Mircom LT-2013MIR SGM-2200-2 Installation guide

Category
Fire protection
Type
Installation guide
In no event shall Mircom be liable for any direct, indirect or consequential damages,
loss of anticipated profits, loss of time or any other losses incurred by the buyer in
connection with the purchase, installation or operation or failure of this product.
Important!
Mircom recommends that the entire system be completely tested on a regular basis.
However, despite frequent testing and due to but not limited to, criminal tampering or
electrical disruption, it is possible for this product to fail to perform as expected.
INSTALLATION INSTRUCTIONS
SGM-2200-2 NAC Expander for
FX-2200 Fire Alarm Control Panel
The SGM-2200-2 provides two additional NAC output circuits to the FX-2200 panel.
This publication describes the physical installation procedure for the NAC Expander.
Parts List
Qty 1 ... SGM-2200-2 module
Qty 4 ... No. 4 screws
Qty 1 ... Lock washer
Qty 1 ... Ribbon Cable
Qty 2 ... 10K
End-of-Line Resistor
Installing the SGM-2200-2 Module
The SGM-2200-2 module mounts inside the FX-2200 Fire Alarm Control Panel on the
back plate in one of the three expander locations.
1. Position the SGM-2200-2 Module in the upper most empty expander module
location.
2. Secure the module to the back plate using the No. 4 screws and lock washer
(provided). Use the lockwasher on the plated mounting hole (see Figure 1 for
location).
3. Connect an unused Vbell to VB+/VB-. Vbell is TB5 on the Main Board. Connect “+”
to “+” and “-” to “-”. Use 18 AWG twisted pair for wiring. Route wires as shown in
Figure 1.
4. Connect Ribbon Cable to panel or previous expander module.
NOTE: This component must be included in the control panel battery
calculation. Refer to the Battery Calculation Sheet in the FX-2200 Installation
Manual (LT-2000MIR) included with the control panel.
LT- 2013MIR Rev.0
Canada
25 Interchange Way
Vaughan, ON, L4K 5W3
Tel: (888) 660-4655
Fax: (905) 660-4113
www.mircom.com
USA
60 Industrial Parkway PMB 278
Cheektowaga, NY, 14227
Tel: (888) 660-4655
Fax: (888) 660-4113
Dead Front Mounting Plate
DACT BD
OR
CITY BD
NAC BD
OR
RELAY BD
LED DISPLAY
RECTIFIER
XFORMER
BATTERY
BATTERY
(optional)
XFORMER
(optional)
T/B
NAC
Power
VB-
VB+
Exp.
Wiring
NAC
Expansion
MAIN BOARD
Main
Display
Network
Card
BAT+
Service / Printer
Port
Expansion
Module
TB5-6 Pos
Terminal Block
Vbell 3
Vbell 2
Vbell 1
BAT-
Bridge +
Bridge -
DISPLAY HARNESS
DISPLAY BD
NAC BD
OR
RELAY BD
TB1TB2TB3TB4
+-+-+-
SGM-2200-2 NAC EXPANDER
FX-2200 Back Box
Figure 1. SGM-2200-2 NAC Expander Installation
CON1
CON2
Connector for VB+/VB-
Plated Mounting Hole
for Lockwasher
  • Page 1 1
  • Page 2 2

Mircom LT-2013MIR SGM-2200-2 Installation guide

Category
Fire protection
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI