12
2. Installation
PXM 1000 User Manual MN150009EN October 2018 www.eaton.com
Voltage Input
Maximum input voltage for the PXM 1000 meter shall not exceed 400LN/690LL VAC rms for
three-phase or 400LN VAC rms for single-phase.
A potential transformer (PT) must be used for medium voltage systems. A typical secondary
output for PTs is 100 or 120 V. Note that the PT secondary voltage setting defaults to 220.
Make sure to change this to the appropriate PT setting when setting up the meter. Please
make sure to select an appropriate PT to maintain the measurement accuracy of the meter.
When connecting using the star configuration wiring method, the PT’s primary side rated
voltage should be approximately equal to the phase to neutral voltage of the system to uti-
lize the full range of the PT. When connecting using the delta configuration wiring method,
the PT’s primary side rated voltage should be approximately equal to the line to line voltage
of the system. A fuse (typical 1 A/250 Vac) should be used in the voltage input loop. The
wire for voltage input is AWG 16-12 or
1.3-2.0 mm2.
ote:N In no circumstance should the secondary of the PT be shorted. The secondary of the
PT should be grounded. Please refer to the wiring diagram section for further details.
Current Input
Current transformers (CTs) are required in most engineering applications. A typical current
rating for the secondary side of the CT is 5 A (standard) or 1 A (optional). Please refer to
the ordering information appendix for further details. CTs must be used if the system rated
current is over 5 A. A CT with 0.5% accuracy or better, with a rating over 2.5 VA is recom-
mended to ensure the meter’s accuracy. The wire length between the CTs and meter shall
not exceed the burden rating of the CT to insure accuracy.
Meter Current inputs accept AWG 15-10 or 1.5-2.5 mm2.
WARNING
When power is on, the secondary side of the CT should not be open circuit in any cir-
cumstance. There should not be any fuse or switch in the CT loop. One end of the CT
loop should be connected to Ground.
Vn Connection
Vn is the reference point of the PXM 1000 meter voltage input. Low wire resistance helps
to improve the measurement accuracy. Different system wiring modes require different Vn
connection methods. Please refer to the wiring diagram section for more details.
3-Phase Wiring Diagram
This meter can satisfy almost any kind of three-phase wiring diagrams. Please read this sec-
tion carefully before choosing the optimum wiring configuration for your power system.
The voltage and current input wiring mode can be set separately in the meter parameter set-
ting process. The voltage wiring mode can be set as 3-phase 4-wire Wye
(3 LN), 3-phase 3-wire direct connection (3 LL), 3-phase 3-wire open delta (2 LL), single-
phase 2-wire (1 LN), and single-phase 3-wire (1 LL). The current input wiring mode can be
set as 3 CT, 2 CT, and 1 CT. The voltage mode can be grouped with the current mode as 3
LN-3 CT (3 CT or 2 CT), 3 LL-3 CT, 2 LL-3 CT, 2 LL- 2 CT, 1 LL-2 CT, 1 LN-1 CT.
2.3.3 Voltage Input Wiring
3-Phase 4-Wire Wye Mode (3 LN)
The 3-phase 4-wire wye mode is commonly used in low voltage electric distribution power
systems. For voltage lower than 400 LN/690 LL Vac, a power line can be connected directly
to the meter’s voltage input terminal as shown in Figure 8.
For high voltage systems (over 400 LN/690 LL Vac), PTs are required as shown in Figure 9.
The meter should be set to 3 LN for both voltage levels.