Condair 2587517-B LINKS ProtoCarrier Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Condair 2587517-B LINKS ProtoCarrier Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Humidification and Evaporative Cooling
INSTALLATION AND
OPERATION MANUAL
ProtoCarrier FPC-C34 and
ProtoCarrier FPC-C35
Condair LINKS
2587517_B
_EN_1
810
For Interfacing Condair Products:
Nortec… GSTC, SETC, NHRS, NHTC
To Building Automation Systems:
BACnet MS/TP, BACnet/IP, Metasys N2 and LonWorks
Technical Support
Thank you for purchasing the ProtoCessor for Condair.
Please call Condair for Technical support of the ProtoCessor product.
Sierra Monitor Corporation does not provide direct support. If Condair needs to escalate the concern, they
will contact Sierra Monitor Corporation for assistance.
Support Contact Information:
U.S.A.
Condair Inc.
2700 90th Street
Sturtevant, WI 53177
USA
Canada
Condair Ltd.
2740 Fenton Rd
Ottawa, Ontario
K1T 3T7
Condair Service:
1.866.667.8321
Fax:
1.613.822.9764
Email: na.info@condair.com
Website: www.condair.com
APPLICABILITY & EFFECTIVITY
Explains ProtoCarrier FPC-C34 hardware and how to install it.
The instructions are effective for the above as of Oct 2018.
Document Revision: 2.G
Web Configurator
Template Revision: 60
INSTALLATION AND
OPERATION MANUAL
Condair LINKS
ProtoCarrier FPC-C34
and ProtoCarrier FPC-C35
2587517_B_EN_1810
Thank you for choosing Condair
Installation date (DD/MM/YYYY):
Commissioning date (DD/MM/YYYY):
Site:
Model:
Serial number:
Manufacturer
Condair Ltd.
2740 Fenton Road, Ottawa, ON, Canada K1T 3T7
Tel. 1.866.667.8321, Fax 613.822.7964
[email protected], www.condair.com
Proprietary Notice
This document and the information disclosed herein are proprietary data of Condair Ltd. Neither this docu-
ment, nor the information contained herein shall be reproduced, used, or disclosed to others without the
written authorization of Condair Ltd., except to the extent required for installation, operation or maintenance of
the customer's equipment.
Liability Notice
Condair Ltd. does not accept any liability due to incorrect installation, maintenance or operation of the
equipment, or due to the use of parts/components/equipment that are not authorized by Condair Ltd.
Copyright Notice
Copyright 2018, Condair Ltd, All rights reserved.
Technical modification rights reserved.
Condair LINKS 2587517_B_EN_1810 I V
Contents
1 Quick Start Guide ..................................................................................................... 7
2 Certifications ............................................................................................................. 8
3 Introduction ............................................................................................................... 9
3.1 ProtoCarrier Gateway ................................................................................................. 9
4 Setup for ProtoCarrier ..............................................................................................10
4.1 Record Identification Data ..........................................................................................10
4.2 Point Count Capacity and Registers per Device .........................................................10
4.3 Configuring Device Communications ..........................................................................10
4.3.1 Input COM Settings for Device with an Inserted ProtoCarrier ..................................10
4.3.2 Set Modbus RTU Node-ID for the Device ................................................................11
5 Interfacing ProtoCarrier to Devices .........................................................................12
5.1 ProtoCarrier FPC-C34 and FPC-C35 Showing Connection Ports ................................12
5.2 Device Connections to ProtoCarrier ............................................................................13
5.2.1 Biasing the Modbus RS-485 Device Network ..........................................................13
5.2.2 End of Line Termination Switch for the Modbus RS-485 Device Network ................14
5.3 BACnet MS/TP or Metasys N2: Wiring Field Port to RS-485 Network .........................15
5.4 LonWorks (FPC-C35): Wiring Field Port to LonWorks Network ...................................15
5.5 Power-Up ProtoCarrier ................................................................................................16
6 Use ProtoCarrier Web Configurator to Setup the Gateway ....................................17
6.1 Connect the PC to ProtoCarrier via the Ethernet Port ..................................................17
6.2 Connecting to ProtoCarrier Web Configurator .............................................................18
6.3 Selecting Profiles for Devices Connected to ProtoCarrier ............................................18
6.4 BACnet/IP: Setting IP Address for Field Network ........................................................20
6.5 Select Field Protocol ...................................................................................................22
6.5.1 BACnet MS/TP Configuration ..................................................................................22
6.5.2 BACnet/IP Configuration .........................................................................................23
6.5.3 Metasys N2 Configuration .......................................................................................24
7 BACnet MS/TP and BACnet/IP: Setting Node_Offset to Assign
Specific Device Instances ........................................................................................25
8 How to Start the Installation Over: Clearing Profiles .............................................26
9 LonWorks (FPC-C35): Commissioning ProtoCarrier on a lonworks Network ......27
9.1 Commissioning ProtoCarrier FPC-C35 on a LonWorks Network .................................27
9.1.1 Instructions to Download XIF File from ProtoCarrier FPC-C35 Using Browser ........27
A Troubleshooting .......................................................................................................... i
A.1 Lost or Incorrect IP Address ........................................................................................... i
A.2 Viewing Diagnostic information ..................................................................................... ii
A.3 Check Wiring and Settings ............................................................................................ ii
VI | 2587517_B_EN_1810 Condair LINKS
A.4 LED Diagnostics for Communications Between ProtoCarrier and Device ................... iii
A.5 Take Diagnostic Capture With the FieldServer Utilities ............................................... iv
A.6 Update Firmware ....................................................................................................... vii
A.7 BACnet: Setting Network_Number for more than one ProtoCarrier on Subnet .......... vii
A.8 Securing the ProtoCarrier with Passwords ............................................................... viii
B Vendor Information - Condair .................................................................................ix
B.1 GE_SE Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks .................... ix
B.2 MHTC Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ...................... x
B.3 NHRS Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ...................... x
B.4 NHTC Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks ...................... xi
C Reference ................................................................................................................. xiii
C.1 Specifications ............................................................................................................ xiii
C.1.1 Compliance with UL Regulations ......................................................................... xiii
Condair LINKS 2587517_B_EN_1810 I V
1
Condair LINKS 2587517_B_EN_1810 I 7
2 Quick Start Guide
1. Record the information about the unit. (Section 5.1)
2. Set the device’s Modbus RTU serial settings (i.e. baud rate, parity, stop bits) and
Modbus Node-ID’s for each device that will be connected to ProtoCarrier FPC-C34
or FPC-C35. (Section 5.3)
3. Metasys N2 (FPC-C34): Set the Node-ID. (Section 5.3.2)
4. BACnet MS/TP or BACnet/IP: Set the BACnet Device Instance. (Section 8)
5. Connect ProtoCarrier’s 6 pin RS-485 connector to the Modbus RS-485 network
that is connected to each of the devices. (Section 5.2)
6. Connect ProtoCarrier FPC-C34’s 3 pin RS-485 port to the Field Protocol
cabling, (Section 6.3) or connect ProtoCarrier FPC-C35’s 2 pin LonWorks port
to the Field Protocol cabling. (Section 6.4)
7. Connect Power to ProtoCarrier’s 6 pin connector. (Section 6.5)
8. Use a browser to access the ProtoCarrier’s embedded tool, which is referred to in
this manual as the Web Configurator, to select the devices that will be attached to
ProtoCarrier and set the Modbus Node-ID. Once the devices are selected, the
ProtoCarrier Automatically builds and loads the Configuration. (Section 7)
9. BACnet/IP (FPC-C34): Use a browser to access the ProtoCarrier Web
Configurator to change the IP Address. No changes to the configuration are
necessary. (Section 7.4)
10. LonWorks (FPC-C35): The ProtoCarrier must be commissioned on the LonWorks
Network. This needs to be done by the LonWorks administrator using a LonWorks
Commissioning tool. (Section 10)
8 I 2587517_B_EN_1810 Condair LINKS
3 Certifications
BTL MARK BACNET TESTING LABORATORY
LONMARK CERTIFICATION
The BTL Mark on ProtoCessor is a symbol that indicates that a
product has passed a series of rigorous tests conducted by an
independent laboratory which verifies that the product correctly
implements the BACnet features claimed in the listing. The mark is a
symbol of a high-quality BACnet product.
Go to http://www.BACnetInternational.net/btl/ for more information
about the BACnet Testing Laboratory. Click here for BACnet PIC
Statement.
LonMark International is the recognized authority for
certification, education, and promotion of interoperability
standards for the benefit of manufacturers, integrators and end
users. LonMark International has developed extensive product
certification standards and tests to provide the integrator and
user with confidence that products from multiple manufacturers
utilizing LonMark devices work together. Sierra Monitor has
more LonMark Certified gateways than any other gateway
manufacturer, including the ProtoCessor, ProtoCarrier and
ProtoCessor for OEM applications and the full featured,
configurable gateways.
Condair LINKS 2587517_B_EN_1810 I 9
4 Introduction
4.1 ProtoCarrier Gateway
ProtoCarrier is an external, high performance Building Automation multi-protocol gateway that is
preconfigured to automatically communicate between Condair’s products (hereafter called “device”)
connected to the ProtoCarrier and automatically configures them for BACnet® MS/TP, BACnet/IP,
Metasys® N2 by JCI or LonWorks® .
It is not necessary to download any configuration files to support the required applications. The
ProtoCarrier is pre-loaded with tested Profiles/Configurations for the supported devices.
10 I 2587517_B_EN_1810 Condair LINKS
5 Setup for ProtoCarrier
5.1 Record Identification Data
Each ProtoCessor has a unique part number located on the side or the back of the unit.
This number should be recorded, as it may be required for technical support. The numbers
are as follows:
Table 1: ProtoCarrier Part Numbers
Part Number
FPC-C34-1411
FPC-C35-1412
FPC-C34 units have the following 2 ports: RS-485 + Ethernet
FPC-C35 units have the following 2 ports: LonWorks + Ethernet
5.2 Point Count Capacity and Registers per Device
The total number of Registers presented by the device attached to the ProtoCessor
cannot exceed:
Table 2: Supported Point Count Capacity
Part Number
Total Registers
FPC-C34-1411
1500
FPC-C35-1412
1500
Table 3: Registers per Device
Devices
Registers per Device
GS_SE
28
MHTC
25
NHRS
30
NHTC
30
5.3 Configuring Device Communications
5.3.1 Input COM Settings for Device with an Inserted ProtoCarrier
Set the serial devices that the ProtoCarrier is connected to have the same Baud Rate,
Data Bits, Stop Bits, and Parity settings as the ProtoCarrier.
Table 4 specifies the device serial port settings required to communicate with the
ProtoCarrier.
Condair LINKS 2587517_B_EN_1810 I 11
Table 4: COM Settings
Serial Port Setting
GS_SE, MHTC & NHRS
NHTC
Protocol
Modbus RTU
Modbus RTU
Baud Rate
9600
9600
Parity
None
Even
Data Bits
8
8
Stop Bits
1
1
5.3.2 Set Modbus RTU Node-ID for the Device
Set Modbus Node-ID for the devices the ProtoCarrier is plugged into. (See Section 7.5 to
input Node-ID)
The Modbus Node-ID needs to be uniquely assigned between 1 and 255.
o The Modbus Node-ID that is assigned for the device needs to be documented
The Modbus Node-ID assigned is used for designating the Device Instance
for BACnet/IP and BACnet MS/TP
The Metasys N2 and Modbus TCP/IP field protocol Node-IDs are automatically set to be
the same value as the Node-ID of the Modbus RTU device.
12 I 2587517_B_EN_1810 Condair LINKS
6 Interfacing ProtoCarrier to Devices
6.1 ProtoCarrier FPC-C34 and FPC-C35 Showing Connection Ports
Figure 1: ProtoCarrier FPC-C34 (upper) and ProtoCarrier FPC-C35 (lower)
Condair LINKS 2587517_B_EN_1810 I 13
6.2 Device Connections to ProtoCarrier
ProtoCarrier 6 Pin Phoenix connector for RS-485 Devices.
The 6 pin Phoenix connector is the same for ProtoCarrier FPC-C34 (BACnet) and
FPC-C35 (LonWorks).
Pins 1 through 3 are for Modbus RS-485 devices.
o The RS-485 GND (Pin 3) is not typically connected.
Pins 4 through 6 are for power. Do not connect power (wait until Section 6.5).
Figure 2: Power and RS-485 Connections
6.2.1 Biasing the Modbus RS-485 Device Network
An RS-485 network with more than one device needs to have biasing to ensure proper
communication. The biasing only needs to be done on one device.
The ProtoCarrier has 510 Ohm resistors that can be used to set the biasing. The
ProtoCarrier’s default positions from the factory for the biasing jumpers are OFF.
The OFF position is when the 2 RED biasing jumpers straddle the 4 pins closest to the
outside of the board of the ProtoCarrier. See Figure 3.
Only turn biasing ON:
IF the BMS cannot see more than one device connected to the ProtoCarrier
AND you have checked all the settings (Modbus COM settings, wiring, and DIP
switches).
To turn biasing ON, move the 2 RED biasing jumpers to straddle the 4 pins closest to the
inside of the board of the ProtoCarrier.
Device Pins
ProtoCarrier Pin #
Pin assignment
Pin RS-485 +
Pin 1
RS-485 +
Pin RS-485 -
Pin 2
RS-485 -
Pin GND
Pin 3
RS-485 GND
Power In (+)
Pin 4
V +
Power In (-)
Pin 5
V -
Frame Ground
Pin 6
FRAME GND
14 I 2587517_B_EN_1810 Condair LINKS
Figure 3: Modbus RS-485 Biasing Switch on the ProtoCarrier C34 (left) and ProtoCarrier C35 (right)
6.2.2 End of Line Termination Switch for the Modbus RS-485 Device Network
On long RS-485 cabling runs, the RS-485 trunk must be properly terminated at each
end.
The ProtoCarrier has an End Of Line (EOL) blue jumper. The default setting for this Blue
EOL switch is OFF with the jumper straddling the pins closest to the inside of the board
of the ProtoCarrier.
On short cabling runs the EOL switch does not to need to be turned ON.
If the ProtoCarrier is placed at one of the ends of the trunk, set the blue EOL
jumper to the ON position straddling the pins closest to the outside of the board
of the ProtoCarrier.
Always leave the single Red Jumper in the A position (default factory setting).
Modbus RS-485
EOL Switch
Leave in Position A
Figure 4: Modbus RS-485 End-Of-Line Termination Switch on the ProtoCarrier C34 (left) and
RS-485 Bias
Switch
Condair LINKS 2587517_B_EN_1810 I 15
6.3 BACnet MS/TP or Metasys N2: Wiring Field Port to RS-485 Network
Connect the BACnet MS/TP or Metasys N2 RS-485 network wires to the 3-pin RS-485 connector on
ProtoCarrier C34 as shown below in Figure 5.
The RS-485 GND (Pin 3) is not typically connected
See Section 8 for information on connecting to BACnet/IP network.
If the ProtoCarrier is the last device on the BACnet MS/TP or Metasys N2 trunk, then the End-Of-
Line Termination Switch needs to be enabled (Figure 6).
o The default setting from the factory is OFF (switch position = right side)
o To enable the EOL Termination, turn the EOL switch ON (switch position = left side)
Figure 5: Connection from ProtoCarrier to RS-485 Field Network
Figure 6: RS-485 BMS Network EOL Switch
6.4 LonWorks (FPC-C35): Wiring Field Port to LonWorks Network
Connect ProtoCarrier to the field network with the LonWorks terminal using approved cable per the FT-10
installation guidelines. LonWorks has no polarity.
BMS RS-485
Wiring
ProtoCarrier
Pin #
Pin
Assignment
RS-485 +
Pin 1
RS-485 +
RS-485 -
Pin 2
RS-485 -
-
Pin 3
RS-485 GND
+
End-of-Line Switch
16 I 2587517_B_EN_1810 Condair LINKS
Figure 7: LonWorks Terminal Connector
6.5 Power-Up ProtoCarrier
Apply power to ProtoCarrier as show below in Table 5 and Figure 8. Ensure that
the power supply used complies with the specifications provided in C.1.
ProtoCarrier accepts either 9-30VDC or 12-24 VAC on pins 4 and 5.
Frame GND should be connected.
Table 5: Power Requirement for ProtoCarrier Daughter Card
Current Draw Type
ProtoCarrier Family
12VDC/VAC
24VDC/VAC
30VDC
FPC C34 (Typical)
170mA
100mA
80mA
FPC C34 (Maximum)
240mA
140mA
100mA
FPC C35 (Typical)
210mA
130mA
90mA
FPC C35 (Maximum)
250mA
170mA
110mA
Note: These values are ‘nominal’ and a safety margin should be added to the power supply of
the host system. A safety margin of 25% is recommended.
Figure 8: Power Connections
Power to
ProtoCarrier
ProtoCarrier
Pin #
Pin
Assignment
Power In (+)
Pin 4
V +
Power In (-)
Pin 5
V -
Frame Ground
Pin 6
FRAME GND
/