Specifications
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120VAC, 60Hz
Operating Temperature . . . . . . . . .32°F to 104°F (0°C to 40°C)
Patents pending
Syracuse, NY 13221-4822
800.223.4185
www.passandseymour.com
UNIT DESCRIPTION
The LightSense™ PSHC Multilocation Controller is used in circuits with the
LightSense multilocation universal or multilocation incandescent dimmer to
control lighting loads from multiple locations.
Load Types
The PSHC has no direct connection to the load. See the installation instructions
or specifications for the PSHDI Incandescent Dimmer, or the PSHDU Universal
Dimmer to determine compatibility with those devices.
INSTALL IN COMPLIANCE WITH ALL APPLICABLE CODES AND
STANDARDS. Failure to follow these instructions may cause
personal injury or equipment damage.
Call 800.223.4185 for Technical Support
Visit our website for FAQs: www.passandseymour.com
INSTALLATION
For ease of installation, Pass & Seymour/Legrand recommends use of a deep
wall box.
DO NOT WIRE WITH CONVENTIONAL SWITCHES AS
PART OF a 3-WAY or 4-WAY SWITCHING CIRCUIT.
The dimmer may be in any position in the circuit. Use a 3-wire and ground
cable to wire between devices. (In existing 3-way switched installations this
wire is already in place.) The PSHC requires a ground. Be sure to verify the
ground connection.
1. Disconnect power to circuit by turning circuit breaker OFF before installation.
2. Remove existing wall plate and switch.
3. Strip existing wires
1
/
2
"
. If two wires will be connected to the same terminal
on a LightSense™ device, both wires must be the same gauge (12AWG or
14AWG).
4.
Select your application to continue…
PSHDU Universal Dimmer or
5. Install the PSHDU dimmer and the PSHC controller, following the wiring
diagram in Figure 1 for two locations, or Figure 2 for three or more locations.
PSHDI Incandescent Dimmer
5. Install the PSHDI dimmer and the PSHC controller, following the wiring
diagram in Figure 3 for two locations, or Figure 4 for three or more locations.
Finishing the installation
6. Attach the wall plate.
7. Switch the circuit breaker ON.
8. Make sure the LED on the dimmer is lit. There is no LED on the PSHC
controller.
CAUTION
TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING THE DIMMER.
Call 800.223.4185 for Technical Support
Figure 1: Two location wiring with a PSHDU Universal Dimmer
Figure 2: Wiring for 3 or more locations with a PSHDU Universal Dimmer
Visit our website for FAQs: www.passandseymour.com
Figure 3: Two location wiring with the PSHDI Incandescent Dimmer.
Figure 4: Wiring for 3 or more locations with the PSHDI Incandescent Dimmer.
Call 800.223.4185 for Technical Support
Replacing Lamps
When a lamp must be replaced, use the Air Gap Isolation feature for safety.
This feature is only available at the dimmer, which can be identified by its status
LED. (The PSHC Multilocation Controllers do not have an LED and can not
operate this feature.)
Power Fail Memory
After a power failure, all LightSense™ devices automatically return to the state
they were in immediately prior to loss of power.
CLEANING
Clean using a cloth dampened only with water and a little mild detergent.
Use of solvents or hydrocarbon-based cleaners may cause permanent
damage.
When you
see in the
instructions,
touch the top
of the switch
as directed.
When you
see in the
instructions,
touch the
bottom of the
switch as
directed.
Tap once Fade the load to its last-used level
Tap twice Full bright
Press and hold Increase the present level
Tap once Fade the load to OFF
Press and hold Decrease the present level
OPERATION
TROUBLESHOOTING
In a multilocation circuit with one or more PSHC multilocation
controllers, the dimmer works, but the multilocation controllers
don’t function.
This condition would exist if the LINE and LOAD connections are
reversed. Check to make sure the connections are correctly terminated at
the dimmer.
The PSHC Multilocation Controllers require a ground connection. Check
to make sure the ground wires are securely connected.
The light level changes without pressing any switches, or the
dimmer does not respond when I press its switch.
There may be a problem with the traveler wire.
1. Remove power from the circuit.
2. Disconnect all traveler wires from the dimmer’s Remote terminals.
3. Restore power.
If the dimmer now operates the load properly, the problem is with the
traveler wire. It may be too long or it may be shorted to another
conductor.
LIMITED FIVE YEAR WARRANTY
Pass & Seymour will remedy any defect in workmanship or material in Pass & Seymour
products which may develop under proper and normal use within five years from date of
purchase by a consumer: (1) by repair or replacement, or, at Pass & Seymour’s option,
(2) by return of an amount equal to consumer’s purchase price. Such remedy is IN LIEU
OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES OF MERCHANTABILITY
OR FITNESS FOR A PARTICULAR PURPOSE. Such remedy by Pass & Seymour does
not include or cover cost of labor for removal or reinstallation of the product. ALL OTHER
FURTHER ELEMENTS OF DAMAGE (INCIDENTAL OR CONSEQUENTIAL DAMAGES)
FOR BREACH OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES INCLUDING
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE
ARE EXCLUDED HEREBY. (Some states do not allow disclaimers or exclusion or
limitation of incidental or consequential damages, so the above disclaimer and limitation
or exclusion may not apply to you.) ANY IMPLIED WARRANTIES INCLUDING WHERE
REQUIRED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE SHALL BE LIMITED TO THE FIVE YEAR PERIOD SET FORTH ABOVE.
(Some states do not allow limitations on how long an implied warranty lasts, so the above
limitation may not apply to you.) To ensure safety, all repairs to Pass & Seymour products
must be made by Pass & Seymour, or under its specific direction. Procedure to obtain
performance of any warranty obligation is as follows: (1) Contact Pass & Seymour,
Syracuse, New York 13221, for instructions concerning return or repair; (2) return the
product to Pass & Seymour, postage paid, with your name and address and a written
description of the installation or use of the Pass & Seymour product, and the observed
defects or failure to operate, or other claimed basis for dissatisfaction. This warranty gives
you specific legal rights and you may also have other rights which vary from state to state.
P.O. Box 4822 Syracuse, NY 13221-4822
Technical Support: 800.223.4185
www.passandseymour.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Legrand LightSense™ Multilocation Controller, PSHC Installation guide

Category
Dimmers
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI