1 to 3000 Hz 1000 Hz 9-10
P251
(*)
AO1 Output Function 0 = Speed Ref.
1 = Not Used
2 = Real Speed
3 to 4 = Not Used
5 = Output Current
6 = Not Used
7 = Active Current
8 to 10 = Not Used
11 = Motor Torque
12 = SoftPLC
13 to 15 = Not Used
16 = Motor Ixt
17 to 20 = Not Used
21 = Application Function 1
22 = Application Function 2
23 = Application Function 3
24 = Application Function 4
25 = Application Function 5
26 = Application Function 6
27 = Application Function 7
28 = Application Function 8
29 = Control Setpoint
30 = Process Variable
2 9-7
P252
(*)
AO1 Output Gain 0.000 to 9.999 1.000 9-7
P253
(*)
AO1 Output Signal 0 = 0 to 10 V
1 = 0 to 20 mA
2 = 4 to 20 mA
3 = 10 to 0 V
4 = 20 to 0 mA
5 = 20 to 4 mA
0 9-8
CFW100 | 0-5
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P263 DI1 Input Function 0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Quick Stop
4 = Forward Run
5 = Reverse Run
6 = Start
7 = Stop
8 = Direction of Rotation
9 = LOC/REM
10 = JOG
11 = Accelerate E.P.
12 = Decelerate E.P.
13 = Multispeed
14 = 2nd Ramp
15 to 17 = Not Used
18 = No Ext. Alarm
19 = No Ext. Fault
20 = Reset
21 to 23 = Not Used
24 = Disab.FlyStart
25 = Not Used
26 = Lock Prog.
27 to 31 = Not Used
32 = 2nd Ramp Multispeed
33 = 2nd Ramp Increase E.P.
34 = 2nd Ramp Decrease E.P.
35 = 2nd Ramp FWD Run
36 = 2nd Ramp REV Run
37 = Start / Inc. E.P.
38 = Dec. E.P. / Stop
39 = Stop
40 = Safety Switch
41 = Application Function 1
42 = Application Function 2
43 = Application Function 3
44 = Application Function 4
45 = Application Function 5
46 = Application Function 6
47 = Application Function 7
48 = Application Function 8
49 = Enable Fire Mode
50 to 54 = Not Used
55 = Run/Stop with Line Start
Lockout
56 = Forward Run with Line Start
Lockout
57 = Reverse Run with Line Start
Lockout
1 cfg 9-11
0-6 | CFW100
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P264 DI2 Input Function 0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Quick Stop
4 = Forward Run
5 = Reverse Run
6 = Start
7 = Stop
8 = Direction of Rotation
9 = LOC/REM
10 = JOG
11 = Accelerate E.P.
12 = Decelerate E.P.
13 = Multispeed
14 = 2nd Ramp
15 to 17 = Not Used
18 = No Ext. Alarm
19 = No Ext. Fault
20 = Reset
21 to 23 = Not Used
24 = Disab.FlyStart
25 = Not Used
26 = Progr. Off
27 to 31 = Not Used
32 = 2nd Ramp Multispeed
33 = 2nd Ramp Increase E.P.
34 = 2nd Ramp Decrease E.P.
35 = 2nd Ramp FWD Run
36 = 2nd Ramp REV Run
37 = Turn ON / Ac. E.P.
38 = De. E.P. / Turn OFF
39 = Stop
40 = Safety Switch
41 = Application Function 1
42 = Application Function 2
43 = Application Function 3
44 = Application Function 4
45 = Application Function 5
46 = Application Function 6
47 = Application Function 7
48 = Application Function 8
49 = Enable Fire Mode
50 = PID Manual / Automatic
51 to 54 = Not Used
55 = Run/Stop with Line Start
Lockout
56 = Forward Run with Line Start
Lockout
57 = Reverse Run with Line Start
Lockout
8 cfg 9-11
CFW100 | 0-7
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P265 DI3 Input Function 0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Quick Stop
4 = Forward Run
5 = Reverse Run
6 = Start
7 = Stop
8 = Direction of Rotation
9 = LOC/REM
10 = JOG
11 = Accelerate E.P.
12 = Decelerate E.P.
