eta PelletsUnit User manual

Type
User manual
2016-11-29
EN
0000000278
V.002
3.38.1
1510
93046-002
PelletsUnit
7 - 15 kW
Service manual
ETA Heiztechnik
Gewerbepark 1
A-4716 Hofkirchen an der Trattnach
Tel: +43 (0) 7734 / 22 88 -0
Fax: +43 (0) 7734 / 22 88 -22
www.eta.co.at
General information
3
1 General information
Support for cleaning and maintenance
This document helps support you with the cleaning
and maintenance of the boiler. The required steps are
listed in detail here.
Take note of the date of the cleaning or maintenance
and any faults that may have occurred. This facilitates
troubleshooting for the expert (system operator,
heating technician...).
For services (such as commissioning, mainte-
nance, fault fixing provided by ETA customer
service), the service reports are provided in digital
form. For clarity, you should staple these reports to this
document or enclose them.
Commissioning data
Enter the boiler number (printed on the type plate), the
date of commissioning as well as the heating
technician who commissioned the system.
Copyright
All contents of this document are property of ETA
Heiztechnik GmbH and are protected by copyright.
Any reproduction, transfer to third parties or use for
other purposes is prohibited without written permission
from the owner.
Subject to technical changes
We reserve the right to make technical modifications
without notice. Printing and typesetting errors or
changes of any kind made in the interim are not cause
for claims. Individual configurations depicted or
described here are only available optionally. In the
event of contradictions between individual documents
regarding delivery scope, the information in our current
price list applies.
Explanation of symbols
Instructions and information
Layout of safety instructions
SIGNAL WORD!
Type and source of danger
Possible effects
Measures for avoiding the danger
Types of safety instruction
CAUTION!
On non-compliance with this safety instruction, there is
a risk of material damage.
WARNING!
On non-compliance with this safety instruction, there is
a risk of physical injury.
DANGER!
On non-compliance with this safety instruction, there is
a risk of major physical injury.
Commissioning data
Boiler number:
________________________________________
Commissioned on:
_________________________________________
Commissioned by (company):
_________________________________________
_________________________________________
_________________________________________
4 www.eta.co.at
Maintenance notes Cleaning and maintenance
2 Cleaning and maintenance
2.1 Maintenance notes
Performing regular cleaning and maintenance
To ensure satisfactory functioning, cleaning and
maintenance must be performed at regular intervals.
Carry out this work within the intervals stated here.
All tasks where the maintenance table reads
"Customer" or "Customer or expert" in the column
"To be carried out by" can be carried out by any trained
adult. Instructions can be provided by the heating
technician or our customer service.
Steps that are marked with "Expert" only can only be
carried out by the heating technician or our customer
service.
Operation only by trained personnel
The product may be operated by trained adults only.
Training may be provided by the heating technician or
our customer service. Please read the associated doc-
umentation carefully in order to avoid errors during
operation and maintenance.
Persons who lack experience and knowledge as well
as children may not operate, clean, or maintain the
product.
Display maintenance steps on the screen
With this boiler, the maintenance steps can also be
displayed on the ETAtouch control system screen. The
required activities will be explained to you step-by-step
and supplemented with detailed graphics. Each
maintenance is saved and the details can be viewed at
any time. So you can maintain a long-term overview of
the maintenance carried out. Of course, the
maintenance can also be carried out using the service
guide, without the support of the ETAtouch control
system.
To access maintenance, switch to settings in the boiler
function block ( [Settings] button) and then select
the function [Maintenance].
Fig. 2-1: Overview (example)
You can also access this overview by pressing
the maintenance switch. Also when the message
appears that maintenance of the boiler is required.
In the overview the different maintenance intervals are
listed in the upper area. This includes the maintenance
already carried out. With the button, information
about the selected maintenance is displayed.
Maintenance that you can carry out as an end
customer is labelled with the symbol. All others are
reserved for specialists and require authorisation.
Press the button to start the maintenance. The
individual steps are displayed on the screen. You can
switch to the next or the previous screen respectively
with the arrow keys on the left and right side of the
screen.
Fig. 2-2: Maintenance step (example)
Cleaning and maintenance Maintenance notes
5
Follow the on-screen instructions and carry out all
steps carefully. Enter your name at the end of
maintenance ( button) and save the maintenance
with the button.
Fig. 2-3: End of maintenance
To end maintenance prematurely, press the right
arrow key several times until you get to the end.
There you can end the maintenance with the
button. Cancellation during a maintenance step is not
possible.
Explanation of the maintenance switch
The maintenance switch on the boiler is needed for
performing maintenance with the aid of the [Main-
tenance] function in the ETAtouch control system. This
displays the individual maintenance steps on the boiler
screen.
With this variant the heating mode is stopped, but
the boiler remains on at the mains switch. So that
all drives are disconnected, the safety chain of the
boiler is disrupted with the maintenance switch. The
screen will display a message when it is time to actuate
the maintenance switch.
Fig. 2-4: Maintenance switch
The maintenance switch is marked with the
symbol and has two settings.
"1" = regular operation
This is the standard position of the maintenance
switch. The boiler can execute heating mode in this
position.
"0" = maintenance mode
In this position, all drives are disconnected to
perform maintenance. The circuit boards,
however, are still live.
Explanation of pictograms
Switch the boiler on/off with the mains switch.
Perform a visual check of the components.
Clean the components, for example, with a
soft cloth.
Remove deposits with a vacuum or an ash
vacuum.
Remove deposits with the poker.
Remove deposits with the cleaning brush.
Replace the wear parts (e.g. seals) on the
components.
Lubricate the components. The lubricant to
use is listed in the respective step.
Install the components with some force (for
example the retaining tube or the Lambda
probe).
Handle the components carefully, since they
break very easily.
Clean panels
If necessary, clean the panels of the boiler and the
ETAtouch screen with a moist cloth.
Under no circumstances use aggressive
solvents, chemicals or scouring agents. They can
lead to stress cracks and damage.
6 www.eta.co.at
Maintenance notes Cleaning and maintenance
Checking the boiler counters
The counters can be seen in the boiler's text menu.
Counter [Consump. since maint.] is used for the
service intervals. If it has reached one of the listed
intervals, maintenance is required. This counter is in:
Counters
Consump. since maint.
Cleaning and maintenance Maintenance notes
7
8 www.eta.co.at
Maintenance openings in the boiler Cleaning and maintenance
2.2 Maintenance openings in the
boiler
Maintenance openings and components
1 Heat exchanger cover
2 Vacuum turbine for pellet transport
3 Firebed switch
4 Stoker drive chain
5 Water pressure sensor
6Ignition
7 Position switch for ash box
Cleaning and maintenance Maintenance openings in the boiler
9
1 Fill level sensor for pellet hopper
2 Safety valve
3 Flue gas temperature sensor
4 Draught fan
5 De-ashing drive chain
6 Filling and draining valve
7 Underpressure sensor
10 www.eta.co.at
Maintenance table Cleaning and maintenance
2.3 Maintenance table
Tasks
Regularl
y
Every
3,000 kg
pellets
or
1 year
Every
5000 kg
pellets
or
3 years
to be
performed by
Empty the ash box
Empty the ash box
Check the seals
X X X Customer
Check the pressure of the heating system X X X Customer
Visual check of the safety valves X X
Customer or
specialist
Chimney
Clean the flue tube
Flush the chimney's condensate drain
X X
Customer or
specialist
Clean combustion chamber
Clean the inner walls of the combustion chamber
Clean the ignition tube
Checking the movability of the firebed switch
Clean the lambda probe
X X
Customer or
specialist
Clean the draught fan X Specialist
Clean the temperature sensor X Specialist
Check the combustion chamber and heat exchanger
Check the firebed button and firebed switch
Check heat exchanger tubes
Check the seal on heat exchanger cover
Dismantle the ignition and clean the ignition tube
X Specialist
Check the pellet hopper
Cleaning the fill level sensor
Clean the strainer
X Specialist
Check the stoker unit
Checking the stoker drive chain
X Specialist
Check de-ashing
Check the de-ashing drive chain
X Specialist
Check the underpressure sensor
Clean the silicon hoses
Calibrate the underpressure sensor
X Specialist
Check the ash box position switch X Specialist
Calibrate the lambda probe X Specialist
Reset the maintenance counter X Specialist
Perform heating test X Specialist
Cleaning and maintenance Regularly
11
2.4 Regularly
2.4.1 Preparation
Stop heating
End the boiler's heating mode with the On/Off switch
in the boiler overview window. The boiler
performs an ember burnout and then changes to
[Switched off] mode. Press the [De-ash] button to
make the boiler perform a final de-ashing.
2.4.2 Empty the ash box
Empty the ash box and inspect the seals
Open the boiler door and fold the locking lever
forwards. Remove the ash box from the boiler.
Fig. 2-5: Locking lever
Take off the cover of the ash box by loosening the two
fasteners and empty the ash box.
Fig. 2-6: Lid
Check the ash for embers. Never put hot ash into
the waste bin!
Inspect the seal on the ash box lid for integrity, and
replace it if necessary.
Fig. 2-7: Seal
Inspect the integrity of the ash box seals on the boiler,
replace them if necessary.
Fig. 2-8: Seals
Attaching the ash box to the boiler
Reattach the cover of the ash box and secure with the
fasteners. Push the ash box over the connection on
the boiler and attach it to the boiler with the locking
lever.
Fig. 2-9: Locking lever
12 www.eta.co.at
Regularly Cleaning and maintenance
2.4.3 Check pressure of the heating
system
Checking the heating system water pressure
In buildings with up to three storeys, the optimum
water pressure in a cold heating system is between 1
and 2 bar. For a warm heating system, the optimum
water pressure is between 1.5 and 2.5 bar.
Fig. 2-10: Pressure gauge
The control system displays a warning on the
screen as soon as the boiler pressure drops
below 1.2 bar. If the boiler pressure falls below 0.8 bar
or rises above 2.8 bar, the control system automatical-
ly switches the boiler off.
You can adjust the pressure in the heating system on
the filling and draining connection of the boiler.
Fig. 2-11: Filling and draining connection
If the water pressure is too low, fill the cold
heating system to approx. 2 bar. Do not fill to a
higher pressure, as water expands with increasing
temperature and the water pressure also rises when
the boiler is in heating mode. The safety valve triggers
at approx. 2.8 bar.
If the water pressure drops several times a year,
contact a heating professional. When refilling
water in the heating system, the same water as used
during initial filling should be used whenever possible
(e.g. prepared water).
2.4.4 Establish operational readiness
Switching on the boiler
Switch the boiler back on with the On/Off
switch.
Cleaning and maintenance 3,000 kg / annually
13
2.5 3,000 kg / annually
2.5.1 Preparation
Stop heating
End the boiler's heating mode with the On/Off switch
in the boiler overview window. The boiler
performs an ember burnout and then changes to
[Switched off] mode. Press the [De-ash] button to
make the boiler perform a final de-ashing.
Switch off boiler via mains switch
WARNING!
Switch off the electricity to the boiler via the mains
switch. This prevents injuries caused by switching
the boiler on inadvertently.
WARNING!
Burns caused by hot parts
Risk of burning on parts located behind the
boiler housing, even after shutting the
boiler down.
Allow the boiler to cool down sufficiently
before starting any activities.
2.5.2 Check safety devices
Checking the safety valves
Perform a visual check of all safety valves of the
heating system. The outlets of the safety valves may
not drip.
Fig. 2-12: Safety valve
If the safety valve drips, open it with a quarter turn of
the red cap and rinse it out (danger of scalding). If the
safety valve still cannot be sealed effectively after
being rinsed several times, it must be cleaned or
replaced by an installer (heating technician).
A manual check of the safety valve is carried out
with a 1/4 turn of the red cap. This rinses the
safety valve. However it is very likely that the seal will
be damaged in the process and thus the outlet will drip.
That is why you should only perform this check on
weekdays and never on weekends in cold winter, as no
heating technician may be available if the seal is
defective.
14 www.eta.co.at
3,000 kg / annually Cleaning and maintenance
2.5.3 Chimney
Cleaning the flue tube
Sweep the flue tube from the flue outlet to the chimney
and remove flue ash from the chimney using a vacuum
cleaner.
Sweep the ash into the chimney, not into the
boiler. Otherwise, ash will collect in the
fan housing and can block the draught fan.
Fig. 2-13: Flue tube
Rinse the chimney's condensate drain
Check the chimney's condensate drain to make sure it
is free, as ash can block the outlet. To check, rinse the
outlet with some water.
Fig. 2-14: Condensate drain
2.5.4 Cleaning the combustion chamber
Removing the panel on the top
Remove the panel on the top of the boiler.
Fig. 2-15: Panel
Remove heat exchanger cover
Remove the insulation over the heat exchanger cover.
Fig. 2-16: Insulation
Cleaning and maintenance 3,000 kg / annually
15
Remove the heat exchanger cover by loosening the
two wing nuts.
Fig. 2-17: Heat exchanger cover
Removing the combustion chamber cover
Using the poker, remove the combustion chamber
cover from the combustion chamber.
Fig. 2-18: Combustion chamber cover
Cleaning the inner walls of the combustion
chamber
Wipe the ash off the inner walls of the combustion
chamber and push it onto the grate or into the heat
exchanger tubes. Use a vacuum cleaner to remove
flue ash from the upper part of the heat exchanger
tubes.
Fig. 2-19: Cleaning the inner walls
Cleaning the ignition tube
Check the ignition tube for combustion residues and
clean it by vacuuming.
Fig. 2-20: Ignition tube
16 www.eta.co.at
3,000 kg / annually Cleaning and maintenance
Checking the movability of the firebed switch
Check the mobility of the firebed button in the
combustion chamber by repeated lifting.
Fig. 2-21: Firebed button
Replacing the combustion chamber cover
Clean the combustion chamber cover and re-insert it in
the combustion chamber.
Fig. 2-22: Combustion chamber cover
Cleaning the lambda probe
Vacuum out the head of the lambda probe using a
vacuum cleaner. Do not dismantle the lambda probe.
Fig. 2-23: Head of the lambda probe
Check heat exchanger tubes
Inspect the heat exchanger tubes for tar deposits.
Fig. 2-24: Heat exchanger tubes
If there are tar deposits in the heat exchanger
tubes, contact customer service immediately. Tar
deposits can have several causes, for example:
Air leaks through the heat exchanger cover or the
lambda probe
insufficient boiler runtime (start-stop operation)
too little heat consumption due to incorrect control
system settings
Usage for an
individual room temperature control but without
buffer storage tank in heating system
an incorrectly calibrated lambda probe
an incorrect differential pressure measurement
Cleaning and maintenance 3,000 kg / annually
17
Checking the seal on the heat exchanger cover
Clean the heat exchanger cover. Inspect the integrity
of the seal on the heat exchanger cover and replace if
necessary.
Fig. 2-25: Heat exchanger cover
CAUTION!
Avoid operation with damaged seals
Never operate the boiler with damaged seals.
Otherwise, leak air is sucked in, disturbing the
combustion process and causing increased wear.
Always replace seals as soon as they are
damaged.
Close heat exchanger cover
Fit the heat exchanger cover evenly using the two wing
nuts.
Fig. 2-26: Heat exchanger cover
Then replace the insulation.
Fig. 2-27: Insulation
Mounting the top panel
Remount the panel on the top of the boiler again.
Fig. 2-28: Panel
18 www.eta.co.at
3,000 kg / annually Cleaning and maintenance
2.5.5 Establish operational readiness
Switch the boiler on via the mains switch and start
de-ashing.
Establish the boiler's power supply at the mains switch.
Press the [De-ash] button to de-ash the boiler.
Switch the boiler back on with the On/Off
switch.
Cleaning and maintenance 5,000 kg / 3 years
19
2.6 5,000 kg / 3 years
2.6.1 Preparation
Before this maintenance, perform all steps for the
preceding maintenance intervals
Before this maintenance, all steps for the
preceding maintenance intervals must be
performed.
WARNING!
The following activities may only be performed by
qualified specialist personnel.
If you carry out these activities without the correspond-
ing specialist training, and above all without the
required experience, safe operation is no longer
guaranteed. The resulting defects and consequential
damage are excluded from the guarantee and
warranty.
Equally an incorrect performance of these activities
can lead to serious injuries.
Stop heating
End the boiler's heating mode with the On/Off switch
in the boiler overview window. The boiler
performs an ember burnout and then changes to
[Switched off] mode. Press the [De-ash] button to
make the boiler perform a final de-ashing.
Switch off boiler via mains switch
WARNING!
Switch off the electricity to the boiler via the mains
switch. This prevents injuries caused by switching
the boiler on inadvertently.
WARNING!
Burns caused by hot parts
Risk of burning on parts located behind the
boiler housing, even after shutting the
boiler down.
Allow the boiler to cool down sufficiently
before starting any activities.
2.6.2 Removing panels
Removing the panel on the top
Remove the panel on the top of the boiler.
Fig. 2-29: Panel
Removing the side panel
Remove the protective screen for the boiler's supply
air.
Fig. 2-30: Protective screen
20 www.eta.co.at
5,000 kg / 3 years Cleaning and maintenance
Remove the side panel.
Fig. 2-31: Side panel
Removing the panel from the front
Unscrew the screws on the panel, lift and remove it.
Fig. 2-32: Panel
2.6.3 Clean draught fan
Cleaning the draught fan
Take the draught fan off the boiler by loosening the
screws.
Fig. 2-33: Draught fan
Remove the ash from the fan housing on the boiler.
Fig. 2-34: Clean the fan housing
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60

eta PelletsUnit User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI