1.0 Introduction
1.1 About this Manual
This installation and operation manual provides information on installing the FA-1000 Series
Fire Alarm Control Panel.
1.2 About the FA-1000
Mircom's FA-1000 Fire Alarm Control Units provide a large capacity of supervised Class A or
B (Style D or B) initiating circuits and supervised Class A or B (Style Z or Y) indicating circuits.
All circuits are supervised for opens and ground faults, and indicating circuits are supervised
for shorts. Optional modules include additional initiating and indicating circuits, relay, and
polarity reversal and city tie. Flush or surface mountable enclosures can be used for retrofits
and on new installations.
1.2.1 Overall Features:
• Basic unit has eight Class B (Style B) initiating circuits that may be configured as four
Class A (Style D) circuits. These are configurable as Alarm, Verified Alarm, Waterflow
Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, or Trouble-Only circuits.
There are two LEDs per circuit: one for trouble (amber), and one for status (red/amber)
• Basic unit has four power limited Class A/B (Style Z/Y) indicating circuits with individual
trouble indicators. Each circuit can be configured as Audible (Silenceable) or Visual
(Non-Silenceable). Audibles may be configured as Steady, Temporal Code, California
Code, or March Time
• Initiating and indicating circuits may be individually disconnected by a DIP switch (slide
switch on "S" Versions for the U.S.A. market only)
• Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, One-
Man Walk Test
For UL installations, disable the Auto Signal Silence timer.
• Subsequent Alarm, Supervisory, and Trouble operation
• Two outputs for four-wire resettable smoke power supply (200 mA each max., 300 mA
total max.)
• Auxiliary relay contacts for Common Alarm and Common Supervisory (disconnectable),
and a Common Trouble relay
• RS-485 interface for RA-1000 Series Remote Multiplex Annunciators
• Optional modules for additional initiating, indicating, and relay circuits, and city tie and
polarity reversal signalling
• Easy configuration via pushbuttons and switches
• Extensive transient protection
• Surface mountable enclosures, flush trims available
1.2.2 Controls and Indicators
Eight pushbuttons, 16 common indicators, provision for up to 24 points (expansion chassis
adds provision for up to another 48 points).