GB-14
GB
▷
The display indicates
H7
. After pre-purge (and the
end of the valve check on FCU..C1), the valves
in the gas inlet section are opened.
▷
The display indicates
08
. The FCU issues the
enable signal to the burner control units to start
the burners.
High temperature operation
The FCU..H1 is fitted with an integrated temperature
module for high temperature operation. As soon as
the FCU has received the signal from the connected
double thermocouples that the temperature defined
in parameter24 has been reached, a signal is sent
to the high temperature inputs of the burner control
units by the output at terminal 18. If voltage is applied
to the high temperature inputs, the burner flames will
no longer be monitored by the burner control units.
WARNING
Risk of explosion! High temperature operation is
only permitted if the temperature in the furnace
chamber is so high that the gas/air mixture is reli-
ably combusted.
In countries where EN746/NFPA86 is applicable,
if the furnace wall temperature is greater than or
equal to 750°C (1400°F), the flame may be moni-
tored by a fail-safe temperature monitoring device
that complies with the standard.
Only if the temperature is greater than or equal
to 750°C (1400°F) may voltage be applied to the
high temperature inputs of the burner control units.
Comply with the local safety regulations.
▷ In high temperature mode, the two dots in the
display are lit permanently.
▷
The flame control system is placed out of op-
eration.
▷
Once the furnace temperature falls below the
value defined in parameter24, terminal18 is
isolated from the voltage supply. The burner con-
trol units continue operating with flame control,
depending on their setting.
Manual mode
▷
For adjustment of the furnace system or for
fault-finding.
▷
In Manual mode, the FCU operates indepen-
dently of the status of the inputs for start-up
signal (terminal1), controlled air flow (terminal2)
and remote reset (terminal3). The function of the
controller enable/emergency stop input (termi-
nal46) is retained.
▷ Manual mode is terminated by switching off the
FCU or in the event of a power failure.
▷
Parameter 67 = 0: Manual mode unlimited in
time. The furnace may continue to be operated
manually in the event of failure of the control
system or the bus.
▷
Parameter 67 = 1: The FCU will terminate Manual
mode 5minutes after the last time the Reset/
Information button is pressed. It switches to the
start-up position/standby(display
00
).
Switch on the FCU while holding the Reset/In-
formation button. Hold the Reset/Information
button until the two dots in the display start to
blink.
▷ If the Reset/Information button is pressed, the
current step in Manual mode is shown. After
the button has been held for 1 second, the next
step will be shown. The FCU now executes its
program sequence until the display indicates
08
.
FCU..F with IC 0
▷
Following controller enable (display
0.8.
), actuator
IC20 can be opened and closed as required.
Press the Reset/Information button.
▷
If the button continues to be held down, the
actuator opens further until maximum capacity
has been reached.
▷ The display indicates
A.1.
with blinking dots.
▷
Once the button has been released, the butterfly
valve stops in the relevant position.
Press the Reset/Information button again.
▷
If the button continues to be held down, the
actuator closes further until minimum capacity
has been reached.
▷ The display indicates
A.0.
with blinking dots.
▷ A change of direction takes place each time the
button is released and pressed again. When the
butterfly valve has reached its final position, the
dots disappear.
FCU 500..F with IC40, FCU500..F with
RBW or frequency converter
▷
Following controller enable (status display
0.8.
), it
is possible to approach binary positions between
minimum and maximum capacity.