Mollet MSD Silo Pressure Detector Operating instructions

  • Hello! I'm a chat assistant, and I've analyzed the operating instructions for the MOLLET MSD-070 and MSD-A pressure detector. This document details the device's intended use as a limit switch for overpressure in silos and vessels, along with safety precautions, technical specifications, and installation guidelines. I am ready to answer your questions about this device.
  • What is the intended use of the pressure detector?
    What happens when the pressure reaches the switching point?
    What are the temperature specifications for this device?
    What is the switching point adjustment?
1.3 Technical data
1.1 Intended use
74706 Osterburken
Ambient temperature -20 °C ... +70 °C
Signal contact change-over contact, potentialfree
If the pressure reaches the switching point SP, the pressure detector
Capacity of the contact 4 A / 250 V AC
will give a signal.
Switching voltage 24 V ... 250 V AC
or 12 V ... 125 V DC
Füllstandtechnik GmbH
Bulk good temperature -25 °C ... +80 °C
Switching point 40 mbar = 0.04 bar = 400 mm WS
Overpressure safety up to 0.5 bar
Cable connection Screw M4
Operating instructions
Manufacturer MOLLET
Cable entry Cable gland M20x1.5
1. Description
Type MSD-070
silos and vessels.
The pressure detector controls as limit switch the overpressure in
1.2 Function
Name Silo pressure detector
Address Industriepark RIO 103
Flange Aluminium
as option Stainless steel 1.4571 / 316 Ti
Weight 1.1 kg
Membrane Stainless steel 1.4301 / 304
Flange socket Steel
Type of protection IP65 acc. to DIN EN 60529
Maintenance none
1.4 Material
Mounting position vertical, ± 5° inclination
Housing ABS (high impact plastic), grey
1.5 Dimensions
M LLET
Füllstandtechnik
GmbH
MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846 Operating instructions
04/13 © by MOLLET MSD-BA 01
8. Attention safety device! Don´t modify anything at the device or at the switching point adjusting!
7. Switch off the power supply, before opening the device. (touch dangerous voltage)
5. Protect the signal contact from voltage peaks when inductive loads are connected.
4. A fuse (with max. 4A) has to be connected upstream in series to the signal contact.
6. The device may put into operation if it is closed, only.
3. Take notice of the temperature specifications at the data plate.
Safety instructions
1. The installation, initial operation and maintenance may be done by a qualified expert with electrical know-how only.
2. Comply with the local and statutory rules and regulations and/or the VDE 0100.
Read and follow these safety instructions first and take notice of the operating instructions.
Flange socket
1.6 Accessory (Option)
IP
SP
Ta
Ts
Contact
MOLOS
Silo pressure detector
MSD
Ø 110
Lk 90 / 4xM8
10
150
Ø 74x2
Gasket
130x105
top
M20x1,5
124
15
10
66
Ø 69
Lk 90 / 4xØ 9
Ø 110
008-0200
[
2. Installation
gasket at the provided flange or flange socket and fix it with
2.3 Electrical connection
Circuit diagram
instructions, before handling with the device !
2.2 Mounting in the vessel
- Weld the flange socket (as a option) vertical (Flange is horizontal)
2.1 Preparation
- Position the pressure detector (Flange is horizontal) with the
- Check the membrane of visual transport damage.
- Read and follow the safety instructions and the operating
4 washers and screws M8.
in the silo top.
2.4 Cable gland
- After electrical connection, tighten the cable gland.
- Screw the cap nut, until the cable entry is closed tightly.
2.5 Cable run
Run the connection cable in a way that no traction can occur at the
pressure detector.
- The switching point is adjusted at 40 mbar.
2.6 Switching point
- A modification may be carried out by the manufacturer only.
M LLET
Füllstandtechnik
GmbH
02 MSD-BA 04/13 © by MOLLET
Operating instructions MOLLET D-74706 Osterburken Tel. +49 6291 6440-0 Fax +49 6291 9846
008-0700
the silo or vessel and the electrical connection have been done
correctly.
3. Utilization
- The pressure detector must not be modified. If there is any
modification, the warranty of the manufacturer will be, cancelled.
3.3 Inexpert handling
- Put the pressure detector into operation only, if the installation in
- Damaged devices have to put out of operation immediately.
- Comply with the specifications on the data plate.
- Use the pressure detector in its intended application only.
3.2 Normal operation
3.1 Commissioning
- The disposal applies to the valid environmental guidelines
conditions.
4. Maintenance and servicing
- Ignoring of the safety instructions and the operating instructions.
- Not intended use.
maintenance.
manufacturer only.
- In case of intended use, the silo pressure detector needs no
- The servicing of the pressure detector may be carried out by the
- Store the pressure detector dry and dust-free.
-
6. Disposal
- The pressure detector can be recycled.
-
4.1 Maintenance
according to the location of the carrier and the local manufacturing
-
- Violation against applicable law and standards.
5. Storage
- Modification at the device or of the switching point adjusting.
-
- Protect the membrane from damage.
4.2 Servicing
008-AP00
P
2
3/4
1
PE
NC
NO
C1 2
3/4
40 mbar
MOLOS
Silo pressure detector
MSD
L
L
E
O
T
M
-
-
F
n
ü
e
l
l
k
s
r
t
a
u
n
b
r
d
e
t
t
e
s
c
h
O
n
6
i
k
0
7
G
4
m
7
-
b
D
H
H
ExB
Wolfgang Hageleit
Geschäftsführer / Managing director
EU-Konformitätserklärung
EU-Declaration of Conformity
Wir/We MOLLET Füllstandtechnik GmbH
Industriepark RIO 103
D-74706 Osterburken
Tel. 06291 64400 Fax 06291 9846
erklären in alleiniger Verantwortung, dass das Produkt:
declares under our sole responsibility, that the product:
Silo-Druckmelder / Silo pressure detector
Typ/Type MSD-070 ... , MSD-A ...
den folgenden Europäischen Richtlinien entspricht:
conforms with the following European directives:
Niederspannungsrichtlinie Low voltage directive 2014/35/EU
Angewandte harmonisierte Normen oder normative Dokumente:
Applied harmonized standards or normative documents:
DIN EN 61010-1:2020 DIN EN 60529:2014
Und die Geräte mit W - Kennzeichnung entsprechen zusätzlich der folgenden Europäischen Richtlinie:
And the devices with W - marking conform additional with the following European directive:
ATEX-Richtlinie ATEX directive 2014/34/EU
Je nach Ausführungsvariante angewandte harmonisierte Normen oder normative Dokumente:
Depending on the design applied harmonized standards or normative documents:
DIN EN IEC 60079-0:2019 DIN EN 60079-11:2012 DIN EN 60079-26:2015
DIN EN 60079-31:2014
EU-Baumusterprüfbescheinigungsnummer:
EU-Type Examination Certificate: IBExU06ATEX1069
Ausgestellt von:.
Issued by: IBExU Institut für Sicherheitstechnik GmbH, 09599 Freiberg (0637)
Qualitätssicherung:
Quality assurance: TÜV NORD CERT GmbH, 30159 Hannover (0044)
Osterburken, den 03.06.2022
EUKE-MSD
M LLET
Füllstandtechnik
GmbH
Diese Erklärung darf nur unverändert weiterverbreitet werden.
This declaration is only allowed to hand out in unchanged form.
15_EUKE-MSD_0
Index 0
Seite/Page 1 von/of 1
/