Danfoss Termix Solar A+/B+ Operating instructions

Type
Operating instructions
OperatingGuide
TermixSolarA+/B+/S+
1.0TableofContents
1.0TableofContents.............................................1
........................................................................2
2.0Functionaldescription......................................3
3.0Safetynotes.....................................................4
3.1SafetyNotesgeneral............................................4
4.0Mounting........................................................5
4.1Mounting...........................................................5
4.2Electricalconnections.............................................7
5.0Design.............................................................8
5.1Design...............................................................8
5.2Schematicdiagram................................................9
5.3Design...............................................................10
5.4Schematicdiagram................................................11
6.0Controls..........................................................12
6.1DHWtemperaturecontrol........................................12
6.2Maintenance........................................................14
7.0Troubleshooting..............................................15
7.1Troubleshootingingeneral......................................15
7.2TroubleshootingDHW............................................15
7.3Disposal.............................................................16
8.0Declaration......................................................19
8.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
1
OperatingGuideTermixSolarA+/B+/S+
2
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
2.0Functionaldescription
Domestichotwatermodulewithheatexchangerand
thermostaticcontrol.Designedforwall-mounting.
Application
TheTermixSolarA+/B+/S+isaninstantaneouswaterheater,
featuringsuperbheatextractionandhighperformance.The
TermixSolarA+/B+/S+isapplicableforheatingsystemswithbuffer
accumulators,solarsystemsorforotherheatsources,whereavery
lowreturntemperatureispreferred.Thelargeheatexchanger
coolsoutthewaterintheprimaryreturnlineveryefciently,
therebycreatingaverygoodoperationeconomy.Aowswitchin
thedomestichotwaterpipeiscontrollingtheprimaryheating
pump.Anoptionalcirculationpumptogetherwithathermostat
canmaintainthecirculatingtemperatureatadesiredtemperature.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerandthe
temperatureisregulatedwithathermostaticcontrolvalve.There
isnoadditionalpressurelossonthesecondarysideoftheDHW
heatexchangerwithathermostaticcontrol.Thereforethistypeof
regulationcanbeusedbylowpressureinthecoldwatermains.
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
3
OperatingGuideTermixSolarA+/B+/S+
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
4
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.BufferTank(BT)supply
2.Domestichotwater(DHW)
3.BufferTank(BT)return
4.Domesticcoldwater(DCW)
5.Hotwatercirculation(HWC)-(Optional)
Connectionsizes:
BT:
G¾”(int.thread)
DCW+DHW+HWC:
G¾”(int.thread)
Dimensions(mm):
Withoutcirculationandcover:
H655xW440xD138
Withoutcirculationandwithcover:
H715xW450xD150
Withcirculationandwithoutcover:
H940xW440xD138
Withcirculationandcover:
H940xW450xD150
Weight(approx.):
BrazedHEX(A+/S+):
14kg
GasketedHEX(B+):
17kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
5
OperatingGuideTermixSolarA+/B+/S+
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
6
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
4.2Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Potentialbonding
Potentialbondingshouldbecarriedoutaccording
to60364-4-41:2007andIEC60364-5-54:2011.
Bondingpointonthemountingplatebelowrightcornermarked
withearthsymbol.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Outdoortemperaturesensor
Outdoorsensorsshouldbemountedsoastoavoidexposureto
directsunlight.Theyshouldnotbeplacedclosetodoors,windows
orventilationoutlets.
Theoutdoorsensormustbeconnectedtothestationonthe
terminalblockundertheelectroniccontrol.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
7
OperatingGuideTermixSolarA+/B+/S+
5.0Design
5.1Design
5.1.1DesignTermixSolarA+/B+/S+
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
13
Chargingpump
M
Electricalwiringbox
21
Tobeorderedseparately
7
Thermostaticcontroller,DHW
35
Ballvalve/non-returnvalve
45
Flowswitch
8
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
5.2Schematicdiagram
5.2.1SchematicdiagramTermixSolarA+/B+/S+
BT
Supply
DHW
BT
Return
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescriptionwithoutcirculation
B
Heatexchanger,DHW
1A
Ballvalve,DVGW
21
Tobeorderedseparately
M
Electricalwiringbox
7
Thermostaticvalve
35
Ballvalve/non-returnvalve
1
Ballvalve
13
Chargingpump
45
Flowswitch
DHW:DomesticHotWater
DCW:
DomesticColdWater
BTSupply:
Buffertanksupply
BTReturn:
Buffertankreturn
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
9
OperatingGuideTermixSolarA+/B+/S+
5.3Design
5.3.1DesignTermixSolarA+/B+/S+withcirculation
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
7
Thermostaticcontroller,DHW
21
Tobeorderedseparately
M
Electricalwiringbox
11A
DHWpump,withbuiltincheckvalve
35
Ballvalve/non-returnvalve
2
Singlecheckvalve
13
Chargingpump
45
Flowswitch
4
Safetyvalve
10
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
5.4Schematicdiagram
5.4.1SchematicdiagramTermixSolarA+/B+/S+withcirculation
DHW
BT
Supply
DCW
BT
Return
HWC
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescriptionwithcirculation
B
Heatexchanger,DHW
2
Singlecheckvalve
13
Chargingpump
M
Electricalwiringbox
4
Safetyvalve
21
Tobeorderedseparately
1
Ballvalve
7
Thermostaticvalve
35
Ballvalve/non-returnvalve
1A
Ballvalve,DVGW
11A
DHWpump,withbuiltincheckvalve
45
Flowswitch
DHW:DomesticHotWater
DCW:
DomesticColdWater
HWC:
HotWaterCirculation
BTSupply:
Buffertanksupply
BTReturn:
Buffertankreturn
5.4.2Technicalparameters
Technicalparameters
Nominalpressure:
PN10
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
BrazedHEX(A+):
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
GasketedHEX(B+):
Gasketmaterial(HEX):
EPDMper.
Heatexchangerstestpressure:13bar
BrazedHEX(S+):
Brazingmaterial(HEX):Stainlesssteel
Heatexchangerstestpressure:24bar
Soundlevel:55dB
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
11
OperatingGuideTermixSolarA+/B+/S+
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.1.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows:
1=20°C
2=35°C
3=50°C
4=60°C
5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto
90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
6.1.2CirculatorpumpUPM3
UPM3Pumpscanbecontrolledinconstantpressure,proportional
pressureorconstantspeedmodedenedbythemeansofasmart
userinterface.
Thevariablespeedmodulatingmodesallowthepumptomatchits
performancetothesystemrequirements,helpingtoreducenoise
whenthermostaticvalvesareclosingdown.
EnergylabellingclassA
12
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
6.1.3GrundfosUPM3AUTOLinstructions
Controlmode
Youcanswitchfromtheperformanceviewtothesettingsviewbypressingthepushbutton.Thesettingsviewshowswhichmode
controlsthecirculator.After2seconds,thedisplayswitchesbacktoperformanceview.
Ifyoupressthebuttonfor2to10seconds,theuserinterfaceswitchesto"settingselection"iftheuserinterfaceisunlocked.Youcan
changethesettingsastheyappear.Theselectionofthecontrolmodedependsonthesystemtypeandtheallocationofpressurelosses.
Ifyoupressthekeylockformorethan10seconds,youcantogglebetweenenabling/disablingthekeylockfunction.
Function
Recommendedfor
Green
YellowYellowYellowYellow
Proportionalpressure1
1-pipesystems
µµ
Proportionalpressure2
µµµ
Proportionalpressure3
2-pipesystems
µµµµ
Constantpressure1
Underoorheating
µµ
Constantpressure2
µµµ
Constantpressure3
µµµµ
ConstantCurve1
µµµ
ConstantCurve2
µµµµ
ConstantCurve3
µµµµµ
ConstantCurveMax.
µµµµ
Operationstatus
Function
Recommendedfor
Green
YellowYellowYellowYellow
Standby**OnlyPWMcontrolled
µ
0%P125%
µµ
25%P150%
µµµ
50%P175%
µµµµ
75%P1100%
µµµµµ
Alarmstatus
Function
Recommendedfor
RedYellowYellowYellowYellow
Blocked
µµ
Supplyvoltagelow
µµ
Electricalerror
µµ
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
13
OperatingGuideTermixSolarA+/B+/S+
6.1.4Domestichotwaterpump
Thedomestichotwaterpumpcanbeprogrammedwiththe
desiredtimeprogramme.
6.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
14
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
15
OperatingGuideTermixSolarA+/B+/S+
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
16
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
17
OperatingGuideTermixSolarA+/B+/S+
18
DEN-GT
VI.JV.I3.02/LUK38016
DanfossDistrictEnergy
OperatingGuideTermixSolarA+/B+/S+
8.0Declaration
8.1Declarationofconformity
Category0withelectricalequipment
DanfossDistrictEnergy
VI.JV.I3.02/LUK38016
DEN-GT
19
OperatingGuideTermixSolarA+/B+/S+
ProducedbyDanfossA/S©10/2017
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Danfoss Termix Solar A+/B+ Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI