System design recommendations, continued
devices,and sight glasses must always be selected for the
particular refrigerant used.This is especially important in
installations using HFC refrigerants.Always refer to the
component manufacturer’s technical documentation.
When selecting a liquid line filter drier, take into account
the drier’s water content capacity, system cooling
capacity, and the refrigerant charge. Use a drier
containing 100 % molecular sieves (no activated alumina)
and that is oversized rather than undersized.
The upper limit of the application envelope for LTZ com-
pressors is at - 4°F evaporating temperature.
A MOP-type expansion valve or a crankcase pressure
regulator (Danfoss KVL) must be used to limit the suction
pressure to a maximum of 39 psig (5°F). Do not apply
both devices in combination.
A suction line heat exchanger is not recommended for
low temperature applications as it may cause high suction
gas superheat, which can result in a discharge temperature
that is too high.
Discharge line
In applications with the condenser mounted above the
compressor, a suitably sized U-trap may be necessary to
prevent oil return to the discharge side of the
compressor when the compressor is idle.The U-trap will
also help eliminate liquid refrigerant floodback from the
condenser to the compressor.
Oil charge and oil separator
In most installations the compressor’s initial factory oil
charge will be sufficient. If, however, there are line runs
exceeding 65 feet, many oil traps, or an oil separator,
additional oil may be needed.When an installation has
multiple evaporators, multiple condensers, or other
elements increasing the risk of slow oil return, an oil
separator is recommended. Find additional information
in the "Start up" section.
System components
System components such as filter driers, expansion
decreases.The lower pressure may be insufficient to sup-
ply enough liquid refrigerant to the evaporator. As a result,
the evaporating temperature
will greatly decrease, leading to low capacity,
and eventually to poor oil return. At start up,
the compressor will pull into a vacuum and will be cut out
by the low pressure protection. Depending on how the
low pressure switch and delay timer are set, short cycling
can occur.
To avoid these problems,use one of several solutions that
can reduce condenser capacity:
• Flood condensers with liquid. This solution requires
extra refrigerant charge, which can introduce other
problems. A non-return valve in the discharge line is
required, and special care should be taken when desi-
gning the discharge piping.
• Reduce air flow to the condenser.
• Install the condenser indoors.
When the compressor is located in an environment with
low ambient temperature,increased refrigerant migration
will occur when the compressor is not running. In such
conditions an extra belt-type crankcase heater is strongly
recommended. Note that with their 100% suction gas
cooled motors, Maneurop
®
compressors can be externally
insulated. Refer to the section titled "Liquid refrigerant
migration & charge limits" for more details.
High Pressure
A high pressure safety switch is required to stop the
compressor if discharge pressure exceeds the values
shown in the table below.
The high pressure switch can be set lower depending on
the application and ambient conditions, but to prevent
compressor cycling around the high pressure limit, the
switch must be either in a lockout circuit or have a
manual reset device.When a discharge valve is used, the
high pressure switch must be connected to the valve’s
service gauge port, which cannot be isolated.
Low pressure
To avoid compressor operation at suction pressures that
are too low,a low pressure safety switch is recommended.
Low ambient temperature operation
At low ambient temperatures, the condensing tempera-
ture and condensing pressure in air cooled condensers
OPERATING LIMITS
15
60 Hz catalog