XIII Troubleshooting
Thefollowingpagescontaintroubleshootingchartsforuseindiagnosingcontrolproblems.Tousethesecharts,goto
theboxmarked“Start”atthetopofthechartonpage34or36andfollowtheappropriatepaththoughthechartuntila
boxwithalistofpossiblecausesisreached.Iftheproblemisknowntobewithintheignitionsystem,godirectlytothe
appropriatetroubleshootingguidefortheboiler.Inusingthesecharts,thefollowingshouldbekeptinmind:
1) Thesechartsareonlymeanttobeusedbyaprofessionalheatingtechnicianasanaidindiagnosingcontrolprob-
lems.
2) Whereapplicable,followallprecautionsoutlinedintheappropriatelightinginstructionsonpages28-29.
3) Ingeneral,thesechartsassumethattherearenolooseormiswiredelectricalconnections.Beforeusingthese
charts,inspectallelectricalconnectionsontheboilertomakesurethattheyaretight.Also,checkthewiringonthe
boileragainsttheappropriatewiringdiagraminFigures18-19.
4) Thepossiblecausesattheendofeachbranchinthesechartsarenotlistedinorderoflikelihood.Allcontrolson
theCWIaretestedatleastonceinthemanufacturingprocessandadefectivecontrolorcomponentisgenerallythe
leastlikelycause.Beforereplacingacomponent,trytoruleoutallotherpossiblecauses.
5) Thesetroubleshootingchartsassumethattheventdamperisclosedatthebeginningofthetroubleshootingprocess.
Withthe120voltsappliedtotheboilerandnocallforheat,thedampershouldgototheclosedposition.Ifitdoes
not,dothefollowing:
• Conrmthat120voltsisappliedtotheboilerandthatthereisnocallforheat.
• Makesurethattheswitchonthedamperisinthe“automatic”position.
• Unplugtheharnessfromthedamperandcheckfor24voltsacrosspin#1(blue)andpin#4(yellow).
• Ifvoltageispresent,thedamperisdefectiveorthereisanobstructioninthepathofthedamperblade.
• Ifnovoltageispresent,thereiseitheralooseconnectioninthedamperharnessorthelimitcontrol(L8148E
orL8124E)isdefective.
6) IfthechartsindicatethattheL8148EorL8124Eisdefective,dothefollowingbeforereplacingit:
• Checkfor24voltsacrossTVandZ.Ifnovoltageispresent,thetransformerintheL8148EorL8124Eis
defective.Itispossiblethatthistransformerhasbeendestroyedbyashortcircuitintheboilerwiring.Before
replacingthecontrol,carefullyinspectalllowvoltagewiringontheboilerforplaceswhereitistouchingthe
frameoftheboilerorwiringontheothersideofthetransformer.
• If24voltsispresentacrossTVandZ,checkfor24voltsbetweenTandW.OnL8148Es,ifnovoltageis
present,makesurethatthebrassjumperispresentbetweenWandZandthatthescrewsholdingthisjumper
inplacearebothtight.IftheboilerisequippedwithaL8124E,voltagewillonlybepresentacrossTandW
whenthereisacallforheatANDtheboilerwatertemperaturehighenoughtosatisfythelowlimit.
• Ifnotalreadydone,temporarilyreplacethethermostatacrossTVandTwithajumper.Iftheboilerreswhen
thisisdone,thereisaproblemwiththethermostatorzonewiring.
• If24voltsispresentacrossTandWandtherelayintheL8148EorL8124Edoesnotpullin,therelayinthis
controlisprobablydefective.Inspectthecoilofthisrelayforvisibleheatdamage.Ifsuchdamageisfound,
thereisagoodchancethatasecondtransformerispresentinthethermostatorzonevalvecircuit,resultingin
theapplicationof48voltsacrosstherelaycoil.Inolderbuildings,thistransformermaybehiddeninaloca-
tionfarfromtheboiler.Ifthissecondtransformerexists,itmustbefoundandremovedbeforetheL8148Eor
L8124Eisreplaced.
7)Whencheckingvoltageacrossdamperharnesspins,becarefulnottoinsertthemeterprobesintothepins.Doingso
maydamagethepin,resultinginalooseconnectionwhentheharnessisreconnected.