Krom Schroder FCU 500 Operating Instructions Manual

Type
Operating Instructions Manual

This manual is also suitable for

DK S N P GR
www.docuthek.com
D GB F NL I E
TR CZ PL RUS H
© 2015 Elster GmbH · Edition 03.15
Safety
Please read and keep in a safe place
Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the opera-
tor. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
, , , ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-com-
pliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Changes to edition 09.4
The following chapters have been changed:
Replacing the protective system/furnace zone
control
– Certification
Contents
Operating instructions
D
GB
F
NL
I
E
GB-1
0506
Translation from the German
Protective system control FCU 500
Furnace zone control FCU 505
Protective system control FCU 500
Furnace zone control FCU 505 ............
Contents ..............................
Safety.................................
Checking the usage .....................
Installation ............................
Replacing the protective system/furnace
zone control ...........................
Cable selection.........................
Wiring ................................4
Connection diagram ....................6
FCU 500 ..............................6
FCU 505 .............................. 7
IC 20 connected to FCU..F1 ...............8
IC 20 E connected to FCU..F1..............9
IC 40 connected to FCU..F1 ..............10
RBW valve connected to FCU..F2 .......... 11
Frequency converter connected to FCU..F2 ..12
Adjustment ...........................
Commissioning........................
Manual mode .........................4
Assistance in the event of malfunction ....5
Replacing the fuse ...................... 21
Parameters and values .................
Legend...............................4
Technical data ........................4
Designed lifetime .......................25
Logistics .............................5
Accessories ..........................5
Certification ..........................6
Contact ..............................6
Safety
Contents
GB-2
D
GB
F
NL
I
E
Checking the usage
The protective system control FCU 500 and furnace
zone control FCU 505 are designed for the moni-
toring and controlling of central safety functions in
multiple burner systems on an industrial furnace.
The FCU500 controls multiple zones acting as the
central protective system control. The FCU505 is
used for protective system and capacity control in
individual furnace zones.
Type code
Code Description
FCU 500
FCU 505
Protective system control
Furnace zone control
Q
W
Mains voltage: 120 V AC, 50/60 Hz
230 V AC, 50/60 Hz
C0
C1
No valve proving system
With valve proving system
F0
F1
F2
Capacity control:
none
with interface for actuator IC
with interface for RBW
H0
H1
Temperature monitoring:
none
with temperature monitoring
K0
K1
K2
Connection terminals:
none
screw terminals
spring force terminals
Part designations
3
5
2
6
8
1
7
4
LED display for program status and fault
messages
Reset/Information button
On/Off button
4 Type label
5 Connection for opto-adapter
6 Power module, detachable
7 Power module type label
8 Parameter chip card
Type designation (FCU…), construction stage, input
voltage – see type label.
FCU
Installation
Installation position: vertically upright, horizontal
or tilted to the left or right.
The FCU mounting is designed for horizontally
aligned 35 × 7.5 mm DIN rails.
If the DIN rail is aligned vertically, end clamps are
required (e.g. Clipfix 35 by Phoenix Contact) to
prevent the FCU from slipping.
Install in a clean environment (e.g. a control
cabinet) with an enclosure ≥ IP 54, whereby no
condensation is permitted.
1
GB-3
D
GB
F
NL
I
E
Replacing the protective system/
furnace zone control
Disconnect the system from the electrical power
supply.
2
Disengage the FCU from the DIN rail.
4 5
6 Transfer the parameter values from the old FCU
to the new FCU.
Remove the parameter chip card from the old
FCU and insert into the new FCU.
CAUTION
Malfunction (fault message
)! The old and
new FCUs must have the same hardware confi-
guration (see type designation on type label). The
parameter chip card is not backward compatible.
If the parameter chip card has been operated in
an FCU with more recent firmware, it cannot be
used in a device with older firmware.
Alternatively, the parameters values can be read
from the old FCU and then read back into the
new FCU using the separate BCSoft software,
see pages 13 (Adjustment) and 25 (Ac-
cessories).
7 Slide the power module back on.
8 Mount the FCU on the DIN rail again.
9 Reconnect the connection terminals.
0 Switch the system on again, see page 13
(Commissioning).
Fault message
: Parameter chip card from
FCU construction stage B or above has been
inserted into FCU construction stage A, see also
page 15 (Assistance in the event of malfunc-
tion).
Cable selection
Use cables suitable for the type of operation and
complying with local regulations.
Signal and control line for screw terminals
max. 2.5mm
2
, for spring force terminals max.
1.5mm
2
.
Do not route FCU cables in the same cable duct
as frequency converter cables or cables emitting
strong fields.
Control lines must fulfil the requirements of
EN60204-1, Chapter12.
Avoid external electrical interference.
GB-4
D
GB
F
NL
I
E
Wiring
Do not reverse phase L1 and neutral conduc-
tor N.
Do not install different phases of a three-phase
current system at the inputs.
Do not connect voltage to the outputs.
A short-circuit on the outputs causes one of the
replaceable fuses to trip.
Ensure that the inputs at terminals 1 to 4 and
44 are only supplied with 24 V DC.
24 V DC power supply: + at terminal 62, - at
terminal 61.
Ensure that the 24 V DC outputs at terminals
41 and 42 are not connected to mains voltage.
Do not set the remote reset so that it operates
automatically in cycles.
Wire the safety circuit inputs via contacts (relay
contacts) only.
The unit features an output for fan control (termi-
nal58). This single-pole contact can be loaded
with a max. of 3A. The max. start-up current of
the fan motor may not exceed a value of max.
6A for 1s– use an external contactor if required.
The limiters in the safety interlock (linking of all the
relevant safety control and switching equipment
for the use of the application, for example, safety
temperature limiter) must isolate terminal46 from
the voltage supply. If the safety interlock is in-
terrupted, the display shows a blinking
50
as
a warning signal and all of the FCU’s control
outputs are disconnected from the electrical
power supply.
Connected control elements must be equipped
with protective circuits in accordance with the
manufacturer’s instructions. The protective circuit
prevents high voltage peaks which can cause
malfunctioning of the FCU.
Functions of terminals 51, 65, 66, 67 and 68 are
dependent on parameter values:
Terminal Dependent on parameter
51 69
65 70
66 71
67 72
68 73
See page 22 (Parameters and values).
Disconnect the system from the electrical power
supply.
Before wiring the FCU, ensure that the yellow
parameter chip card has been installed in the
FCU– see page3 (Replacing the protective
system/furnace zone control).
Screw terminals or spring force terminals are
available for the FCU– see page25 (Acces-
sories).
Wire as shown on the connection diagram– see
page6 (Connection diagram).
Ensure a good PE (ground) wire connection to
the burner control units and burners.
FCU..H
Use type K NiCr-Ni, type N NiCrSi-NiSi or type S
Pt10Rh-Pt Class 1 double thermocouples only.
Thermocouple
Temperature range
(°C)
Type K NiCr-Ni -40 to 1000
Type N NiCrSi-NiSi -40 to 1000
Type S Pt10Rh-Pt 0 to 1600
Parameter 22 = 1: Type K double thermocouple
NiCr-Ni
Parameter 22 = 2: Type N double thermocouple
NiCrSi-NiSi
Parameter 22 = 3: Type S double thermocouple
Pt10Rh-Pt
STM:
Parameter 20 = 1: High temperature operation
with STM. Position the double thermocouple at
the coldest point in the furnace so that it can
reliably detect whether the spontaneous igni-
tion temperature (>750°C) has been exceeded.
STL:
Parameter 20 = 2: Maximum temperature moni-
toring using STL. Position the double thermo-
couple at the warmest point in the furnace so
that it can reliably detect whether the maximum
permitted temperature has been exceeded.
STL and STM:
Parameter 20 = 3: High temperature operation
with STM and maximum temperature monitor-
ing with STL. Position the double thermocouple
in the furnace in such a way that it can reliably
detect whether the spontaneous ignition tem-
perature (>750°C) has been exceeded and
also whether the maximum permitted furnace
temperature has been exceeded.
FCU..C
Parameter 51 = 1: Tightness test before furnace
start-up.
Parameter 51 = 2: On; tightness test after fur-
nace shut-down, after a fault lock-out or after
mains on.
Parameter 51 = 3: On; tightness test before
furnace start-up and after furnace shut-down.
Parameter 51 = 4: Permanent via proof of closure
function (POC).
GB-5
D
GB
F
NL
I
E
Safety interlock output in the case of higher
power requirement
The burner start enable signal is issued to the
connected burner control units or automatic bur-
ner control units via the safety interlock output
(terminal 57).
For burner control units or automatic burner
control units whose safety interlock input has
a power consumption of ≤ 2 mA, the power
(max. 0.5 A, cos ϕ = 1) of the FCU is sufficient
to directly activate them.
In the event that a higher output current is re-
quired, the output current can be increased by
means of a contact multiplier using two contac-
tors. Design the circuit as follows:
61 62
FCU 500
5AT
FS
A
STW/
STB
+ - + -
L1
+24 V
V1
V2
V3
41 42 44 45
65
46
66
47
48
68
53 54 55 56 57 5849 50 51 52
ϑ
LDS
HT
P
90°
90°
67
13 14 15 16 17 185 6 7 8 11 123 41 2
L1
N
K1
K2
+24 V DC
k1k1
k2k2
Input BCU/IFD
STW/
STB
3.15AT
F = I
N
× 0.6
BCU with power supply for valves and
ignition transformer via safety interlocks
(terminal 5)
N
2.5 A
N N
N
230 V AC
BCU 4xx
F1
1 2
PE
7 8 119 10 12 13 14 15
24 25 26 2718 19 20
5
50 5130 31 32 33 34 35 36 37 38
6
23
22
21
3 4
1
6
17
28
29
max. 2 A
253 V
max. 2 A
253 V
F3
V1
L1
I
Z
V2
In the event that a higher output current is re-
quired, the output current can be increased by
means of a contact multiplier using three contac-
tors. Design the circuit as follows:
61 62
FCU 500
A
STW/
STB
+ - + -
+24 V
41 42 44 45
65
46
66
47
48
68
53 54 55 56 5749 50 51 52
ϑ
67
13 14 15 16 17
5 6 7 8
11 12
3 41 2
L1
N
K1
K2
K3
k3 k1
k2
k1
k3
k2
Input BCU
Terminal 5
Input BCU
Terminal 22
P
STW/
STB
F = I
N
× 0.6
GB-6
D
GB
F
NL
I
E
Connection diagram
FCU 500
Legend– see page24 (Legend).
61 62
FCU 500
5AT
FS
A
L1
+24 V
V1
V2
V3
41 42 44 45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
ϑ
N
0 V
p
u
2
1
4
p
u
PZL
PZH
LDS
HT
P
90°
90°
PZL
PZ
PDZ
+24 V DC
K2 K1
k11
k21
M
67
13 14 15 16 17 1811 123 41 2
+ - + -
5 6 7 8
P69
P72
P70
P71 P73
Output
Air
min
Air
STM/
STL
Gas
min
3.15AT
0.6 x I
N
I
N
× 0.6
Gas
max
GB-7
D
GB
F
NL
I
E
FCU 505
Legend – see page 24 (Legend).
61 62
FCU 505
5AT
FS
A
L1
+24 V
V1
V2
V3
41 42 44 45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
N
0 V
p
u
2
1
4
p
u
PZL
PZH
LDS
HT
P
90°
90°
PZL
PZ
PDZ
+24 V DC
K2 K1
k11
k21
M
67
13 14 15 16 17 1811 123 41 2
+ - + -
5 6 7 8
P69
P72
P70
P71 P73
Output
Air
min
Air
STM/
STL
Gas
min
Gas
max
3.15AT
I
N
× 0.6
0.6 x I
N
GB-8
D
GB
F
NL
I
E
IC 0 connected to FCU..F
Parameter 40 = 1.
Continuous control via three-point step controller.
61 62
FCU 500
5AT
FS
A
L1
+24 V
V1
V2
V3
41 42 44 45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
ϑ
LDS
HT
P
90°
90°
67
13 14 15 16 17 1811 12
3 41 2
PE
L1
N
3 2 116 67 4812 1115 13
S3 S4
S11
S10
90°
M
IC 20
PE
S1S2
90°
90°
STW/
STB
+ - + -
5
6 7 8
3.15AT
Output
GB-9
D
GB
F
NL
I
E
IC 0 E connected to FCU..F
Parameter 40 = 1.
Continuous control via analogue input.
61 62
FCU 500
5AT
FS
A
L1
+24 V
V1
V2
V3
41 42 44 45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
ϑ
LDS
HT
P
90°
90°
67
13 14 15 16 17 1811 12
3 41 2
20 19 18 3 2 167 4812 11
S3
S4
S1 0
OUT
90°
90°
90°
IC 20..E
S1
S2
517
+ +
IN
OK
R
R
PE
A
D
A
D
R
1 2 3 4 5 6
ON
µC
131516
M
PE
L1
N
STW/
STB
+ - + -
5
6 7 8
3.15AT
GB-10
D
GB
F
NL
I
E
IC 40 connected to FCU..F
Parameter 40 = 2.
Continuous control via analogue input.
Set IC 40 to operating mode 27, see operating
instructions Actuators IC 20, IC 40, IC 40S.
61 62
FCU 500
5AT
FS
A
L1
+24 V
V1
V2
V3
41 42 44 45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
ϑ
LDS
HT
P
90°
90°
67
13 14 15 16 17 1811 12
3 41 2
IC 40
PE
19 18 16 15 14 12 11 10 8 7 5 4 2 1
A
AC
D
DC
M
mA
L
N
22 21 20
R..
STW/
STB
+ - + -
5 6
7 8
3.15AT
GB-11
D
GB
F
NL
I
E
RBW valve connected to FCU..F
Parameter 40 = 3.
Continuous control via three-point step
controller
61 62
FCU 500
5AT
FS
A
L1
+24 V
V1
V2
V3
41 42 44
45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
ϑ
LDS
HT
P
67
13 14 15 16 17 1811 12
3 41 2
N
M
R B W
90°
90°
L1
RBW
COM
HI
LO
AUTO
STW/
STB
+ - + -
5 6 7 8
Continuous control via analogue input
N
M
+ F -
90°
L1
mA
A
D
OUT
+
-
RBW
FCU 500
5AT
45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
67
13 14 15 16 17 1811 12
COM
HI
LO
AUTO
5 6 7 8
PLC
GB-12
D
GB
F
NL
I
E
Frequency converter connected to FCU..F
Parameter 40 = 4.
Continuous control via speed-controlled fan.
61 62
FCU 500
5AT
FS
A
L1
+24 V
V1
V2
V3
41 42 44
45
65
46
66
47 48
68
53 54 55 56 57 5849 50 51 52
ϑ
LDS
HT
P
67
13 14 15 16 17 1811 12
3 41 2
mA
PDZ
M
L1
DI 3DI 2DI 1
P
0–100%
COM
HI
LO
AUTO
+ - + -
5 6 7 8
PLC
Target = actual
STW/
STB
FC
GB-13
D
GB
F
NL
I
E
Adjustment
In certain cases, it may be necessary to change the
parameters set at the factory. Using the separate
software package BCSoft and a PC opto-adapter, it
is possible to modify parameters on the FCU, such
as the pre-purge time or the behaviour in the event
of a flame failure.
The software package and the opto-adapter
are available as accessories– see page25
(Accessories).
Changed parameters are saved on the integrated
parameter chip card.
The factory settings are secured with a program-
mable password.
If the password has been changed, the end cus-
tomer can look up the changed password in the
plant documentation or ask the system supplier.
Commissioning
During operation, the 7-segment display shows
the program status:
––
Device Off
00
Start-up position/standby
H0
Switch-on delay/min. pause time
H1
Waiting for purge signal from furnace FCU
H2
Waiting for start enable
A
Approaching minimum capacity
0
“No flow” state check on fan
01
Fan run-up time t
GV
A
Approaching maximum capacity
1
Air pressure cut-out check
P1
Pre-purge
A
Approaching ignition capacity
Valve check
H7
Controller enable switch-on delay
H8
Waiting for burner operating signal
08
Operation/controller enable
P9
Post-purge
C1
Controlled air flow
U I
Remote control (with OCU)
Data transfer (programming mode)
X.X.
High temperature mode
0.0.
(blinking dots) Manual mode
WARNING
Risk of explosion! Check the system for tightness
before commissioning.
Do not start the FCU until you are certain that the
wiring is correct, the parameters have been set
correctly and all input and output signals are be-
ing processed perfectly by means of conducting
a function check and reading the parameters on
the device.
Switch on the system.
The display indicates
––
.
Switch on the FCU by pressing the On/Off button.
The display indicates
00
.
If the display blinks (fault), reset the FCU by press-
ing the Reset/Information button, see also page
15 (Assistance in the event of malfunction).
Apply the start-up signal to terminal1.
The display indicates
H0
.
The safety interlocks
are checked during the switch-on delay time/
min. pause time.
The display indicates
01
. The fan starts.
The display indicates
1
. The air deficiency cut-
out check starts.
The display indicates
P1
. Pre-purge starts.
FCU..C1: the valve check runs in parallel to pre-
purge. If the valve check lasts longer than pre-
purge, the display indicates
.
GB-14
D
GB
F
NL
I
E
The display indicates
H7
. After pre-purge (and the
end of the valve check on FCU..C1), the valves
in the gas inlet section are opened.
The display indicates
08
. The FCU issues the
enable signal to the burner control units to start
the burners.
High temperature operation
The FCU..H1 is fitted with an integrated temperature
module for high temperature operation. As soon as
the FCU has received the signal from the connected
double thermocouples that the temperature defined
in parameter24 has been reached, a signal is sent
to the high temperature inputs of the burner control
units by the output at terminal 18. If voltage is applied
to the high temperature inputs, the burner flames will
no longer be monitored by the burner control units.
WARNING
Risk of explosion! High temperature operation is
only permitted if the temperature in the furnace
chamber is so high that the gas/air mixture is reli-
ably combusted.
In countries where EN746/NFPA86 is applicable,
if the furnace wall temperature is greater than or
equal to 750°C (1400°F), the flame may be moni-
tored by a fail-safe temperature monitoring device
that complies with the standard.
Only if the temperature is greater than or equal
to 750°C (1400°F) may voltage be applied to the
high temperature inputs of the burner control units.
Comply with the local safety regulations.
In high temperature mode, the two dots in the
display are lit permanently.
The flame control system is placed out of op-
eration.
Once the furnace temperature falls below the
value defined in parameter24, terminal18 is
isolated from the voltage supply. The burner con-
trol units continue operating with flame control,
depending on their setting.
Manual mode
For adjustment of the furnace system or for
fault-finding.
In Manual mode, the FCU operates indepen-
dently of the status of the inputs for start-up
signal (terminal1), controlled air flow (terminal2)
and remote reset (terminal3). The function of the
controller enable/emergency stop input (termi-
nal46) is retained.
Manual mode is terminated by switching off the
FCU or in the event of a power failure.
Parameter 67 = 0: Manual mode unlimited in
time. The furnace may continue to be operated
manually in the event of failure of the control
system or the bus.
Parameter 67 = 1: The FCU will terminate Manual
mode 5minutes after the last time the Reset/
Information button is pressed. It switches to the
start-up position/standby(display
00
).
Switch on the FCU while holding the Reset/In-
formation button. Hold the Reset/Information
button until the two dots in the display start to
blink.
If the Reset/Information button is pressed, the
current step in Manual mode is shown. After
the button has been held for 1 second, the next
step will be shown. The FCU now executes its
program sequence until the display indicates
08
.
FCU..F with IC 0
Following controller enable (display
0.8.
), actuator
IC20 can be opened and closed as required.
Press the Reset/Information button.
If the button continues to be held down, the
actuator opens further until maximum capacity
has been reached.
The display indicates
A.1.
with blinking dots.
Once the button has been released, the butterfly
valve stops in the relevant position.
Press the Reset/Information button again.
If the button continues to be held down, the
actuator closes further until minimum capacity
has been reached.
The display indicates
A.0.
with blinking dots.
A change of direction takes place each time the
button is released and pressed again. When the
butterfly valve has reached its final position, the
dots disappear.
FCU 500..F with IC40, FCU500..F with
RBW or frequency converter
Following controller enable (status display
0.8.
), it
is possible to approach binary positions between
minimum and maximum capacity.
GB-15
D
GB
F
NL
I
E
Assistance in the event of
malfunction
DANGER
Electric shocks can be fatal! Before working on
possible live components, ensure the unit is discon-
nected from the power supply.
Fault-clearance must only be undertaken by author-
ized trained personnel.
Faults may be cleared only using the measures
described below.
If the FCU does not respond even though all
faults have been remedied: remove the unit and
return it to the manufacturer for inspection.
? Faults
! Cause
Remedy
? The 7-segment display does not light up.
! Mains voltage is not applied.
Check the wiring, apply mains voltage (see type
label).
1 0
? The display blinks and indicates
10
.
! Actuation of the remote reset input is faulty.
! Too many remote resets. More than 5× resets
have been conducted within the last 15minutes,
either automatically or manually.
! Consecutive fault caused by a previous fault
whose actual cause has not been remedied.
Pay attention to previous fault messages.
Remedy cause.
The cause will not be remedied by performing a
reset every time a fault lock-out occurs.
Check whether remote reset complies with
standards (EN746 allows resetting only under
supervision) and correct if necessary.
The FCU may only be reset manually under su-
pervision.
Press the Reset/Information button on the FCU.
2 0
? The display blinks and indicates
20
.
! Voltage is applied to the output at terminal 56.
Check the wiring and ensure that the voltage
outputs and inputs have the same polarity and
are not reversed.
! The unit has suffered an internal fault in the power
module.
Replace the power module.
2 1
? The display blinks and indicates
21
.
! Inputs 51 and 52 are activated simultaneously.
Check input 51.
Input 51 may only be activated if the valve is
open.
Check input 52.
Input 52 may only be activated if the valve is in
the ignition position.
2 2
? The display blinks and indicates
22
.
! Valve IC 20 has been wired incorrectly.
Check the wiring. Wire the outputs and inputs
of connection terminals 52–55 as shown in
the connection diagram – see page 8 (IC
20 connected to FCU..F1).
! The unit has suffered an internal fault in the power
module.
Replace the power module.
2 3
? The display blinks and indicates
23
.
! The valve position is not constantly signalled
back to theFCU.
Check the wiring and ensure that the open/igni-
tion position of the valve is constantly signalled
back via terminal52.
2 4
? The display blinks and indicates
24
.
! Faulty activation via the bus. Requirements for
“Open” and “Close” set simultaneously.
Ensure that “Open” and “Close” are not activated
simultaneously.
3 0
? The display blinks and indicates
30
.
! Abnormal data change in the parameters set for
theFCU.
Reset the parameters to their original values using
the BCSoft software.
Establish the cause of the fault to avoid repeat
faults.
Ensure that the cables have been installed prop-
erly– see page3 (Cable selection).
GB-16
D
GB
F
NL
I
E
If the measures described above do not help,
remove the unit and return it to the manufacturer
for inspection.
3 1
? The display blinks and indicates
31
.
! Abnormal data change in the parameters set for
theFCU.
Reset the parameters to their original values using
the BCSoft software.
Establish the cause of the fault to avoid repeat faults.
Ensure that the cables have been installed prop-
erly– see page3 (Cable selection).
If the measures described above do not help,
remove the unit and return it to the manufacturer
for inspection.
3 2
? The display blinks and indicates
32
.
! Supply voltage too low.
Operate the FCU in the specified mains voltage
range (mains voltage +10/-15%, 50/60Hz).
! The unit has suffered an internal fault.
Remove the unit and return it to the manufacturer
for inspection.
3 3
? The display blinks and indicates
33
.
! Faulty parameterization.
Check parameter settings using BCSoft.
! The unit has suffered an internal fault.
Remove the unit and return it to the manufacturer
for inspection.
3 6
? The display blinks and indicates
36
.
! The unit has suffered an internal fault.
Remove the unit and return it to the manufacturer
for inspection.
3 7
? The display blinks and indicates
37
.
! Faulty feedback from contactors.
Check voltage supply to terminal 68 – see
page 5 (Safety interlock output in the case
of higher power requirement).
Check the setting of parameter73.
3 8
? The display blinks and indicates
38
.
! Interruption of signal at the “Fan feedback” input
(terminal44).
Check voltage supply to terminal44.
Check the setting of parameter31.
4 0
? The display blinks and indicates
40
.
! The gas solenoid valve V1 is leaking.
Check the gas solenoid valve V1.
! The gas pressure switch DGp
u
/2 (DGp
u
¾) for
the tightness test has been set incorrectly.
Check the inlet pressure.
Set DGp
u
/2 (DGp
u
¾) to the correct inlet pressure.
Check the wiring.
! The test pressure between V1 andV2 has not
decreased.
Check the installation.
! The test period is too long.
Change parameter56 (Measurement time) using
BCSoft.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
4 1
? The display blinks and indicates
41
.
! The gas solenoid valve V2 or V3 is leaking.
Check the gas solenoid valves V2/V3.
! The gas pressure switch DGp
u
/2 (DGp
u
¾) for
the tightness test has been set incorrectly.
Check the inlet pressure.
Set DGp
u
/2 (DGp
u
¾) to the correct inlet pressure.
Check the wiring.
! The test period is too long.
Change parameter56 (Measurement time) using
BCSoft.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
4 2
? The display blinks and indicates
42
.
! Test volume V
p2
is leaking.
! The gas solenoid valve V3, one of the burner-side
valves or the pipework is leaking.
Check the gas solenoid valves and pipework.
GB-17
D
GB
F
NL
I
E
! The gas pressure switch DGp
u
/2 (DGp
u
¾) has
been set incorrectly.
Check the inlet pressure.
Set DGp
u
/2 (DGp
u
¾) to the correct inlet pressure.
Check voltage supply to terminal 45 (65).
! The set test period V
p1
+V
p2
is too long.
Change the test period using parameter57.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
4 4
? The display blinks and indicates
44
.
! The FCU could not supply one of the test vol-
umes (V
p1
orV
p2
).
! The FCU could not reduce the pressure of V
p1
orV
p2
.
Faulty wiring of the activated valves.
Check valve actuation.
Faulty wiring of the pressure switches.
Check voltage supply to terminal 46 (65).
4 5
? The display blinks and indicates
45
.
! Faulty valve actuation.
! Reversed valve connection.
Check the wiring of the valves.
5 0
? The display blinks and indicates
50
.
! Interruption of signal at the “Enable/Emergency
stop” input (terminal46).
Check voltage supply to terminal46.
Check the setting of parameter10.
5 1
? The display blinks and indicates
51
.
! Short-circuit on one of the outputs of the safety
circuit.
Check the wiring.
Check fine-wire fuseF1 (3.15A, slow-acting,H).
The fine-wire fuse can be replaced once the
power module has been removed, see also
page 21 (Replacing the fuse)
Then check the faultless processing of all input
and output signals.
! The unit has suffered an internal fault in the power
module.
Replace the power module.
5 2
? The display blinks and indicates
52
.
! The FCU is being permanently reset.
Check voltage supply to terminal3.
Apply voltage to terminal3 only for reset, approx.
1second.
6 0
? The display blinks and indicates
60
.
! The safety temperature limiter (STL) has detected
an overtemperature condition.
Check the temperature control.
Check the wiring of terminals 5, 6, 7 and8.
! The double thermocouple is defective.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer
for inspection.
6 2
? The display blinks and indicates
62
.
! A cable discontinuity has been detected in the
thermocouple at terminals 5 and 6.
Check the wiring of terminals 5 and6.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer
for inspection.
6 3
? The display blinks and indicates
63
.
! A cable discontinuity has been detected in the
thermocouple at terminals 7 and 8.
Check the wiring of terminals 7 and8.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer
for inspection.
GB-18
D
GB
F
NL
I
E
6 4
? The display blinks and indicates
64
.
! A malfunction (sensor short-circuit) has been de-
tected in the thermocouple at terminals 5 and6.
Check the wiring of terminals 5 and 6.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer
for inspection.
6 5
? The display blinks and indicates
65
.
! A malfunction (sensor short-circuit) has been de-
tected in the thermocouple at terminals 7 and8.
Check the wiring of terminals 7 and 8.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer
for inspection.
6 6
? The display blinks and indicates
66
.
! Limit value of the temperature difference set via
Parameter 23 between the thermocouples at
terminals 5 and 6, and terminals 7 and 8 has
been exceeded.
Check parameter 23 and adjust correctly.
Replace the double thermocouple.
If the fault cannot be remedied by doing this,
remove the FCU and return it to the manufacturer
for inspection.
6 7
? The display blinks and indicates
67
.
! The thermocouples are being operated outside
of the allowed temperature range.
Use type K NiCr-Ni, type N NiCrSi-NiSi or typeS
Pt10Rh-Pt Class 1 double thermocouples:
Thermocouple Temperature range (°C)
Typ K NiCr-Ni -40 to 1000
Typ N NiCrSi-NiSi -40 to 1000
Typ S Pt10Rh-Pt 0 to 1600
7 0
? The display blinks and indicates
70
.
! The connected burner control units have not
signalled “Operating position reached (burner
started)” within the time defined by parameter47.
Check voltage supply to “Operating signal” input
(terminal4).
Check the setting of parameter47.
7 2
? The display blinks and indicates
72
.
! The connected burner control units are not ready
for operation.
Check voltage supply to terminal67.
Check the setting of parameter72.
8 9
9 4 9 5 9 6
9 7
9 8 9 9
? The display blinks and indicates
89
,
94
,
95
,
96
,
97
,
98
or
99
.
! System fault– the FCU has performed a safety
shut-down. The cause may be a unit defect or
abnormal EMC influence.
Ensure that the ignition cable has been installed
properly– see page3 (Cable selection).
Ensure that the EMC regulations for the sys-
tem are satisfied– particularly for systems with
frequency converters – see page 3 (Cable
selection).
Reset the unit.
Disconnect the protective system control from
the mains supply and then switch it on again.
Check mains voltage and frequency.
If the measures described above do not help, the
unit has probably suffered a hardware defect–
remove the unit and return it to the manufacturer
for inspection.
GB-19
D
GB
F
NL
I
E
0
? The display blinks and indicates
0
.
! The “no flow” state check of the air pressure
switch has failed.
Check the function of the air pressure switch.
Before the fan is switched on, there must be no
high signal at the input for air monitoring (termi-
nal47) when air monitoring is activated.
1
? The display blinks and indicates
1
.
! The operating check of the air pressure switch
has failed. The air monitor has not switched after
fan start-up.
Check the air monitor wiring.
Check the air pressure switch setpoint.
Check the function of the fan.
P
? The display blinks and indicates
P
.
! The input signal (terminal48) for the air pressure
switch has dropped out during pre-purge.
Check the air supply during the purging process.
Check the electrical wiring of the air pressure
switch.
Check voltage supply to terminal48.
Check the air pressure switch setpoint.
1 0
? The display blinks and indicates
X
.
! The input signal for the air pressure switch has
dropped out during start-up/operation at position
stepX.
! Failure of the air supply at position stepX.
Check the air supply.
Check the air pressure switch setpoint.
X
? The display blinks and indicates
X
.
! The signal for monitoring the max. gas pressure
(terminal50) has dropped out at position stepX.
Check the wiring.
Check the gas pressure.
X
? The display blinks and indicates
X
.
! The signal for monitoring the min. gas pressure
(terminal49) has dropped out at position stepX.
Check the wiring.
Check the gas pressure.
A
? The display blinks and indicates
A
.
! No “Closed” signal from actuator.
Check the butterfly valve for air and the function
of the limit switches in the actuator.
Check the wiring.
Check the actuator.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
A
? The display blinks and indicates
A
.
! No “Open” signal from actuator.
Check the butterfly valve for air and the function
of the limit switches in the actuator.
Check the wiring.
Check the actuator.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
GB-20
D
GB
F
NL
I
E
A
? The display blinks and indicates
A
.
! No “Ignition position” signal from actuator.
Check the butterfly valve for air and the function
of the limit switches in the actuator.
Check the wiring.
Check the actuator.
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
E
? The display blinks and indicates
E
.
! Internal communication with bus module has
suffered a fault.
Connected control elements must be equipped
with protective circuits in accordance with the
manufacturer’s instructions.
This prevents high voltage peaks which can
cause malfunctioning of the FCU.
Use suppressed electrode adapters (1 kΩ).
If the fault cannot be remedied by doing this,
remove the unit and return it to the manufacturer
for inspection.
! The bus module is defective.
Replace the bus module.
? The display blinks and indicates
.
! Incorrect or defective parameter chip card (PCC).
Only the parameter chip card provided is to be
used.
Replace defective parameter chip card.
1
? The display blinks and indicates
1
.
! No input signal for the proof of closure switch
during standby.
Check the wiring.
Mains voltage must be supplied to the FCU if the
valve is closed and no voltage is to be applied
if the valve is open.
Check that the proof of closure switch and valve
function perfectly, replace defective valves.
8
? The display blinks and indicates
8
.
! The FCU is receiving no information as to whether
the POC switch contact is still open.
Check the wiring.
During start-up, mains voltage must be supplied
to the FCU if the valve is closed and no voltage
is to be applied if the valve is open.
Check that the proof of closure switch and valve
function perfectly, replace defective valves.
0
? The display blinks and indicates
0
.
! BCU waiting for connection to PLC.
Check whether the PLC is switched on.
Check the network wiring.
Check the PLC programming.
Check whether the correct device name and
IPaddress for the FCU have been entered in
the PLCprogram.
1
? The display blinks and indicates
1
.
! An invalid address has been set on the bus mod-
ule.
Adapt the bus module’s address with the code
switches to the address allocated in the PLCpro-
gram.
Check whether the bus module’s address is in
the permitted address range (001toFEF).
2
? The display blinks and indicates
2
.
! The bus module has received an incorrect con-
figuration from thePLC.
Check whether the correct GSD file was imported
into the PLC.
3
? The display blinks and indicates
3
.
! The device name for the FCU is invalid in the
PLC program.
Device name on delivery:
not-assigned-fcu-500-xxx
(xxx = code switch setting on the FCU).
The device name must at least consist of the
expression fcu-500-xxx.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26

Krom Schroder FCU 500 Operating Instructions Manual

Type
Operating Instructions Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI