Lightolier A0200 User manual

Type
User manual

This manual is also suitable for

Lightolier Fixture A0200 is a pre-wired compact fluorescent emergency lighting fixture designed for decorative surface utility applications. It is intended for indoor use only and should be installed by a qualified electrician in accordance with the National Electrical Code and local regulations.

The fixture features two or three emergency lamps that automatically switch on at reduced output for 90 minutes in the event of a power failure. It is equipped with a charging indicator light that illuminates when the battery is being charged.

The fixture requires an unswitched source of power for the emergency pack and must be connected ahead of any local switching in switched fixtures. It comes with various wiring diagrams for different lamp configurations and voltage requirements.

Lightolier Fixture A0200 is a pre-wired compact fluorescent emergency lighting fixture designed for decorative surface utility applications. It is intended for indoor use only and should be installed by a qualified electrician in accordance with the National Electrical Code and local regulations.

The fixture features two or three emergency lamps that automatically switch on at reduced output for 90 minutes in the event of a power failure. It is equipped with a charging indicator light that illuminates when the battery is being charged.

The fixture requires an unswitched source of power for the emergency pack and must be connected ahead of any local switching in switched fixtures. It comes with various wiring diagrams for different lamp configurations and voltage requirements.

6.
Select the appropriate wiring diagram to connect the emergency pack and the AC ballast: (See Pages 2 & 3)
An unswitched source of power is required for the emergency pack.
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST.
INSTALLATION, BATTERY CONNECTOR MUST BE OPEN. DO NOT JOIN BATTERY CONNECTOR UNTIL
INSTALLATION
WARNING: TO PREVENT HIGH VOLTAGE ON THE RED & YELLOW OUTPUT LEADS PRIOR TO
Read and understand all instructions before proceeding.
A. WIRING -
personnel.
eyes. If acid is spilled on skin or eyes, flush with fresh water and contact a physician immediately.
emergency pack are turned off at the fuse box. Servicing should be performed by qualified personnel only.
end of the emergency pack). Make certain that the switch (if the fixture is switched) and the unswitched lines to the
10. Before servicing to prevent electrical shock, disconnect the battery connectors on the emergency pack (located on the
normal and the emergency power supplies before servicing.
9. This unit has more than one power supply connection piont. To reduce the risk of electrical shock, disconnect both the
8. Do not use the equipment for other than intended use.
7. The use of accessory equipment is not reccommended by the manufacturer and may cause an unsafe condition.
6. Equipment should be mounted in locations and at a height where it will not be readily subject to tampering by unauthorized
may burst or release toxic materials. Do not short circuit; may cause burns. Battery acid can cause burns to skin and
5. Do not attemp to service the battery. A sealed, rechargeable, no maintance battery is used. Do not incinerate or mutilate;
4. Do not mount near gas or electrical heaters.
3. Do not use outdoors.
are connected.
2. Be sure all electrical connections are complete and outlet box is closed before battery connectors on emergency pack
1. Turn off AC power before proceeding.
3. The emergency pack must be fed from the same branch circuit as the AC ballast(s).
1. Make sure AC power is off at fuse box.
2. Make sure that the necessary branch circuit wiring is available.
4. In switched fixtures, emergency pack must be connected ahead of any local switching.
connectors on emergency pack are connected.
5. Be sure all electrical connections are made and outlet box is closed before battery
IS:EMSU
Page 1 of 3A0200
INSTRUCTION SHEET NO.
631 Airport Road, Fall River, MA 02720
LIGHTOLIER a GENLYTE THOMAS company.
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
before installation. To prevent electric shock, turn off electricity at fuse box before proceeding.
To assure full compliance with local codes and regulations, check with your local electrical inspector
This fixture is intended for installation in accordance with the National Electrical Code and local regulations.
Retain these instructions for maintenance reference.
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED INCLUDING:
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
EMERGENCY LIGHTING DECORATIVE SURFACE UTILITY FIXTURES
INSTRUCTION FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT
WARNING: (RISK OF FIRE)
SUPPLY WIRING MUST BE RATED 90˚C. WHEN INSTALLING THE FOLLOWING MODEL NUMBERS ONLY: 5240WH326UE, 5241WH326UE,
5242PB326UE, 5243SA326UE, 5243SB326UE, 5543PB326UE AND 5543WH326UE. MOST DWELLINGS BUILT BEFORE 1985 HAVE SUPPLY WIRE RATED FOR 60˚.
CONSULT A QUALIFIED ELECTRICIAN BEFORE INSTALLATION.
SUPPLIED FOR THE INSTALLATION OF SPECIFIC MODEL BEING INSTALLED.
NOTICE: THIS INSTRUCTION SHEET TO BE USED IN CONJUNCTION WITH INSTRUCTIONS
631 Airport Road, Fall River, MA 02720
LIGHTOLIER a GENLYTE THOMAS company.
IS:EMSU
Page 2 of 3A0200
INSTRUCTION SHEET NO.
(TWO EMERGENCY LAMPS ON)
LEAD TO AC BALLAST HOT LEAD.
277V EMERGENCY PACK HOT
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
(TWO EMERGENCY LAMPS ON)
LEAD TO AC BALLAST HOT LEAD.
120V EMERGENCY PACK HOT
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
EMERGENCY LIGHTING DECORATIVE SURFACE UTILITY FIXTURES
INSTRUCTION FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
before installation. To prevent electric shock, turn off electricity at fuse box before proceeding.
To assure full compliance with local codes and regulations, check with your local electrical inspector
This fixture is intended for installation in accordance with the National Electrical Code and local regulations.
Retain these instructions for maintenance reference.
WIRING DIAGRAM B
(2-Lamp 39W 4 Pin Twin Tube
RED
RED
YEL B
YEL A
BLUE
BLUE
WHITE
BLACK
GREEN
RED
RED
YEL/BLK
YELLOW
BLUE
BLUE/WHITE
(COM) WHITE
120V (BLK)
(ORG)
277V
Pre-Wired for 120V)
GRD
GRD
HOTCOMHOT
(SWITCHED OR UNSWITCHED)
(UNSWITCHED)
CAPPED
UNUSED
JMPR 2
JMPR 1
RED
RED
SKTSKT
SKTSKT
LIGHT
INDICATOR
BROWN -
VIOLET +
SWITCH
TEST
BLK
BLK
BLK
BLK
RED
WHITE
CONNECTOR
BATTERY
BALLAST
EMERGENCY
BALLAST
AC
BALLAST
AC
WHITEWHITE
WIRING DIAGRAM C
(2-Lamp 39W 4 Pin Twin Tube
RED
YEL/BLK
YELLOW
BLUE
BLUE/WHITE
(COM) WHITE
277V (ORG)
(BLK)
120V
Pre-Wired for 277V)
HOTCOM
HOT
(SWITCHED OR UNSWITCHED)
(UNSWITCHED)
CAPPED
UNUSED
LIGHT
INDICATOR
BROWN -
VIOLET +
RED
WHITE
CONNECTOR
BATTERY
BALLAST
EMERGENCY
WIRING DIAGRAM A
(2-Lamp 13W OR 26W 4 Pin Quad Tube
Pre-Wired for 120V or 277V)
LEAD TO AC BALLAST HOT LEAD.
120V OR 277V EMERGENCY PACK HOT
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
RED
RED
YEL B
YEL A
BLUE
BLUE
WHITE
BLACK
GREEN
RED
RED
YEL/BLK
YELLOW
BLUE
BLUE/WHITE
(COM) WHITE
120V (BLK) OR 277V (ORG)
277V (ORG)
120V (BLK) OR
GRD
HOTCOMHOT
(SWITCHED OR UNSWITCHED)
(UNSWITCHED)
LEAD
CAP UNUSED
JMPR 1
JMPR 2
RED
SKT
SWITCH
TEST
SWITCH
TEST
BLK
BLK
BALLAST
EMERGENCY
BALLAST
AC
WHITE
LIGHT
INDICATOR
BROWN -
VIOLET +
RED
WHITE
CONNECTOR
BATTERY
SKT
JMPR 2
JMPR 1
(TWO EMERGENCY LAMPS ON)
RED
RED
YEL B
YEL A
BLUE
BLUE
WHITE
BLACK
GREEN
RED
IS:EMSU
Page 3 of 3A0200
INSTRUCTION SHEET NO.
631 Airport Road, Fall River, MA 02720
LIGHTOLIER a GENLYTE THOMAS company.
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
before installation. To prevent electric shock, turn off electricity at fuse box before proceeding.
To assure full compliance with local codes and regulations, check with your local electrical inspector
This fixture is intended for installation in accordance with the National Electrical Code and local regulations.
Retain these instructions for maintenance reference.
BLACK
GREEN
BLACK
OR UNSWITCHED)
(SWITCHED
HOT
WHITE
RED
RED
BLUE
BLUE
WHITE
BLACK
GREEN
BALLAST
AC
C. MAINTAINANCE
Although no routine maintainance is required to keep the emergency ballast functional, it should be checked periodically to
ensure that it is working. The following schedule is recommended:
reduced output for 90 minutes.
B. OPERATION
When AC power is applied, the charging indicator light is illuminated indicating that the battery is being charged. When the
power fails, the emergency lighting ballast automatically switches to emergency operation, keeping two lamps illuminated at
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture once every 3 months. Both lamps should operate at reduced output.
3. Conduct a 90 minute discharge test once a year. Both lamps should operate at at reduced output for 90 minutes.
EMERGENCY LIGHTING DECORATIVE SURFACE UTILITY FIXTURES
INSTRUCTION FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT
WIRING DIAGRAM D
(3-Lamp 26W 4 Pin Quad Tube
Pre-Wired for 120V or 277V)
LEAD TO AC BALLAST HOT LEAD.
120V OR 277V EMERGENCY PACK HOT
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
RED
RED
YEL A
YEL B
BLUE
BLUE
BLACK
GREEN
RED
RED
YEL/BLK
YELLOW
BLUE
BLUE/WHITE
(COM) WHITE
120V (BLK) OR 277V (ORG)
277V (ORG)
120V (BLK) OR
GRD
COMHOT
(UNSWITCHED)
LEAD
CAP UNUSED
JMPR 1
JMPR 2
RED
SKTSKT
SKT
SWITCH
TEST
BLACK
BLACK
BALLAST
EMERGENCY
BALLAST
AC
WHITE
LIGHT
INDICATOR
BROWN -
VIOLET +
RED
WHITE
CONNECTOR
BATTERY
(TWO EMERGENCY LAMPS ON)
  • Page 1 1
  • Page 2 2
  • Page 3 3

Lightolier A0200 User manual

Type
User manual
This manual is also suitable for

Lightolier Fixture A0200 is a pre-wired compact fluorescent emergency lighting fixture designed for decorative surface utility applications. It is intended for indoor use only and should be installed by a qualified electrician in accordance with the National Electrical Code and local regulations.

The fixture features two or three emergency lamps that automatically switch on at reduced output for 90 minutes in the event of a power failure. It is equipped with a charging indicator light that illuminates when the battery is being charged.

The fixture requires an unswitched source of power for the emergency pack and must be connected ahead of any local switching in switched fixtures. It comes with various wiring diagrams for different lamp configurations and voltage requirements.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI