SICK WSU26-2/WEU26-2 Photoelectric Safety Switch Operating instructions

Type
Operating instructions
S
D
DK
E
F
FIN
GB
GR
I
N
NL
P
WSU26-2/WEU26-2
Photoelectric Safety Switch
O P E R AT I N G I N S T R U C T I O N S
113
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Division Sécurité • RFA • Tous droits réservés
Notice
d'instructions
F
Homologations
Chapitre 10
143
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
Contents
1 Document Information 145
1.1 About this document 145
1.2 Target group 145
1.3 Scope of information 146
1.4 Symbols used in this document 146
2 Safety 147
2.1 Application areas of the device 147
2.2 Intended use of the device 149
2.3 General safety advice and protective
measures 150
2.4 Environmental compatibility 150
3 Product Description 151
3.1 System design 151
3.2 Mode of operation 151
4 Electrical Installation 152
4.1 Testing 153
4.2 Spark suppression 154
4.3 Short-circuit monitoring 155
4.4 Overvoltage protection (fuse) 155
5 Mounting 156
5.1 Safety distance 156
5.2 Distance to reflective surfaces 157
5.3 Multiple fuse protection 158
5.3.1 Interference 159
6 Commissioning 160
6.1 Alignment 160
6.2 Fault Diagnosis 161
7 Test Instructions 162
7.1 Pre-commissioning tests 162
7.2 Regular testing of the safety device by
experts 163
7.3 Daily testing of the safety device by
authorised personnel 163
8 Maintenance 165
Contents
144
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
9 Technical Data 166
10 Certificates of Conformity 169
11 Checklist 170
12 Appendix 339
Appendix 339
List of diagrams
1 Dimensional drawing for Models WSU 26/2-xx0 and
WEU 26/2-xx0
2 Dimensional drawing for Models WSU 26/2-xx4 and
WEU 26/2-xx4
3 Dimensional drawing for Models WSU 26/2-xx1 and
-xx3 and WEU 26/2-xx1, -xx2 and xx3
4 Connection schematic WSU 26/2-x3x (DC)
5 Connection schematic WEU 26/2-x3x (DC)
6 Connection schematic WSU 26/2-x1x, -x2x (AC)
7 Connection schematic WEU 26/2-x1x, -x2x (AC)
8 Connection schematic WSU 26/2-xx4
9 Connection schematic WEU 26/2-xx4
10 Correct and incorrect mounting of WSU/WEU with
multiple fuse protection systems
11 Mounting of two WSU/WEU in series
Contents
145
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
Abbreviations
Power-driven tools (machine, plant)
Non-contact protection system
Photoelectric Safety Switch: Sender unit
Photoelectric Safety Switch: Receiver unit
Output Signal Switching Device
Active Optoelectronic Protective Device
1.1 About this document
This document provides instructions for the operation of the
WSU/WEU Photoelectric Safety Switch. It contains information
on
! Application
! Mounting
! Electrical installation
! Commissioning
! Maintenance
1.2 Target group
The target group of this document is those who install, com-
mission and use the WSU/WEU Photoelectric Safety Switch.
Document Information
Chapter 1
1 Document Information
KA
BWS
WSU
WEU
OSSD
AOPD
146
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
1.3 Scope of information
These Operating Instructions contain information on how to in-
stall, commission and operate the device. Official and legal re-
gulations must always be observed. It is not possible to
provide comprehensive information on all these requirements
in this document. In Germany, for example, the Trade Associati-
on Directives (ZH 1/597 and ZH 1/281) in particular must be
observed. Further information on health and safety and opto-
electronic protection equipment can be obtained directly from
your local SICK distributor, e. g. Safe Machines (SICK guideli-
nes on the operation of optoelectronic protection equipment).
1.4 Symbols used in this document
Some information in these Operating Instructions is highlighted
to ease rapid access to this information:
A note provides information on special features of the device.
An explanation gives basic information.
A recommendation assists in deciding upon the best action.
Warning!
A warning indicates actual or potential hazards. This is to redu-
ce the risk of accidents.
Always read warning notices carefully and follow them closely.
Document Information
Chapter 2
Note
Explanation
Recommendation
WARNING
147
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
The devices can only perform their safety function if they are
used correctly and integrated into the process in a failsafe
manner.
The WSU/WEU Photoelectric Safety Switch meets the require-
ments of Type 4 Safety Devices as stipulated in EN 61 496-1
and pr EN 50 100-2.
2.1 General safety advice and
protective measures
1. National and international regulations apply for the operati-
on of non-contact protection equipment as well as for com-
missioning and regular maintenance checks, in particular
! Machinery Safety Regulation 98/37 EC
! Provision and Use of Work Equipment Regulations
89/665 EEC
! Relevant safety regulations
! Accident prevention regulations and safety guidelines
It is the responsibility of the manufacturers and operators
of the machine on which SICK protection equipment is used
to discuss all safety legislation, which may apply, with the
responsible authorities and to observe these rules and re-
gulations.
2. Furthermore, our notes, in particular the Test Regulations
(see section ‘Tests’) in the Technical Description or these
Operating Instructions (such as use, assembly, installation
Safety
Chapter 2
2 Safety
WARNING
148
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
or integration in the machine control unit) must be obser-
ved.
3. The tests must be performed by qualified experts or by
specially authorised and instructed personnel and must be
documented in such a way as to be able to be viewed and
understood at any time.
4. Our Operating Instructions shall be given to the employee
(operator) working at the machine on which SICK protection
equipment is used. The employee shall be trained for his
job and operation of the equipment by an expert.
5. The Test Protocol relating to use of the non-contact safety
device is printed at the end of the English section of these
Operating Instructions. Acceptance testing is performed on
the basis of that protocol.
6. Mounting and connection may only be done by qualified
personnel. Before commissioning, the mounting and con-
nection must be inspected by the operator’s responsible
staff member, as is required by the standards and directi-
ves of the specific country.
Safety
Chapter 2
149
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
System construction of the WSU/WEU 26/2
Entry/exit safeguarding using a WSU/WEU 26/2
The following key points are important for correct operation:
2.2 Application Areas
The WSU/WEU 26/2 Photoelectric Safety Switch is used as an
access safety system to hazardous areas around machinery or
plant. The device is securely mounted in the access area at a
pre-determined safe distance from the hazardous point. When
the light beam is interrupted the device transmits an emergen-
cy stop signal to the machinery or plant.
Safety
Chapter 2
Point-of-operation
Mechanical
guarding
Direction of
entry into
hazardous
area
Entry/exit
guarding
with WSU/WEU
RW
WSU WEU
0,5 ... 18 m
15 ... 70 m
Beam diameter
23 mm
150
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
2.3 Intended use of the device
The WSU/WEU Photoelectric Safety Switch may only be used as
specified in Section 2.2 Application Areas. The device may be
operated only in accordance with its technical specifications.
Any other use or modification – including during mounting and
installation – will invalidate any guarantee and any claim
against SICK AG.
2.4 Environmental compatibility
The WSU/WEU Photoelectric Safety Switch is designed to have
the lowest possible impact on the environment. It neither emits
nor contains any environmentally damaging substances, and
consumes minimal quantities of energy and resources.
Always consider the environment in everything you do at your
workplace. This also means complying with the following in-
structions concerning disposal.
Disposal
Unusable systems or systems beyond repair must be disposed
of in accordance with the regulations on refuse disposal cur-
rently valid in the respective country.
The aluminium housing must be recycled. If possible, remove
the plastic front panel.
All electronic components can be simply dismantled. They
should be disposed of as special waste. SICK AG will not ac-
cept back unusable systems or systems beyond repair.
When dismantling and disposing of components, provisions re-
lating to occupational safety, the environment and disposal
should be observed.
Safety
Chapter 2
151
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
3.1 System design
The WSU/WEU Photoelectric Safety Switch comprises the follo-
wing components:
! WSU Sender unit
! WEU Receiver unit
3.2 Mode of Operation
The WSU/WEU 26/2 Photoelectric Safety Switch consists of
one sender unit and one receiver unit. The WSU sender unit
emits a light beam, which is picked up by the WEU receiver
unit.
An interruption in the light beam by an object causes the out-
put relay to de-energize, which stops the machine.
The sender and receiver units are equipped with LEDs for func-
tion monitoring. Their function as a diagnostic element is set
out in Section 6 Commissioning.
Indicator diodes on the device signal the various operating mo-
des (see Section 6.2 Fault Diagnosis). However, the informati-
on that they display is not relevant to safety status. The
indicator diodes also serve as error diagnostic systems (see
Section 6.2 Fault Diagnosis).
Product Description
Chapter 3
3 Product Description
152
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
Electrical connections must be made appropriate to device op-
tion (see Connection Schematics in the Appendix). With device-
connector options, pay attention to the coding denoted. It must
match the coding of the cable socket, thus preventing connec-
tion to an unsuitable version (other supply voltage, other ran-
ge).
Both contacts at the test input of the sender unit must be clo-
sed during operation. Testing (open for min. 75 ms and close
again) should be done with an uninterrupted light beam. This
causes the output relay to de-energize.
Switch off power!
Electrical connection of the WSU/WEU or modification may only
be carried out with power removed.
To connect the WSU/WEU with a PG thread, the housing lid
must be unscrewed.
Use both normally-open contacts!
At least two outputs must be connected to the control unit of
the machine being protected (Figs. 4, 5, 7, 9, Appendix). An
electromagnetic contact element (relay) must be connected to
each of the two outputs (normally-open contacts).
Electrical Installation
Chapter 4
4 Electrical installation
WARNING
WARNING
Note
153
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
Use normally-open outputs!
In new factories, both normally-open outputs must be indepen-
dently supplied to two contact elements (e.g. contractors, re-
lays). The normally-closed output should be used only for
functions that are not directly safety-related.
In general, the normally-open contacts
should be used. However, in older
factories a normally-open / normally-
closed combination was selected.
This no longer conforms to present-
day safety requirements. Should the
WSU/WEU be installed in old factories,
both normally-open contacts should
be connected in series to the
normally-closed contact as a second
channel.
4.1 Testing
This enables a check to be made on the contact elements con-
nected. In the process, operation of the normally-closed con-
tacts will de-activate the sender. Testing is initiated during a
minimum open time (see Section 9 Technical Data).
Testing must be undertaken via machinery control in the safe
phase (e.g. a safe movement). If the test is unsuccessful, the
power-driven machine - initiated by the WEU - will receive a de-
energize signal from the machinery control system.
Use the testing function as described!
The test input must be used exclusively as described.
456789
K1
K2
Installation in old facto-
ries
WARNING
WARNING
Electrical Installation
Chapter 4
154
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
4.2 Spark suppression
Spark suppressors are required when using an
inductive load ...
... and must be connected in parallel to the inductive load. Con-
nections that are made in parallel to the output contact are not
permissible, and may result in unsafe operation.
Wiring for inductive contact element
Supply voltage Part No. R C
V ΩµF
115 ... 230 6 001 224 220 0,22
24 6 001 225 100 2,2
Option: plastic encapsulated; connection wires
NYAF 0.5 mm Ø with spade terminals; fixing with adhe-
sive pad or cable ties.
Summary of Spark suppressor values
Electrical Installation
Chapter 4
WARNING
C
R
Supply
voltage
User
relay
Contact
in
WEU
155
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
4.3 Short-circuit monitoring
The cables from the output contacts are not monitored by the
WEU for short circuits.
Suitable measures
Suitable steps should be taken for monitoring short circuits.
These could be
! Short-circuit safe (protected) routing of cables from the WEU
to the contact elements
! Screening output cables individually and connect screening
to 0 V
! Incorporating both contacts to differing voltage levels
! Using relay(s) at the outputs where the pull in voltage must
be greater than U
V
/2.
4.4 Overvoltage protection (fuse)
A fuse must be provided for the control circuit. The fuse rating
must correspond to the maximum current draw of the output
relay.
Electrical Installation
Chapter 4
WARNING
156
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
Provisionally install the Photoelectric Safety Switch, coarsely
aligned. This alignment is done with the help of the sight groo-
ve on the upper section of the housing and the lateral beam
marking.
5.1 Safety distance
The WSU/WEU must be attached such that, if the light beam is
broken during hazardous movement of the machinery, the
point-of-operation can only be reached when this hazardous
movement has ceased. For this purpose, a safety distance S
must be maintained between the nearest boundary of the
Safety distance between the nearest boundary of the point-of-ope-
ration and the light beam
Mounting
Chapter 5
5 Mounting
S
Mechanical
guarding
Point-of-operation
Entry/exit
guarding
with WSU/
WEU
Direction of
entry into ha-
zardous area
157
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
point-of-operation and the light beam (Fig.). The safety di-
stance depends on the machine stopping time and on the ap-
proach speed of the personnel.
The machine stopping time must be determined by repeated
measurements under practical conditions. 1.6 m/s is the re-
commended approach speed.
The safety distance is calculated as follows:
S Safety distance (mm)
K Approach speed 1.6 m/s
T Machine stopping time (ms) + response time of WEU
(see 9 Technical Data)
C Dependent on number of beams (1, 2, or 3), see Table
Number of beams 1 2 3
Height of beam(s) 750 400 300
above floor (mm) 900 700
1100
C 1200 850 850
5.2 Distance to reflective surfaces
Reflective surfaces located (placed or fixed) within the sender
and receiver range, may cause reflection and thus prevent an
obstacle from being reliably detected.
For this reason, a minimum distance "a" from reflective sur-
faces to the optical axis (linear connection between transmitter
and receiver) must be maintained (see illustration below). The
distance "a" is dependent on the distance between the sender
and receiver.
Testing for spurious reflection is described in Section 7 Test
Instructions.
S = K · T + C
Mounting
Chapter 5
158
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
Correct mounting, correctly aligned: reflective object outside diver-
gent light beam. No reflection. The obstacle is clearly detected
Distance "a" as a function of scanning range RW I and RW II
a (mm)
2500
2000
1500
1000
500
400
300
200
100
3
10
6
20
12
40
9
30
18
60
15
50
21
70
WSU WEU
4Ëš
4Ëš
a
a
a (70 m)
a (18 m)
RW (m)
RW I
RW II
5.3 Multiple units
When using two WSU/WEU in a single safeguarding application,
interference must be prevented. Because the light beam of the
WSU diverges, the light-beam cross section increases the grea-
ter the distance between the WSU and the WEU. Consequently,
WSU WEU
a
4Ëš
4Ëš
Central beam Entry direction
Beam array bro-
ken
Obstacle
Mounting
Chapter 5
Reflective object (e.
g. material container)
Point-of-
operation
boundary
159
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
GB
the following conditions must be observed when installing the
WSU/WEU (Fig. 10, Appendix).
5.3.1 Interference
The light beam from the WSU must be received only by the in-
tended WEU. To prevent interference from several adjacent
WSU/WEUs, the appropriate light beam diameters when moun-
ting the devices (Fig. 11, Appendix) must be taken into consi-
deration.
WSUs are available in two options ...
... for operating ranges 0.5 - 18 m and also 15 - 70 m. The
WSU for 15 - 70 m may not be used for operating ranges be-
low 15 m. The operating range is stated on the type plate.
Mounting
Chapter 5
WARNING
160
WSU/WEU 26/2
8 008 631/P134/20-12-04 © SICK AG • Safety Systems • Germany • All rights reserved
Operating Instructions
The device is switched on by connecting the supply voltage to
the sender unit and to the receiver unit. The device is ready for
operation after approx. 2 s.
For more detailed information on this, see Technical Descripti-
on WSU/WEU 26/2.
6.1 Alignment using the indicator lights
Switch on the supply. The yellow LED on the WSU should light
up.
Align the modules with each other such that the green and yel-
low LEDs on the WEU light up.
For optimum alignment, determine the limits of the transmissi-
on and receiving range by pivoting the sender and receiver
units horizontally and vertically. When the device leaves its re-
spective optical range, the yellow LED on the WEU begins to
flash. Then fix the sender and receiver units in the middle of
the determined optical range.
Commissioning
6 Commissioning
Chapter 6
WSU WEU
yellow green
red
yellow
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350