Legrand LightSense™ Incandescent Dimmer, PSHDI Installation guide

Category
Dimmers
Type
Installation guide
PSHDI
LightSense
Incandescent Dimmer
Installation Instructions
Specifications
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120VAC, 60Hz
Operating Temperature . . . . . . . . .32°F to 104°F (0°C to 40°C)
Maximum Load Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . .600W
Minimum Load Required . . . . . . . . . . . . . . . . . . . . . . . . . . .40W
Load Type Compatibility . . . . . . . . . . . . . . . . . . . . . . . .40-600W
Incandescent (tungsten/quartz halogen) transformers
U.S. Patent 6,175,220. Other utility,
design, and foreign patents pending.
Syracuse, NY 13221-4822
800.223.4185
www.passandseymour.com
UNIT DESCRIPTION
The PSHDI incandescent dimmer controls incandescent or magnetic low
voltage lighting loads. Used in conjunction with LightSense™ PSHC
multilocation controllers, the PSHDI offers control of a dimming circuit from
multiple locations.
Load Types
Use the LightSense incandescent dimmer for these load types (40-600W at
120V):
Incandescent and quartz halogen lamps
Dimmable magnetic low voltage transformers (max load 500W)
Do not wire with conventional switches as part of a 3-way or 4-way
switching circuit.
Do not mix different load types on the same dimmer.
Do not use with diode equipped (some types of energy saving) lamps.
Do not use to control motors.
For dimmable, 2-wire fluorescent and compact fluorescent fixtures, electronic
low voltage, neon or cold cathode fixtures or diode equipped lamps, use the
LightSense PSHDU universal dimmer.
Derating
When
more than one dimmer
is installed in a multi-gang box, it is necessary to
reduce the maximum load on each dimmer:
For a dimmer in either end position of a multi-gang box, reduce its maximum
load to 500W.
For a dimmer in a central position of a multi-gang box, reduce its maximum
load to 400W.
Call 800.223.4185 for Technical Support
CAUTION
To reduce the risk of
overheating and possible
damage to other equipment, do
not install to control a receptacle,
a motor-operated appliance, or a
fluorescent lighting fixture.
CAUTION
Afin de réduire le risque de
surchauffe et la possibilité
d’endommager d’autres matériels,
ne pas installer pour commander
une prise, un appareil à moteur,
ou une lampe fluorescente.
Visit our website for FAQs: www.passandseymour.com
INSTALLATION
For ease of installation, Pass & Seymour/Legrand recommends use of a deep
wall box.
1. Disconnect power to circuit by turning circuit breaker OFF before installation.
2. Remove existing wall plate and switch.
3. Strip existing wires
1
/
2
"
. If two wires will be connected to the same terminal
on a LightSense™ device, both wires must be the same gauge (12AWG or
14AWG).
4. If NEUTRAL wires are provided to the fixture, connect them together using a
wire nut. The dimmer does not use a neutral connection.
Select your application to continue
Single Location
5. Wire the LINE (black), LOAD and GND supply wires to the correspondingly
marked screw terminals, according to Figure 1. Does not use a neutral
connection.
LOAD
LINE
GND
Wire Legend
Ground
Line
Neutral
Figure 1: Single location wiring
PSHDI
DIMMER
CAUTION
TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE
INSTALLING THE DIMMER.
Call 800.223.4185 for Technical Support
Figure 2: Two location wiring
Two Locations
Use with one LightSense™ PSHC multilocation controller.
5. Install the PSHDI dimmer and the PSHC controller, following the wiring
diagram in Figure 2. The dimmer can go in either location. Use a 3-wire and
ground cable to wire between devices. (In existing 3-way switched
installations this wire is already in place.) The PSHC requires a ground. Be
sure to verify the ground connection.
Visit our website for FAQs: www.passandseymour.com
Three or More Locations
Use with two or more LightSense PSHC multilocation controllers, for
multilocation control. DO NOT WIRE WITH CONVENTIONAL SWITCHES AS
PART OF a 3-WAY or 4-WAY SWITCHING CIRCUIT.
5. Install the PSHDI dimmer and the PSHC controllers, following the wiring
diagram in Figure 3. The dimmer may be in any position in the circuit. Use
a 3-wire and ground cable to wire between devices. (In existing 3-way
switched installations this wire is already in place.) Be sure to verify the
ground connection.
Finishing the installation
6. Attach the wall plate.
7. Switch the circuit breaker ON.
8. Make sure the LED on the PSHDI dimmer is lit. There is no LED on the
PSHC controller.
For ease of installation, Pass & Seymour/Legrand recommends use of a deep
wall box.
INSTALL IN COMPLIANCE WITH ALL APPLICABLE CODES AND
STANDARDS. Failure to follow these instructions may cause
personal injury or equipment damage.
GND
REMOTE
Load
Wires
Wire Legend
Traveler
Ground
Line
Neutral
GND
LOAD
LINE
GND
REMOTE
REMOTE
PSHC
Multilocation
Controller
PSHDI
DIMMER
Supply
Wires
Connect traveler wire (red) between the
REMOTE terminals on each device in the circuit.
12AWG
or
14AWG
between
LightSense
devices
PSHC
Multilocation
Controller
Figure 3: Wiring for 3 or more locations
Call 800.223.4185 for Technical Support
Note: The dimmer may feel warm to the touch during normal operation.
Replacing Lamps
When a lamp must be replaced, use the Air Gap Isolation feature for safety.
This feature is only available at the dimmer, which can be identified by its status
LED. (The remotes do not have an LED and can not operate this feature.)
To activate the feature from the dimmer:
Press FIRMLY, so that the paddle clicks and latches in. Make sure the
status LED is extinguished, indicating that it’s safe to relamp.
To release and return to normal operation, press .
Power Fail Memory
After a power failure, all LightSense™ devices automatically return to the state
they were in immediately prior to loss of power.
When you see
in the
instructions,
touch the top
of the switch
as directed.
When you see
in the
instructions,
touch the
bottom of the
switch as
directed.
Tap once Fade the circuit to its last-used level
Tap twice Full bright
Press and hold Increase the present level
Tap once Fade the circuit to OFF
Press and hold Decrease the present level
OPERATION
CLEANING
Clean using a cloth dampened only with water and a little mild detergent.
Use of solvents or hydrocarbon-based cleaners may cause permanent damage.
TROUBLESHOOTING
In a multilocation circuit with one or more multilocation
remotes, the dimmer works, but the multilocation remotes don’t
function.
This condition would exist if the LINE and LOAD connections are
reversed. Check to make sure the connections are correctly terminated at
the dimmer.
The remotes require a ground connection. Check to make sure the ground
wires are securely connected.
The Dimmer does not work and the status LED is flashing red
at 1Hz (5 times in 5 seconds):
The dimmer has detected an unsuitable load. Remove power, check the
load, restore power and try again.
at 2Hz (10 times in 5 seconds):
The dimmer has detected an overload condition and has shut down. Clear
the fault condition by returning the unit to OFF, disconnect loads in excess
of rated load and try again.
at 3Hz (15 times in 5 seconds):
The dimmer has detected a short-circuit condition and has shut down.
Remove power, rectify the short-circuit condition, restore power, and try
again.
LIMITED FIVE YEAR WARRANTY
Pass & Seymour will remedy any defect in workmanship or material in Pass & Seymour
products which may develop under proper and normal use within five years from date of
purchase by a consumer: (1) by repair or replacement, or, at Pass & Seymour’s option,
(2) by return of an amount equal to consumer’s purchase price. Such remedy is IN LIEU
OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES OF MERCHANTABILITY
OR FITNESS FOR A PARTICULAR PURPOSE. Such remedy by Pass & Seymour does
not include or cover cost of labor for removal or reinstallation of the product. ALL OTHER
FURTHER ELEMENTS OF DAMAGE (INCIDENTAL OR CONSEQUENTIAL DAMAGES)
FOR BREACH OF ANY AND ALL EXPRESSED OR IMPLIED WARRANTIES INCLUDING
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE
ARE EXCLUDED HEREBY. (Some states do not allow disclaimers or exclusion or
limitation of incidental or consequential damages, so the above disclaimer and limitation
or exclusion may not apply to you.) ANY IMPLIED WARRANTIES INCLUDING WHERE
REQUIRED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE SHALL BE LIMITED TO THE FIVE YEAR PERIOD SET FORTH ABOVE.
(Some states do not allow limitations on how long an implied warranty lasts, so the above
limitation may not apply to you.) To ensure safety, all repairs to Pass & Seymour products
must be made by Pass & Seymour, or under its specific direction. Procedure to obtain
performance of any warranty obligation is as follows: (1) Contact Pass & Seymour,
Syracuse, New York 13221, for instructions concerning return or repair; (2) return the
product to Pass & Seymour, postage paid, with your name and address and a written
description of the installation or use of the Pass & Seymour product, and the observed
defects or failure to operate, or other claimed basis for dissatisfaction. This warranty gives
you specific legal rights and you may also have other rights which vary from state to state.
P.O. Box 4822 Syracuse, NY 13221-4822
Technical Support: 800.223.4185
www.passandseymour.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Legrand LightSense™ Incandescent Dimmer, PSHDI Installation guide

Category
Dimmers
Type
Installation guide

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI