Danfoss Termix AT BTD Operating instructions

Type
Operating instructions
Operatingguide
TermixATBTD
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.2Start-up..............................................................5
5.0MountinginstructionsTermixATBTDwall
cabinet............................................................6
5.1Mounting...........................................................6
6.0Design.............................................................8
6.1DesignTermixATBTD5pipes...................................8
6.2SchematicdiagramTermixATBTD5Pipes....................9
6.3DesignTermixATBTD4pipes...................................10
6.4SchematicdiagramTermixATBTD4Pipes....................11
7.0Controls..........................................................12
7.1DHWtemperaturecontrol........................................12
7.2Other.................................................................13
7.3Maintenance........................................................14
8.0Troubleshooting..............................................15
8.1Troubleshootingingeneral......................................15
8.2TroubleshootingDHW............................................15
8.3Disposal.............................................................16
9.0Declaration......................................................19
9.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
1
OperatingguideTermixATBTD
2.0Functionaldescription
Districtheatingsubstationwithtankfordomestichotwater
preparationandwiththermostaticcontrol.Designedfor
wall-mounting.
Application
TheTermixATBTDsubstationisacompletesolutionforhot
water.TheTermixATBTDisapplicableforsingle-familyhouses
orapartments.
Domestichotwater(DHW)
Thedomestichotwatercircuitconsistsofahotwatertankwithcoil
andself-actingthermostaticcontrolvalve.Thehotwatertankand
coilareenamelledandthetankcontainsamagnesiumanode.The
substationisdeliveredwithabuiltinsafetyvalve.
2
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
3
OperatingguideTermixATBTD
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connectionsizes:
Allconnections:
G¾”(int.thread)
Dimensions(mm):
Withcover:
100L:H1180xW540xD520
150L:H1510xW540xD520
Weight(approx.):85100kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
TermixATBTD5pipes
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
TermixATBTD4pipes
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
4.2Start-up
Start-up,Directheating
Theshut-offvalvesshouldbeopenedandtheunitobservedas
itentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
5
OperatingguideTermixATBTD
5.0MountinginstructionsTermixATBTDwallcabinet
5.1Mounting
Wallbracket
MounttheWallbracketaccordingtotheDrawing.
UseAtocenterthetankonthebracket.
B-AllpipethreadsareISO½” .
Mountthecontainerunitinthewallbracket.
6
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
Sideplates
Fastentherightandleftsideplatesbyplacingthekeyholesover
thescrewsonthesidesofthewallbracket.
1Bottompanel
Slidetheslotsinthebottompanelontothe2bushesintheside
plates,andfastenthepanelwiththe2screwsinthefront.
2Topplate
Mountthetopplate.
3Frontcover
Mountthefrontcoverbyloweringthekeyholesontothescrews
inthesideplates.
4Clockpanel
Mounttheclockpanelbyloweringthekeyholesontothescrews
inthesideplates.
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
7
OperatingguideTermixATBTD
6.0Design
6.1DesignTermixATBTD5pipes
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
E
Hotwatertankwithcoil
4
Safetyvalve
S
Siphon
20
Filling/drainvalve
1A
Ballvalve,DVGW
41A
Fittingpiece,coldwatermains
2
Singlecheckvalve
59
Differentialpressure/temperatureregulatorwithowlimiting
8
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
6.2SchematicdiagramTermixATBTD5Pipes
DHW
DCW
CWM
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
E
Hotwatertankwithcoil
4
Safetyvalve
1
Ballvalve
20
Filling/drainvalve
1A
Ballvalve,DVGW
41A
Fittingpiece,coldwatermains
2
Singlecheckvalve
59
Differentialpressure/temperatureregulatorwithowlimiting
DHW:DomesticHotWater
DCW:
DomesticColdWater
CWM:
Coldwatermains
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
9
OperatingguideTermixATBTD
6.3DesignTermixATBTD4pipes
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
E
Hotwatertankwithcoil
4
Safetyvalve
S
Siphon
20
Filling/drainvalve
1A
Ballvalve,DVGW
59
Differentialpressure/temperatureregulatorwithowlimiting
2
Singlecheckvalve
10
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
6.4SchematicdiagramTermixATBTD4Pipes
DHW
DCW
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
E
Hotwatertankwithcoil
4
Safetyvalve
1
Ballvalve
20
Filling/drainvalve
1A
Ballvalve,DVGW
59
Differentialpressure/temperatureregulatorwithowlimiting
2
Singlecheckvalve
DHW:DomesticHotWater
DCW:
DomesticColdWater
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
6.4.1Technicalparameters
Technicalparameters
Nominalpressure:
PN10
Max.DHsupplytemperature:
T–max=95°C
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
11
OperatingguideTermixATBTD
7.0Controls
7.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
7.1.1AB-QMcontroller(45–60°)
QTisaself-actingthermostaticactuatordesignedtobeused
asreturntemperaturecontrolthermostatinone-pipeheating
systems.
QTisdedicatedtobeusedwithAB-QMautomaticbalancing&
controlvalve.
AB-QMDN10-20(45-60°C)
QTSensorsetting(turns)
Temperaturesetting
01
2
34
5
6
20%
48,050,553,0
55,5
58,060,563,0
30%
47,049,552,0
54,5
57,059,562,0
40%
46,048,551,053,556,058,561,0
50%
45,0
47,5
50,052,555,0
57,5
60,0
60%
44,046,549,0
51,5
54,056,559,0
70%
43,0
45,5
48,050,553,0
55,5
58,0
80%
42,0
44,5
47,049,552,0
54,5
57,0
90%
41,043,546,048,551,053,556,0
AB-QM(ow
setting)
100%
40,042,545,0
47,5
50,052,555,0
Thevaluesareintendedasaguide.
12
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
7.2Other
7.2.1Coldwatermeterttingpiece
Thesubstationisequippedwithattingpieceforcoldwatermeter.
Assemblyofcoldwatermeter:
1:Closeballvalves
Closetheballvalvesoncoldwater,ifthereiswateronthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththecoldwatermeter.
Donotforgetthegaskets.
4:Tightenconnections
Aftermountingofthecoldwatermeterremembertocheckand
tightenallthreadedconnections.
7.2.2Siphon
PlacedtheSiphondirectlyundertheSafetyvalve.
Ensurethatthedrainpipehasaminimuminternaldiameterof
32mm.
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
13
OperatingguideTermixATBTD
7.3Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
14
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
8.0Troubleshooting
8.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
8.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
15
OperatingguideTermixATBTD
8.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
16
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
17
OperatingguideTermixATBTD
18
DEN-GT
VI.JV.Y3.02/LUK40692
DanfossDistrictEnergy
OperatingguideTermixATBTD
9.0Declaration
9.1Declarationofconformity
Category0withoutelectricalequipment
DanfossDistrictEnergy
VI.JV.Y3.02/LUK40692
DEN-GT
19
OperatingguideTermixATBTD
ProducedbyDanfossA/S©10/2017
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20