13 = Multispeed
14 = 2nd Ramp
15 to 17 = Not Used
18 = No Ext. Alarm
19 = No Ext. Fault
20 = Reset
21 to 23 = Not Used
24 = Disab.FlyStart
25 = Not Used
26 = Lock Prog.
27 to 31 = Not Used
32 = 2nd Ramp Multispeed
33 = 2nd Ramp Increase E.P.
34 = 2nd Ramp Decrease E.P.
35 = 2nd Ramp FWD Run
36 = 2nd Ramp REV Run
37 = Start / Inc. E.P.
38 = Dec. E.P. / Stop
39 = Stop
40 = Safety Switch
41 = Application Function 1
42 = Application Function 2
43 = Application Function 3
44 = Application Function 4
45 = Application Function 5
46 = Application Function 6
47 = Application Function 7
48 = Application Function 8
49 = Enable Fire Mode
50 = Not Used
51 = Command to Increase the
Control Setpoint (EP)
52 = Not Used
53 = 1st DI for Control Setpoint
Selection
54 = Not Used
55 = Run/Stop with Line Start
Lockout
56 = Forward Run with Line Start
Lockout
57 = Reverse Run with Line Start
Lockout
0 cfg 9-11
0-8 | CFW100
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P266 DI4 Input Function 0 = Not Used
1 = Run/Stop
2 = General Enable
3 = Quick Stop
4 = Forward Run
5 = Reverse Run
6 = Start
7 = Stop
8 = Direction of Rotation
9 = LOC/REM
10 = JOG
11 = Accelerate E.P.
12 = Decelerate E.P.
13 = Multispeed
14 = 2nd Ramp
15 to 17 = Not Used
18 = No Ext. Alarm
19 = No Ext. Fault
20 = Reset
21 to 23 = Not Used
24 = Disab.FlyStart
25 = Not Used
26 = Progr. Off
27 to 31 = Not Used
32 = 2nd Ramp Multispeed
33 = 2nd Ramp Increase E.P.
34 = 2nd Ramp Decrease E.P.
35 = 2nd Ramp FWD Run
36 = 2nd Ramp REV Run
37 = Start / Inc. E.P.
38 = Dec. E.P. / Stop
39 = Stop
40 = Safety Switch
41 = Application Function 1
42 = Application Function 2
43 = Application Function 3
44 = Application Function 4
45 = Application Function 5
46 = Application Function 6
47 = Application Function 7
48 = Application Function 8
49 = Enable Fire Mode
50 to 51 = Not Used
52 = Command to Decrease the
Control Setpoint (EP)
53 = Not Used
54 = 2nd DI for Control Setpoint
Selection
55 = Run/Stop with Line Start
Lockout
56 = Forward Run with Line Start
Lockout
57 = Reverse Run with Line Start
Lockout
0 cfg 9-11
P267
(*)
DI5 Input Function See options in P263 0 cfg 9-11
P268
(*)
DI6 Input Function See options in P263 0 cfg 9-11
P269
(*)
DI7 Input Function See options in P263 0 cfg 9-11
P270
(*)
DI8 Input Function See options in P263 0 cfg 9-12
P271 DIs Function 0 = (DI1..DI8)NPN
1 = (DI1..DI4)PNP
2 = (DI5..DI8)PNP
3 = (DI1..DI8)PNP
0 cfg 9-14
CFW100 | 0-9
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P275
(*)
DO1 Function 0 = Not Used
1 = F* ≥ Fx
2 = F ≥ Fx
3 = F ≤ Fx
4 = F = F*
5 = Not Used
6 = Is > Ix
7 = Is < Ix
8 = Torque > Tx
9 = Torque < Tx
10 = Remote
11 = Run
12 = Ready
13 = No Fault
14 = No F070
