IMPORTANT
READ CAREFULLY BEFORE INSTALLING FIXTURE. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
RAB xtures must be wired in accordance with the National Electrical Code and all applicable local codes. Proper
grounding is required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE
INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT
AND THE HAZARDS INVOLVED.
WARNING: Make certain power is OFF and batteries are DISCONNECTED before installing or maintaining xture.
No user serviceable parts inside.
Thank you for buying RAB lighting xtures. Our goal is to design the best quality products to get the job done right. We’d like to hear your comments. Call
the Marketing Department at 888-RAB-1000, or email: marketing@rabweb.com
MOUNTING
CAUTION: Suitable for Wet Locations as Downlight
and Wall Mount only.
1. Loosen and remove (4) Screws and separate Back
Box from Emergency Housing. Use provided tether.
2. Drill necessary holes on Back Box. Measurements
of drill positions are shown below.
3. Match the hole pattern and place the Gasket on the
Back Box.
4. Secure the Back Box on the surface with hardware
appropriate for the mounting surface.
5. Wire the xture to the incoming supply wires
according to NEC and local codes. Use UL listed
wire connectors.
6. For WPLED26/E, each battery unit has one
connector. For WPLED26/EC, each battery unit has
two connectors as shown below. For details refer to
the appropriate Wiring Diagram section and supplied
Instruction Sheet.
7. Connect the battery connectors. DO NOT connect
the Batteries before wiring the xture to the supply.
8. Secure Housing to Back Box. Check Housing
Gasket seal all around.
9. Apply sealant to all unused conduit entry points.
To ensure weatherproof seal, apply weatherproof
silicone sealant around the edge where the xture
meets the wall.
Housing
Screws
Bracket Screw
Two connectors for
WPLED26/EC
Back Box Housing
Gasket
WPLED26/E
Battery
Connector
Gasket
Screws
Bracket
Emergency
Batteries
WPLED26 EMERGENCY INSTALLATION SHEET
CLEANING & MAINTENANCE
CAUTION: Be sure xture temperature is cool
enough to touch. Do not clean or maintain while
xture is energized.
1. Clean glass lens & xture with non-abrasive glass
cleaning solution.
2. Do not open xture to clean the LED. Do not touch
the LED.
US: Pat. D634,873; CN: ZL 201030129137.X; MX: 32491;
TW: D139540; CA: D RAB Lighting Inc. Patent Pending.
Note: These instructions do not cover all details or variations
in equipment nor do they provide for every possible situation
during installation, operation or maintenance.
WPLED26 (2X13)
EMERGENCY 120V OR
277V
WIRING DIAGRAM
2.22.12
LED 26W EMERGENCY
120V OR 277V WIRING DLC
KS
AC DRIVER
COM
GROUND
BODINE
BSL722 LED
EMERGENCY
DRIVER
BATTERY 1
LEAVE OPEN
DO NOT CONNECT
DURING
MANUFACTURING
CUSTOMER SHOULD
CONNECT ONLY AFTER
FINISHING WIRING TO AC
POWER. BATTERY COULD
HAVE CHARGE & SHOCK
RED-WHITE STRIPE
RED
FUSE
HOLDER
CHARGING
INDICATOR LIGHT /
TEST SWITCH
BLUE
WHITE
YELLOW
YELLOW - BLACK STRIPE
WPLED26
SWITCHED HOT
CHARGING
INDICATOR/
TEST
SWITCH
BLACK
WHITE
WHITE/BLACK
VIOLET
BROWN
RED-WHITE STRIPE
BLUE
BLACK
BLACKGREY
GREY
WHITE
WHITE
WHITE
WHITE
WHITE - RED STRIPE
WHITE
BLACK
WHITE
BLACK
BLACK
BLACK
BLACK
UNSWITCHED HOT
RAB LABEL - ADD
RAB LABEL - ADD
LABEL PROVIDED
BATTERY 2
EMERGENCY
HOUSING
RED
RED
RED
RED
RED
RED
BLACK
WPLED26/E WIRING DIAGRAM (Refer to next page for WPLED26/EC wiring diagram)
2.940
[74,68]
7.500
[190,5]
.600
[15,24]
3.750
[95,25]
DRILL TEMPLATE
7.5”
3.75”
0.6”
2.94”
WPLED26 EMERGENCY INSTALLATION SHEET
WPLED26 (2X13)
EMERGENCY 120V OR
277V
WIRING DIAGRAM
4.18.12
LED 26W EMERGY COLD
120V OR 277V WIRING DLC
KS
AC DRIVER
COM
GROUND
BODINE
BSL722 LED
EMERGENCY
DRIVER
BATTERY 1
LEAVE OPEN
DO NOT CONNECT
DURING
MANUFACTURING
CUSTOMER SHOULD
CONNECT ONLY AFTER
FINISHING WIRING TO AC
POWER. BATTERY COULD
HAVE CHARGE & SHOCK
RED-WHITE STRIPE
RED
FUSE
HOLDER
CHARGING
INDICATOR LIGHT /
TEST SWITCH
BLUE
WHITE
YELLOW
YELLOW - BLACK STRIPE
WPLED26
SWITCHED HOT
CHARGING
INDICATOR/
TEST
SWITCH
BLACK
WHITE
WHITE/BLACK
VIOLET
BROWN
RED-WHITE STRIPE
BLUE
BLACK
BLACK
GREY
GREY
WHITE
YELLOW/RED
WHITE - RED STRIPE
WHITE
BLACK
WHITE
BLACK
BLACK
BLACK
BLACK
UNSWITCHED HOT
RAB LABEL - ADD
RAB LABEL - ADD
LABEL PROVIDED
BATTERY 2
EMERGENCY
HOUSING
RED
RED
RED
BLUE/ORANGE
RED
BLACK
WHITE
RED
YELLOW/RED
RED
WHITE
WHITE
WHITE
YELLOW/RED
RED
BLUE
BLUE
RED
WHITE
RED
YELLOW/RED
RED
WHITE
WHITE
BLUE/ORANGE
BAT 1
BAT 1
BAT 2
BAT 2
BAT 1
BAT 1
BAT 2
BAT 2
WPLED26/EC WIRING DIAGRAM (Refer to previous page for WPLED26/E wiring diagram)
WPLED26/EMG-IN-0414
  • Page 1 1
  • Page 2 2
  • Page 3 3

RAB Lighting WPLED26Y/E USA Operating instructions

Type
Operating instructions
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI