IQ 100 Series (130/140/150) Meter
Overview &Specifications
14 User and Installation Manual IM02601003E-July 2010 www.eaton.com
Utility Peak Demand (IQ140/150)
The IQ 100 Series meter provides user-congured Fixed Window or Sliding Window Demand. This
feature allows you to set up a Customized Demand Prole. Fixed Window Demand is demand used over
a user-congured demand period (usually 5, 15 or 30 minutes). Sliding Window Demand is a xed
window demand that moves for a user-specied subinterval period. An example of Sliding Window De-
mand is a 15-minute demand using 3 subintervals and providing a new demand reading every 5 minutes,
based on the last 15 minutes.
Utility Demand Features can be used to calculate kW, kVAR, kVA and PF readings. All other parameters
offer Max and Min capability over the user-selectable averaging period. Voltage provides an Instanta-
neous Max and Min reading which displays the highest surge and lowest sag seen by the meter.
Specications
Power Supply
· Range: 1 Option: Universal, (90 to 265) VAC @50/60Hz or (100 to
370) VDC
4 Option: (18-60) VDC
· Power Consumption: 5 VA, 3.5W
Voltage Inputs (Measurement Category III)
· Range: Universal, Auto-ranging up to 416Vac L-N, 721Vac L-L
· Supported hookups: 3 Element Wye, 2.5 Element Wye, 2 Element Delta, 4 Wire
Delta
· Input Impedance: 1M Ohm/Phase
· Burden: 0.0144VA/Phase at 120 Volts
· Pickup Voltage: 10Vac
· Connection: Screw terminal (Figure 3.4)
· Max Input Wire Gauge: AWG#12 / 2.5mm2
· Fault Withstand: Meets IEEE C37.90.1
· Reading: Programmable Full Scale to any PT Ratio
Current Inputs
· Class 10: 5A Nominal, 10A Maximum
· Class 2: 1A Nominal, 2A Maximum
· Burden: 0.005VA Per Phase Max at 11 Amps
· Pickup Current: 0.1% of Nominal
· Connections: O or U Lug Electrical Connection (Figure 3.1)
Pass-through Wire, 0.177” / 4.5mm Maximum Diameter
(Figure 3.2)
Quick Connect, 0.25” Male Tab (Figure 3.3)
· Fault Withstand: 100A/10sec., 300A/3sec ., 500A/1sec.
· Reading: Programmable Full Scale to any CT Ratio