15 = Not Used
16 = No F021/F022
17 = Not Used
18 = No F072
19 = 4-20 mA OK
20 = Not Used
21 = Forward
22 to 23 = Not Used
24 = Ride-Through
25 = Pre-Charge OK
26 = Fault
27 = Not Used
28 = SoftPLC
29 to 34 = Not Used
35 = No Alarm
36 = Without fault and alarm
37 = Application Function 1
38 = Application Function 2
39 = Application Function 3
40 = Application Function 4
41 = Application Function 5
42 = Application Function 6
43 = Application Function 7
44 = Application Function 8
45 = Fire Mode ON
46 = Low Level of Process Variable
47 = High Level of Process Variable
13 9-20
P276
(*)
DO2 Function See options in P275 0 9-20
P277
(*)
DO3 Function See options in P275 0 9-21
P281
(*)
Fx Frequency 0.0 to 400.0 Hz 3.0 Hz 9-22
P282
(*)
Fx Hysteresis 0.0 to 15.0 Hz 0.5 Hz 9-23
P290
(*)
Ix Current 0.0 to 10.0 A 1.0 x I
nom
9-23
P293
(*)
Tx Torque 0 to 200 % 100 % 9-23
P295 Inverter Rated Current 1.6 to 7.3 A According to the
Inverter Model
ro 6-2
P296 Line Rated Voltage 0 = Reserved
1 = 110 - 127 Vac
2 = 200 - 240 Vac
According to the
Inverter Model
ro 6-2
P297 Switching Frequency 2.5 to 15.0 kHz 5.0 kHz cfg, V/f,
VVW
8-9
P299 DC Braking Start Time 0.0 to 15.0 s 0.0 s V/f, VVW 8-10
P300 DC Braking Stop Time 0.0 to 15.0 s 0.0 s V/f, VVW 8-11
P301 DC Braking Frequency 0.0 to 15.0 Hz 3.0 Hz V/f, VVW 8-11
P302 DC Braking Current 0.0 to 100.0 % 20.0 % V/f, VVW 8-12
P303 Skip Frequency 1 0.0 to 400.0 Hz 0.0 Hz V/f, VVW 8-12
P304 Skip Frequency 2 0.0 to 400.0 Hz 0.0 Hz V/f, VVW 8-12
P306 Skip Band 0.0 to 25.0 Hz 0.0 Hz V/f, VVW 8-12
P308 Serial Address 1 to 247 1 cfg 12-2
P310 Serial Baud Rate 0 = 9600 bits/s
1 = 19200 bits/s
2 = 38400 bits/s
3 = 57600 bits/s
4 = 76800 bits/s
1 cfg 12-3
0-10 | CFW100
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P311 Serial Bytes Config. 0 = 8 bits, no, 1
1 = 8 bits, even,1
2 = 8 bits, odd, 1
3 = 8 bits, no, 2
4 = 8 bits, even,2
5 = 8 bits, odd, 2
1 cfg 12-3
P312 Serial Protocol 0 to 1 = Reserved
2 = Modbus RTU Slave
3 = BACnet
4 = Reserved
5 = ModBus RTU Master
2 cfg 12-3
P313 Action for Communic. Error 0 = Inactive
1 = Ramp Stop
2 = General Disable
3 = Go to LOC
4 = LOC Keep Enab.
5 = Cause Fault
1 12-1
P314 Serial Watchdog 0.0 to 999.0 s 0.0 s cfg 12-3
P316 Serial Interf. Status 0 = Inactive
1 = Active
2 = Watchdog Error
ro 12-3
P320 Flying Start / Ride-Through 0 = Inactive
1 = Flying Start
2 = FS / RT
3 = Ride-Through
0 cfg 8-9
P331 Voltage Ramp for FS and RT 0.2 to 60.0 s 2.0 s 8-10
P332 Dead Time 0.1 to 10.0 s 1.0 s 8-10
P340 Auto-Reset Time 0 to 255 s 0 s 10-2
P352 Fan Control Config. 0 = OFF
1 = ON
2 = CT
2 cfg 10-3
P375
(*)
External Sensor Temp. 0 to 200 ºC ro 9-4
P397 Control Config 0 to F (hexa)
Bit 0 = Slip Compens. Regen.
Bit 1 = Reserved
Bit 2 = Is Stabilization
Bit 3 = P297 reduction in A050
1 (hexa) cfg 8-15
P399 Motor Rated Efficiency 50.0 to 99.9 % According to the
Inverter Model
cfg, VVW 8-29
P400 Motor Rated Voltage 0 to 240 V 220 V cfg, VVW 8-29
P401 Motor Rated Current 0.0 to 10.0 A 1.0 x I
nom
cfg, VVW 8-30
P402 Motor Rated Speed 0 to 24000 rpm 1720 rpm cfg, VVW 8-30
P403 Motor Rated Frequency 0 to 400 Hz 60 Hz cfg, VVW 8-30
P404 Motor Rated Power 0 = 0.16 HP (0.12 kW)
1 = 0.25 HP (0.18 kW)
2 = 0.33 HP (0.25 kW)
3 = 0.50 HP (0.37 kW)
4 = 0.75 HP (0.55 kW)
5 = 1.00 HP (0.75 kW)
According to the
Inverter Model
cfg, VVW 8-30
P407 Motor Rated Power Factor 0.50 to 0.99 According to the
Inverter Model
cfg, VVW 8-23
P408 Run Self-Tuning 0 = No
1 = Yes
0 cfg, VVW 8-30
P409 Stator Resistance 0.01 to 99.99 According to the
Inverter Model
cfg, VVW 8-31
P510 SoftPLC Eng. Unit See options in P209 0 5-3
P511 SoftPLC Indication Form See options in P210 1 5-4
P580 Fire Mode Config 0 = Inactive
1 = Active
2 = Active / P134
3 = Reserved
4 = Active / General Disable
0 cfg 8-15
P582 Fire Mode Auto-reset Adjustable 0 = Limited
1 = Unlimited
0 cfg 8-15
P588 EOC Maximum Torque 0 to 85 % 0 % cfg 8-24
P589 EOC Minimum Voltage 40 to 80 % 40 % cfg 8-24
P590 EOC Minimum Frequency 12.0 to 400.0 Hz 20.0 Hz cfg 8-24
P591 EOC Hysteresis 0 to 30 % 10 % cfg 8-24
P613 Main SW Revision -9999 to 9999 ro 6-2
CFW100 | 0-11
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P680 Logical Status 0 to FFFF (hexa)
Bit 0 = Reserved
Bit 1 = Run Command
Bit 2 = Fire Mode
Bit 3 to 4 = Reserved
Bit 5 = 2nd Ramp
Bit 6 = Config. Mode
Bit 7 = Alarm
Bit 8 = Running
Bit 9 = Enabled
Bit 10 = Forward
Bit 11 = JOG
Bit 12 = Remote
Bit 13 = Subvoltage
Bit 14 = Reserved
Bit 15 = Fault
ro 11-6
P681 13-Bit Speed 0 to FFFF (hexa) ro 11-7
P682 Serial/USB Control 0 to FFFF (hexa)
Bit 0 = Ramp Enable
Bit 1 = General Enable
Bit 2 = Run Forward
Bit 3 = JOG Enable
Bit 4 = Remote
Bit 5 = 2nd Ramp
Bit 6 = Reserved
Bit 7 = Fault Reset
Bit 8 to 15 = Reserved
ro 12-1
P683 Serial/USB Speed Ref. 0 to FFFF (hexa) ro 12-2
P684
(*)
CO/DN Control 0 to FFFF (hexa)
Bit 0 = Ramp Enable
Bit 1 = General Enable
Bit 2 = Run Forward
Bit 3 = JOG Enable
Bit 4 = Remote
Bit 5 = 2nd Ramp
Bit 6 = Reserved
Bit 7 = Fault Reset
Bit 8 to 15 = Reserved
ro 12-1
P685
(*)
CO/DN Speed Ref 0 to FFFF (hexa) ro 12-2
P690 Logic State 2 0 to FFFF (hexa)
Bit 0 to 1 = Reserved
Bit 2 = DC Link Voltage Extended
Bit 3 = Energy Saver
Bit 4 = Fs Reduction
Bit 5 = Reserved
Bit 6 = Deceleration Ramp
Bit 7 = Acceleration Ramp
Bit 8 = Freeze Ramp
Bit 9 = Setpoint Ok
Bit 10 = DC Link Regulation
Bit 11 = 50 Hz Config
Bit 12 = Ride-Through
Bit 13 = Flying Start
Bit 14 = DC Braking
Bit 15 = PWM pulse
ro 11-7
P700
(*)
CAN Protocol 1 = CANopen
2 = DeviceNet
12-4
P701
(*)
CAN Address 0 to 127 63 12-4
P702
(*)
CAN Baud Rate 0 = 1 Mbps/Auto
1 = Reserved/Auto
2 = 500 Kbps
3 = 250 Kbps
4 = 125 Kbps
5 = 100 Kbps/Auto
6 = 50 Kbps/Auto
7 = 20 Kbps/Auto
8 = 10 Kbps/Auto
0 12-5
P703
(*)
Bus Off Reset 0 = Manual
1 = Automatic
1 12-5
0-12 | CFW100
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P705
(*)
CAN Controller Status 0 = Disabled
1 = Auto-baud
2 = CAN Active
3 = Warning
4 = Error Passive
5 = Bus Off
6 = No Bus Power
ro 12-5
P706
(*)
RX CAN Telegrams 0 to 9999 ro 12-5
P707
(*)
TX CAN Telegrams 0 to 9999 ro 12-5
P708
(*)
Bus Off Counter 0 to 9999 ro 12-5
P709
(*)
CAN Lost Messages 0 to 9999 ro 12-5
P710
(*)
DeviceNet I/O instances 0 = ODVA Basic 2W
1 = ODVA Extend 2W
2 = Manuf.Spec.2W
3 = Manuf.Spec.3W
4 = Manuf.Spec.4W
5 = Manuf.Spec.5W
6 = Manuf.Spec.6W
0 12-6
P711
(*)
DeviceNet Read Word #3 0 to 1199 0 12-6
P712
(*)
DeviceNet Read Word #4 0 to 1199 0 12-6
P713
(*)
DeviceNet Read Word #5 0 to 1199 0 12-6
P714
(*)
DeviceNet Read Word #6 0 to 1199 0 12-6
P715
(*)
DeviceNet Write Word #3 0 to 1199 0 12-6
P716
(*)
DeviceNet Write Word #4 0 to 1199 0 12-6
P717
(*)
DeviceNet Write Word #5 0 to 1199 0 12-6
P718
(*)
DeviceNet Write Word #6 0 to 1199 0 12-6
P719
(*)
DeviceNet Network Status 0 = Offline
1 = OnLine, NotConn
2 = OnLine, Connect.
3 = Connection Timed out
4 = Link Failure
5 = Auto-Baud
ro 12-6
P720
(*)
DeviceNet Master Status 0 = Run
1 = Idle
ro 12-6
P721
(*)
CANopen Comm. Status 0 = Disabled
1 = Reserved
2 = Communic. Enabled
3 = Error Ctrl. Enable
4 = Guarding Error
5 = Heartbeat Error
ro 12-7
P722
(*)
CANopen Node Status 0 = Disabled
1 = Initialization
2 = Stopped
3 = Operational
4 = Preoperational
ro 12-7
P760 BACnet Dev Inst Hi 0 to 419 0 12-3
P761 BACnet Dev Inst Lo 0 to 9999 0 12-4
P762 Max Number of master 0 to 127 127 12-4
P763 MS/TP Max info Frame 0 to FFFF (hexa) 1 (hexa) 12-4
P764 I-AM Msg transmition 0 = Power Up
1 = Continuous
0 12-4
P765 Token RX Quantity 0 to FFFF (hexa) ro 12-4
P840
(*)
IR Control Command 0 to FFFF (hexa) ro 9-19
P842
(*)
Quick View 1 IR 0 to 959 2 5-4
P843
(*)
Quick View 2 IR 0 to 959 375 5-4
P900 SoftPLC Status 0 = No Application
1 = Installing Application
2 = Incompat. Application
3 = Application Stopped
4 = Application Running
ro 13-1
P901 SoftPLC Command 0 = Stop Application
1 = Run Application
0 13-1
P902 Scan Cycle Time 0.000 to 9.999 s ro 13-1
P903 SoftPLC Appl. 0 = User
1 = PID Controller
1 cfg 13-1
P904 Action for SoftPLC Application not
Running
0 = Disabled
1 = Cause Alarm (A708)
2 = Cause Fault (F709)
0 13-2
CFW100 | 0-13
0
QUICK REFERENCE OF PARAMETERS
Param. Description Adjustable Range Factory Setting Prop. Page
P910 SoftPLC Parameter 1 -9999 to 9999 0 13-2
P911 SoftPLC Parameter 2 -9999 to 9999 0 13-2
P912 SoftPLC Parameter 3 -9999 to 9999 0 13-2
P913 SoftPLC Parameter 4 -9999 to 9999 0 13-2
P914 SoftPLC Parameter 5 -9999 to 9999 0 13-2
P915 SoftPLC Parameter 6 -9999 to 9999 0 13-2
P916 SoftPLC Parameter 7 -9999 to 9999 0 13-2
P917 SoftPLC Parameter 8 -9999 to 9999 0 13-2
P918 SoftPLC Parameter 9 -9999 to 9999 0 13-2
P919 SoftPLC Parameter 10 -9999 to 9999 0 13-2
P920 SoftPLC Parameter 11 -9999 to 9999 0 13-2
P921 SoftPLC Parameter 12 -9999 to 9999 0 13-2
P922 SoftPLC Parameter 13 -9999 to 9999 0 13-3
P923 SoftPLC Parameter 14 -9999 to 9999 0 13-3
P924 SoftPLC Parameter 15 -9999 to 9999 0 13-3
P925 SoftPLC Parameter 16 -9999 to 9999 0 13-3
P926 SoftPLC Parameter 17 -9999 to 9999 0 13-3
P927 SoftPLC Parameter 18 -9999 to 9999 0 13-3
P928 SoftPLC Parameter 19 -9999 to 9999 0 13-3
P929 SoftPLC Parameter 20 -9999 to 9999 0 13-3
P930 SoftPLC Parameter 21 -9999 to 9999 0 13-3
P931 SoftPLC Parameter 22 -9999 to 9999 0 13-3
P932 SoftPLC Parameter 23 -9999 to 9999 0 13-3
P933 SoftPLC Parameter 24 -9999 to 9999 0 13-3
P934 SoftPLC Parameter 25 -9999 to 9999 0 13-3
P935 SoftPLC Parameter 26 -9999 to 9999 0 13-3
P936 SoftPLC Parameter 27 -9999 to 9999 0 13-3
P937 SoftPLC Parameter 28 -9999 to 9999 0 13-3
P938 SoftPLC Parameter 29 -9999 to 9999 0 13-3
P939 SoftPLC Parameter 30 -9999 to 9999 0 13-3
P940 SoftPLC Parameter 31 -9999 to 9999 0 13-3
P941 SoftPLC Parameter 32 -9999 to 9999 0 13-3
P942 SoftPLC Parameter 33 -9999 to 9999 0 13-3
P943 SoftPLC Parameter 34 -9999 to 9999 0 13-3
P944 SoftPLC Parameter 35 -9999 to 9999 0 13-3
P945 SoftPLC Parameter 36 -9999 to 9999 0 13-3
P946 SoftPLC Parameter 37 -9999 to 9999 0 13-4
P947 SoftPLC Parameter 38 -9999 to 9999 0 13-4
P948 SoftPLC Parameter 39 -9999 to 9999 0 13-4
P949 SoftPLC Parameter 40 -9999 to 9999 0 13-4
P950 SoftPLC Parameter 41 -9999 to 9999 0 13-4
P951 SoftPLC Parameter 42 -9999 to 9999 0 13-4
P952 SoftPLC Parameter 43 -9999 to 9999 0 13-4
P953 SoftPLC Parameter 44 -9999 to 9999 0 13-4
P954 SoftPLC Parameter 45 -9999 to 9999 0 13-4
P955 SoftPLC Parameter 46 -9999 to 9999 0 13-4
P956 SoftPLC Parameter 47 -9999 to 9999 0 13-4
P957 SoftPLC Parameter 48 -9999 to 9999 0 13-4
P958 SoftPLC Parameter 49 -9999 to 9999 0 13-4
P959 SoftPLC Parameter 50 -9999 to 9999 0 13-4
SoftPLC Parameter Configuration for PID Controller Application (P903 = 1)
Param. Description Adjustable Range Factory Setting Prop. Page
P910 PID Controller Application Version 0.00 to 90.00 ro 13-2
P911 Control Setpoint -99.99 to 99.99 2.00 13-2
P912 Control Setpoint 1 -99.99 to 99.99 2.00 13-2
P913 Control Setpoint 2 -99.99 to 99.99 2.30 13-2
P914 Control Setpoint 3 -99.99 to 99.99 1.80 13-2
P915 Control Setpoint 4 -99.99 to 99.99 1.60 13-2
0-14 | CFW100
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158

Automation Direct CFW100 Owner's manual

Type
Owner's manual
This manual is also suitable for