NOTE:
Before performing electrical connections, ensure that the DC switch is OFF.Since the stored
electrical charge remains in a capacitor long after the DC switch is turned OFF. So it’s
necessary to wait for at least 5 minutes for the capacitor to be electrically discharged.
This topic describes the Sunny Horse Series electrical connections. Read this part carefully
before connecting cables.
4.1 Electrical connection
This topic describes the electrical connection process.
4.2 Connecting PGND Cables
Connect the Sunny Horse Series to the grounding electrode using protection ground (PGND)
cables for grounding purposes.
4.3 Connecting AC Output Power Cables
Connect the Sunny Horse Series to the AC power distribution frame (PDF) or electrical grid
using AC output power cables after obtaining approval from local electrical grid operator.
4.4 Connecting Communication Cables
This topic describes the functions of WIFI and RS485 ports and the method of connecting
WIFI and RS485 communication cables.
4.6 Safety check
Before start the inverter, comply with the safety precautions and check AC、DC connections.
4.5 Connecting DC Input Power Cables
Connect the Sunny Horse Series to PV arrays using DC input power cables.
4
Electrical Connections
Outlines of this chapter
PV modules generate electric energy before exposed to sunlight and can create
an electrical shock hazard. Therefore, before connecting DC input power cable,
cover PV modules using opaque cloth.
Sunny Horse Series has 2 MPP trackers, all PV modules connected to the same
MPPT should have similar rated electrical characteristics (including Isc, Voc, Im,
Vm, Pm and temperature coefficients), have the same number of series
connected PV modules and be all in the same orientation (azimuth and tilt
angle).
Installation and maintenance of inverter, must be operated by professional
electrical engineer.
Attention
Danger
Note
All rights reserved Shenzhen SOFARSOLAR Co ., Ltd.
C
Document Version 2.0(2016.03.29) 23 All rights reserved Shenzhen SOFARSOLAR Co ., Ltd.
C
Document Version 2.0(2016.03.29)
24
User manual User manual
Installation Electrical Connections
Sunny Horse Series(10K~20KTL) Sunny Horse Series(10K~20KTL)
1 2 3
4.1 Electrical connection
Start
4.2 Connecting PGND Cables
Connect the Sunny Horse Series to the grounding electrode using protection ground (PGND)
cables for grounding purposes.
Note:
Good grounding for the Sunny Horse Series can help resist the impact of the surge voltage and improve the
EMI performance. First connect the PGND cable before connecting the AC power cable, DC power cable, and
communication cable.
For the system with one Sunny Horse Series, connect the PGND cable to the ground. For the system with
multiple Sunny Horse Series, connect the PGND cables of all Sunny Horse Series to the grounding electrode
using equipotential bonding.
If the installation location is near the ground, first connect the PGND cable to the ground before installing the
Sunny Horse Series on the wall.
Figure4-1 Shows the flowchart for connecting cables to the Sunny Horse Series
Connect PGND Cables Connect AC Output power
Cables
End Connect DC Input power
Cables
Connect Communication
Cables
The inverter is transformerless, Requires The positive pole and the negativepole
of the PV array are not grounded, Otherwise it will cause inverter failure, In the
PV power generation system, all non current carrying metal parts(such as:
Bracket, Junction box shell, inverter shell) should be connected to earth.
Attention
Figure4-2 Ground terminal composition
1M5 welded stud 2OT Terminal 3M5 Antiskid nut. . .
Sunny Horse Series Grounding Stud