AMX EXB-COM2 Specification

Category
Gateways/controllers
Type
Specification
Operation/Reference Guide
Central Controllers
ICSLan Device Control Boxes
EXB-COM2
EXB-I/O8
EXB-IRS4
EXB-MP1
EXB-REL8
Last Revised: 8/02/2012
AMX Limited Warranty and Disclaimer
This Limited Warranty and Disclaimer extends only to products purchased directly from AMX or an AMX Authorized Partner which
include AMX Dealers, Distributors, VIP’s or other AMX authorized entity.
AMX warrants its products to be free of defects in material and workmanship under normal use for three (3) years from the date of
purchase, with the following exceptions:
Electroluminescent and LCD Control Panels are warranted for three (3) years, except for the display and touch overlay compo-
nents are warranted for a period of one (1) year.
Disk drive mechanisms, pan/tilt heads, power supplies, and MX Series products are warranted for a period of one (1) year.
AMX lighting products are guaranteed to switch on and off any load that is properly connected to our lighting products, as long
as the AMX lighting products are under warranty. AMX also guarantees the control of dimmable loads that are properly con-
nected to our lighting products. The dimming performance or quality there of is not guaranteed, impart due to the random combi-
nations of dimmers, lamps and ballasts or transformers.
AMX software is warranted for a period of ninety (90) days.
Batteries and incandescent lamps are not covered under the warranty.
AMX AutoPatch Epica, Modula, Modula Series4, Modula CatPro Series and 8Y-3000 product models will be free of defects in
materials and manufacture at the time of sale and will remain in good working order for a period of three (3) years following the
date of the original sales invoice from AMX. The three-year warranty period will be extended to the life of the product (Limited
Lifetime Warranty) if the warranty card is filled out by the dealer and/or end user and returned to AMX so that AMX receives it
within thirty (30) days of the installation of equipment but no later than six (6) months from original AMX sales invoice date. The
life of the product extends until five (5) years after AMX ceases manufacturing the product model. The Limited Lifetime Warranty
applies to products in their original installation only. If a product is moved to a different installation, the Limited Lifetime Warranty
will no longer apply, and the product warranty will instead be the three (3) year Limited Warranty.
All products returned to AMX require a Return Material Authorization (RMA) number. The RMA number is obtained from the AMX
RMA Department. The RMA number must be clearly marked on the outside of each box. The RMA is valid for a 30-day period. After
the 30-day period the RMA will be cancelled. Any shipments received not consistent with the RMA, or after the RMA is cancelled, will
be refused. AMX is not responsible for products returned without a valid RMA number.
AMX is not liable for any damages caused by its products or for the failure of its products to perform. This includes any lost profits, lost
savings, incidental damages, or consequential damages. AMX is not liable for any claim made by a third party or by an AMX Autho-
rized Partner for a third party.
This Limited Warranty does not apply to (a) any AMX product that has been modified, altered or repaired by an unauthorized agent or
improperly transported, stored, installed, used, or maintained; (b) damage caused by acts of nature, including flood, erosion, or earth-
quake; (c) damage caused by a sustained low or high voltage situation or by a low or high voltage disturbance, including brownouts,
sags, spikes, or power outages; or (d) damage caused by war, vandalism, theft, depletion, or obsolescence.
This limitation of liability applies whether damages are sought, or a claim is made, under this warranty or as a tort claim (including
negligence and strict product liability), a contract claim, or any other claim. This limitation of liability cannot be waived or amended by
any person. This limitation of liability will be effective even if AMX or an authorized representative of AMX has been advised of the
possibility of any such damages. This limitation of liability, however, will not apply to claims for personal injury.
Some states do not allow a limitation of how long an implied warranty last. Some states do not allow the limitation or exclusion of inci-
dental or consequential damages for consumer products. In such states, the limitation or exclusion of the Limited Warranty may not
apply. This Limited Warranty gives the owner specific legal rights. The owner may also have other rights that vary from state to state.
The owner is advised to consult applicable state laws for full determination of rights.
EXCEPT AS EXPRESSLY SET FORTH IN THIS WARRANTY, AMX MAKES NO OTHER WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. AMX
EXPRESSLY DISCLAIMS ALL WARRANTIES NOT STATED IN THIS LIMITED WARRANTY. ANY IMPLIED WARRANTIES THAT
MAY BE IMPOSED BY LAW ARE LIMITED TO THE TERMS OF THIS LIMITED WARRANTY. EXCEPT AS OTHERWISE LIMITED
BY APPLICABLE LAW, AMX RESERVES THE RIGHT TO MODIFY OR DISCONTINUE DESIGNS, SPECIFICATIONS, WARRAN-
TIES, PRICES, AND POLICIES WITHOUT NOTICE.
Table of Contents
i
ICSLan Device Control Boxes
Table of Contents
ICSLan Device Control Boxes .............................................................................1
Overview .................................................................................................................. 1
Common Features..................................................................................................... 2
LAN/PoE Port ........................................................................................................... 3
Detailed LED Behavior.............................................................................................. 4
Installation ..........................................................................................................5
Mounting Options (Rack Trays and Mounting Brackets) ........................................... 5
AVB-VSTYLE-SURFACE-MNT (FG1010-722) .................................................................... 5
AVB-VSTYLE-RMK (FG1010-720)..................................................................................... 5
AVB-VSTYLE-RMK-FILL-1U (FG1010-721)........................................................................ 5
AVB-VSTYLE-POLE-MNT (FG1010-723)........................................................................... 6
SAFETY INSTRUCTIONS ........................................................................................... 7
Preparing/Connecting Captive Wires........................................................................ 7
LAN/PoE Port ........................................................................................................... 7
Network Configuration .......................................................................................9
Overview .................................................................................................................. 9
Default Parameters For Static IP Mode .......................................................................... 9
DHCP Mode .................................................................................................................... 9
TCP/IP Address Configuration......................................................................................... 9
Telnet IP Configuration Commands............................................................................... 10
Master Connection Modes...................................................................................... 10
TCP vs. UDP .................................................................................................................. 10
URL vs. NDP vs. Auto .................................................................................................... 10
Factory Default Parameters .................................................................................... 11
Device IDs .............................................................................................................. 12
Using the ID Pushbutton......................................................................................... 12
Using "Identify Mode" to Set the Device Address on the EXB Modules ...................... 13
Toggling Between Static and DHCP IP Addressing....................................................... 14
Performing a Factory Reset .................................................................................... 14
Resetting the Unit to the Factory Default Firmware Image .................................... 14
Programming the EXB Modules.............................................................................. 15
EXB-COM2 .......................................................................................................17
Overview ................................................................................................................ 17
EXB-COM2 Product Specifications................................................................................ 17
Connections and Wiring.......................................................................................... 18
LAN/PoE Port (RJ45) ..................................................................................................... 18
ii
ICSLan Device Control Boxes
Table of Contents
Port 1(Multi-Protocol COM Port)................................................................................... 18
Port 2 (RS-232 only)....................................................................................................... 18
NetLinx Programming............................................................................................. 19
EXB-COM2 Port Assignments ...................................................................................... 19
EXB-COM2 SEND_COMMANDs.................................................................................... 19
SEND_STRING Escape Sequences ................................................................................. 19
Telnet commands .......................................................................................................... 19
EXB-I/O8 ...........................................................................................................21
Overview ................................................................................................................ 21
EXB-I/O8 Product Specifications ................................................................................... 21
Connections and Wiring.......................................................................................... 22
LAN/PoE Port (RJ45) ..................................................................................................... 22
Port 1 (I/O 1-8) .............................................................................................................. 22
NetLinx Programming............................................................................................. 22
EXB-IO8 Port Assignments ........................................................................................... 22
EXB-IO8 Channel Assignments ..................................................................................... 22
EXB-I/O8 SEND_COMMANDs....................................................................................... 23
Telnet commands .......................................................................................................... 23
EXB-IRS4 ...........................................................................................................25
Overview ................................................................................................................ 25
EXB-IRS4 Product Specifications ................................................................................... 25
Connections and Wiring.......................................................................................... 26
LAN/PoE Port (RJ45) ..................................................................................................... 26
IR/Serial Port Bank (Ports 1-4)................................................................................. 26
Input Port Bank....................................................................................................... 26
Input Linking ........................................................................................................... 27
Unlinked Mode (Default) ............................................................................................... 27
Linked Mode ................................................................................................................. 27
Input Pin ........................................................................................................................ 27
Entering/Exiting Linked Mode....................................................................................... 27
Linked Modes ................................................................................................................ 28
NetLinx Programming............................................................................................. 29
EXB-IRS4 Port Assignments........................................................................................... 29
EXB-IRS4 Channel Assignments..................................................................................... 29
EXB-IRS4 SEND_COMMANDs ....................................................................................... 30
Telnet commands .......................................................................................................... 30
EXB-MP1 ..........................................................................................................31
Overview ................................................................................................................ 31
EXB-MP1 Product Specifications ................................................................................... 31
Table of Contents
iii
ICSLan Device Control Boxes
Connections and Wiring.......................................................................................... 32
LAN/PoE Port (RJ45) ..................................................................................................... 32
Port 1 (RS-232 only) ...................................................................................................... 32
Port 2 (I/O) .................................................................................................................... 32
Port 3 (IR-TX/Serial)....................................................................................................... 33
Port 4 (IR-RX)................................................................................................................. 33
NetLinx Programming............................................................................................. 34
EXB-MP1 SEND_COMMANDs....................................................................................... 34
SEND_STRING Escape Sequences................................................................................. 34
Telnet commands .......................................................................................................... 34
EXB-REL8 ..........................................................................................................35
Overview ................................................................................................................ 35
EXB-REL8 Product Specifications .................................................................................. 35
Connections and Wiring.......................................................................................... 36
LAN/PoE Port (RJ45) ..................................................................................................... 36
Port 1 (Relay Connector) ............................................................................................... 36
NetLinx Programming............................................................................................. 36
EXB-REL8 Port Assignments.......................................................................................... 36
EXB-REL8 Channel Assignments.................................................................................... 36
EXB-REL8 SEND_COMMANDs...................................................................................... 36
Telnet commands .......................................................................................................... 36
NetLinx Send Commands .................................................................................37
B9MOFF .................................................................................................................................... 37
B9MON ..................................................................................................................................... 37
CAROFF..................................................................................................................................... 37
CARON...................................................................................................................................... 37
CH ............................................................................................................................................. 38
CHARD ...................................................................................................................................... 38
CHARDM ................................................................................................................................... 38
CP.............................................................................................................................................. 39
CTOF ......................................................................................................................................... 39
CTON ........................................................................................................................................ 39
CTSPSH ..................................................................................................................................... 40
CTSPSH OFF.............................................................................................................................. 40
ESCSEQOFF .............................................................................................................................. 40
ESCSEQON ............................................................................................................................... 40
GET BAUD................................................................................................................................. 40
GET DBT.................................................................................................................................... 40
GET INPUT ................................................................................................................................ 41
GET MODE................................................................................................................................ 41
GET OFF DELAY........................................................................................................................ 41
GET ON DELAY ......................................................................................................................... 41
HSOFF ....................................................................................................................................... 41
HSON ........................................................................................................................................ 41
iv
ICSLan Device Control Boxes
Table of Contents
IROFF........................................................................................................................................ 42
LED-DIS..................................................................................................................................... 42
LED-EN ..................................................................................................................................... 42
POD .......................................................................................................................................... 42
POF........................................................................................................................................... 43
PON .......................................................................................................................................... 43
PTOF......................................................................................................................................... 44
PTON ........................................................................................................................................ 44
REBOOT.................................................................................................................................... 44
RXCLR ....................................................................................................................................... 45
RXOFF ...................................................................................................................................... 45
RXON........................................................................................................................................ 45
SET BAUD ................................................................................................................................. 45
SET DBT .................................................................................................................................... 46
SET DBTF .................................................................................................................................. 46
SET INPUT................................................................................................................................. 46
SET INPUT LINK ........................................................................................................................ 46
SET IO LINK .............................................................................................................................. 46
SET MODE ................................................................................................................................ 47
SET_NDX_DESC........................................................................................................................ 47
SET OFF DELAY ........................................................................................................................ 47
SET ON DELAY ......................................................................................................................... 47
SP.............................................................................................................................................. 48
TSET BAUD ............................................................................................................................... 48
TXCLR ....................................................................................................................................... 48
XCH .......................................................................................................................................... 49
XCHM ....................................................................................................................................... 49
XOFF......................................................................................................................................... 50
XON.......................................................................................................................................... 50
SEND_STRING Escape Sequences .......................................................................... 51
27,17......................................................................................................................................... 51
27,18,0...................................................................................................................................... 51
27,18,1...................................................................................................................................... 51
27,19......................................................................................................................................... 51
27,20,0...................................................................................................................................... 51
Terminal (Telnet) Commands ............................................................................53
Overview ................................................................................................................ 53
Establishing a Terminal Connection via Telnet........................................................ 53
Telnet Username and Password.............................................................................. 53
Additional Notes ........................................................................................................... 54
Setting a Telnet Username and Password ..................................................................... 54
Telnet Commands ................................................................................................... 54
? or Help ................................................................................................................................... 54
DEVICE STATUS........................................................................................................................ 54
EXIT .......................................................................................................................................... 55
FACTORYFWIMAGE ................................................................................................................. 55
GET CONFIG............................................................................................................................. 55
Table of Contents
v
ICSLan Device Control Boxes
GET CONNECTION ................................................................................................................... 55
GET DEVICE .............................................................................................................................. 55
GET DNS ................................................................................................................................... 55
GET ETHERNET MODE ............................................................................................................. 55
GET FRIENDLY <name> ............................................................................................................ 55
GET IP ....................................................................................................................................... 56
GET LOCATION......................................................................................................................... 56
GET SN...................................................................................................................................... 56
MSG [ON|OFF]........................................................................................................................... 56
NDP UNBIND ............................................................................................................................ 56
PING [ADDRESS] ....................................................................................................................... 56
REBOOT .................................................................................................................................... 56
RENEW DHCP ........................................................................................................................... 56
RESET FACTORY ....................................................................................................................... 56
SET CONNECTION.................................................................................................................... 57
SET DEVICE ............................................................................................................................... 57
SET DNS .................................................................................................................................... 57
SET ETHERNET MODE .............................................................................................................. 58
SET FRIENDLY........................................................................................................................... 58
SET IP ........................................................................................................................................ 58
SET LOCATION ......................................................................................................................... 58
Notes on Specific Telnet Clients ............................................................................. 59
Windows Client Programs ............................................................................................. 59
SET TELNET PORT..................................................................................................................... 59
SET TELNET USERNAME........................................................................................................... 59
SET TELNET PASSWORD .......................................................................................................... 59
SHOW CONNECTION LOG ....................................................................................................... 59
SHOW CONNECTION STATS .................................................................................................... 59
SHOW LOG ............................................................................................................................... 59
Linux Telnet Client ........................................................................................................ 60
Enabling / Disabling Telnet on EXB Modules.......................................................... 60
vi
ICSLan Device Control Boxes
Table of Contents
ICSLan Device Control Boxes
1
ICSLan Device Control Boxes
ICSLan Device Control Boxes
Overview
The EXB family of ICSLan Device Control Boxes (FIG. 1) provides Ethernet-based remote port expansion for
NetLinx Central Controllers. ICSLan Device Control Boxes may be used to provide remote ports for a master
(eliminating the need to implement another Central Controller), or to provide large numbers of ports in a rack-
mount environment.
FIG. 1 ICSLan Device Control Boxes
ICSLan Device Control Boxes - Product Family
Name FG# Description Page Reference
EXB-COM2 FG2100-22 ICSLan Serial Interface, 2 Ports See page 17
EXB-I/O8 FG2100-21 ICSLan Input/Output Interface, 8 Channels See page 21
EXB-IRS4 FG2100-23 ICSLan IR/S Interface, 4 IR/S and 4 Inputs See page 25
EXB-MP1 FG2100-26 ICSLan Multi-Port, 1 COM, 1 IR/S, 2 I/O, 1 IR RX See page 31
EXB-REL8 FG2100-20 ICSLan Relay Interface, 8 Channels See page 35
EXB-MP1 (FG2100-26)
EXB-COM2 (FG2100-22)
EXB-I/08 (FG2100-21)
EXB-IRS4 (FG2100-23)
EXB-REL8 (FG2100-20)
ICSLan Device Control Boxes
2
ICSLan Device Control Boxes
Common Features
Many features are common to all products in the EXB family, as described in the following table.
Model -specific features are described in the following sections.
ICSLan Device Control Boxes - Common Features
Dimensions (HWD): EXB-COM2, -I/O8, -IRS4 and -REL8:
1.00” x 4.35” x 5.15” (25.48 x 110.36 x 130.81)
•EXB-MP1:
1.00” x 3.04” x 4.82” (25.48cm x 77.14cm x 122.43cm)
Weight: EXB-COM2: 1 lb (454 g)
EXB-I/O8: 1 lb (454 g)
EXB-IRS4: 1 lb (454 g)
EXB-MP1: 1 lb (454 g)
EXB-REL8: 1 lb (454 g)
Power Requirements: PoE (Power-over-Ethernet).
Idle (minimum) Power Draw: Busy (maximum) Power Draw
EXB-COM2: 40mA 1.92 watts 40mA 1.92 watts
EXB-IO8: 30mA 1.44 watts 40mA 1.92 watts
EXB-IRS4: 40mA 1.92 watts 50mA 2.4 watts
EXB-MP1 40mA 1.92 watts 40mA 1.92 watts
EXB-REL8: 40mA 1.92 watts 70mA 3.36 watts
Enclosure: Metal with black matte finish
Front Panel Components
ID Pushbutton: The ID Pushbutton serves four functions:
ID Mode: Used in conjunction with the ID Mode feature in NetLinx Studio, a
momentary push assigns a device address to the Module. See the Using
"Identify Mode" to Set the Device Address on the EXB Modules section on
page 13 for details.
Static/DHCP: If the button is pressed and held for 10 seconds or longer and
then released, the unit toggles between static and dynamic IP addressing. See
the Toggling Between Static and DHCP IP Addressing section on page 14 for
details.
Factory Reset: If the ID button is held for 10 seconds or longer during the boot
process, the unit will reset to factory defaults. See the Performing a Factory
Reset section on page 14 for details.
Factory Image: If the ID pushbutton is held for 20 seconds and released while
the Module is booting up, the Module will restore itself to a factory firmware
image. See the Resetting the Unit to the Factory Default Firmware
Image section on page 14 for details.
Status LED: The green Status LED indicates unit status.
See the Detailed LED Behavior section on page 4 for details.
L/A LED: The green L/A (Link / Active) LED indicates communication status.
See the Detailed LED Behavior section on page 4 for details.
Rear Panel Components
Ethernet / PoE
Connector
RJ-45 connector provides IP communication and PoE.
This is an Auto MDI/MDI-X enabled port, therefore either straight-through or
crossover Ethernet cables can be used.
Note: The Ethernet connector is located on the front panel of the EXB-MP1 (see
FIG. 9 on page 31)
Module Specific
Connectors
Varies per model - refer to Connections and Wiring in each of the following
sections.
ICSLan Device Control Boxes
3
ICSLan Device Control Boxes
LAN/PoE Port
The LAN/PoE (RJ45) port on all EXB Modules provides 10/100 BaseT network connectivity. Use standard
Cat5/6/6E ethernet cable to connect the EXB Module to the LAN. The following table lists the pinouts,
signals, and pairing for the Network port.
The Ethernet Port LEDs show communication activity, connection status, speeds, and mode information:
SPD (speed) - Yellow LED lights On when the connection speed is 100 Mbps and turns Off when
the speed is 10 Mbps.
L/A (link/activity) - Green LED lights On when the Ethernet cables are connected and terminated
correctly, and blinks when receiving Ethernet data packets.
ICSLan Device Control Boxes - Common Features (Cont.)
Storage/Operating
Environment:
Operating Temperature: 0° C (32° F) to 40° C (104° F)
Storage Temperature: -10° C (14° F) to 60° C (140° F)
Operating Humidity: 5% to 85% RH (non-condensing)
Heat Dissipation (Typical): 36.9 BTU/hr
Designed for indoor use only.
Certifications: FCC Part 15 Class B, CE, and IEC 60950
Included & Optional
Accessories
Varies per model - refer to the Specifications tables in each of the following
sections.
LAN/PoE Port Pinouts and Signals
Pin Signals Connections Pairing Color
1 TX + 1 --------- 1 1 --------- 2 White-Orange
2 TX - 2 --------- 2 Orange
3 RX + 3 --------- 3 3 --------- 6 White-Green
4 no connection 4 --------- 4 Blue
5 no connection 5 --------- 5 White-Blue
6 RX - 6 --------- 6 Green
7 no connection 7 --------- 7 White-Brown
8 no connection 8 --------- 8 Brown
ICSLan Device Control Boxes
4
ICSLan Device Control Boxes
Detailed LED Behavior
The table below provides detailed descriptions of all blink patterns for the Status and A/L LEDs on the front
panels of all EXB Modules.
The I/O LED column refers to port-specific Input and/or Output LEDs on a particular model. For
example, I/O includes all serial TX and RX LEDs on a COM2 or all Relay output LEDs on a
REL8.
The term “Light Show” refers to the back-and-forth scanning pattern of the LEDs associated with
the I/Os on each model.
See the Using the ID Pushbutton section on page 12 for additional information.
EXB Modules - Detailed LED Behavior
Module Condition L/A LED Status LED I/O LED
Normal Online with
Master (rest)
On if connected to master.
Blink off w/ data.
Follow Master’s
instruction for Blink
Message if online with
Master, otherwise ON
On when active,
otherwise off
Normal Boot (DHCP
found)
Note: This state
continues from the
time an IP address is
obtained until the device
is online with the Master.
OFF ON Normal Light Show,
then OFF until online
with Master, then normal
operation
Normal Boot (DHCP, no
server)
Note: This state
continues until a valid
IP address is obtained.
Fast Blink, then normal
operation
ON Normal Light Show,
then OFF until online
with Master, then
normal operation
Normal Boot (Static IP)
Note: This state
continues until the device
finishes the Light Show.
OFF during Light Show,
then normal operation
(Off until connected to
Master)
Fast Blink (continues
only during Light Show),
then ON until first blink
from Master.
Normal Light Show,
then OFF until online
with Master, then normal
operation
Boot with ID Pushbutton
held down
Slow Blink (1Hz) Slow Blink (1Hz) Slow Blink (1Hz)
ID Pushbutton held down
long enough for reset to
default parameters
Fast Blink until ID
Pushbutton is released,
then OFF
Fast Blink until ID
Pushbutton is released,
then OFF
Fast Blink until ID
Pushbutton is released,
then OFF
ID Pushbutton held down
long enough for reset to
default firmware image
Solid ON, transitions to
OFF once the unit
completes writing to flash
and is ready to reboot
Solid ON, transitions
to OFF once the unit
completes writing to flash
and is ready to reboot
Solid ON, transitions
to OFF once the unit
completes writing to
flash and is ready to
reboot
In Auto ID mode Normal Blink (2Hz) Normal
ID Pushbutton held down
long enough to accept
new ID
2 Blinks, then normal 2 Blinks, then normal 2 Blinks, then normal
After boot: ID Pushbutton
held down, but not long
enough for IP mode
change
Slow Blink (1Hz) Slow Blink (1Hz) Slow Blink (1Hz)
After boot: ID Pushbutton
held down long enough
for IP mode change
Fast Blink, then OFF Fast Blink, then OFF Fast Blink, then OFF
Downloading Firmware to
Flash Due to an upgrade
via NetLinx Studio.
Fast Blink, alternating
with Status LED)
Fast Blink, alternating
with L/A LED)
Fast Blink, alternating
LEDs
Installation
5
ICSLan Device Control Boxes
Installation
Mounting Options (Rack Trays and Mounting Brackets)
Refer to the documentation provided with each of the mounting kits for installation instructions (also available
online at www.amx.com).
AVB-VSTYLE-SURFACE-MNT (FG1010-722)
V Style Single Module Surface Mount Brackets - Mount a single module to the wall, under a desk, etc
(FIG. 2).
AVB-VSTYLE-RMK (FG1010-720)
V Style Module Tray Rack - Mount up to four modules side by side in a 1 RU space (FIG. 3).
AVB-VSTYLE-RMK-FILL-1U (FG1010-721)
V Style Module Tray Rack - Mount up to four modules side by side in a 1 RU space, with Fill Plates for
instances when the entire tray is not full (FIG. 3).
Note that the tray illustrated in FIG. 3 is shown upside down for ease of installation. However, the tray can be
rack-mounted in a rack either way.
Also note that the Fill Plate included in this illustration is included only in the AVB-VSTYLE-RMK-FILL-1U
(FG1010-721).
FIG. 2 AVB-VSTYLE-SURFACE-MNT
FIG. 3 AVB-VSTYLE-RMK
Below surface mounting
Above surface mounting
Fill Plate
(included with the AVB-VSTYLE-RMK-FILL-1U mounting kit only)
The AVB-VSTYLE-RMK and AVB-VSTYLE-RMK-FILL-1U mounting kits are
appropriate for the EXB-COM2, -IRS4, -IO8 and -REL8 (but not the EXB-MP1).
Installation
6
ICSLan Device Control Boxes
AVB-VSTYLE-POLE-MNT (FG1010-723)
V Style Single Module Pole Mounting Kit - Suspend a single module to a pole (FIG. 4).
FIG. 4 AVB-VSTYLE-POLE-MNT
Installation
7
ICSLan Device Control Boxes
SAFETY INSTRUCTIONS
For UL compliance, the EXB family of ICSLan Device Control Boxes should be powered directly
via any listed external IEC/UL 60950-1 2nd edition certified LPS PoE switch or injector, such as
the AMX NXA-ENET8POE or PS-POE-AF.
The EXB family of ICSLan Device Control Boxes are intended for Network Environment 0 per
IEC TR62101, and are to be connected only to PoE networks without routing to the outside plant.
Preparing/Connecting Captive Wires
1. Strip 0.25 inch of wire insulation off all wires.
2. Insert each wire into the appropriate opening on the connector according to the wiring diagrams and
connector types described in this section.
Do not tighten the screws excessively; doing so may strip the threads and damage the connector.
LAN/PoE Port
The LAN/PoE (RJ45) port on all EXB Modules provides 10/100 BaseT network connectivity. Use standard
Cat5/6/6E ethernet cable to connect the EXB Module to the LAN. The following table lists the pinouts,
signals, and pairing for the Network port.
The Ethernet Port LEDs show communication activity, connection status, speeds, and mode information:
SPD (speed) - Yellow LED lights On when the connection speed is 100 Mbps and turns Off when
the speed is 10 Mbps.
L/A (link/activity) - Green LED lights On when the Ethernet cables are connected and terminated
correctly, and blinks when receiving Ethernet data packets.
LAN/PoE Port Pinouts and Signals
Pin Signals Connections Pairing Color
1 TX + 1 --------- 1 1 --------- 2 White-Orange
2 TX - 2 --------- 2 Orange
3 RX + 3 --------- 3 3 --------- 6 White-Green
4 DC + 4 --------- 4 Blue
5 DC + 5 --------- 5 White-Blue
6 RX - 6 --------- 6 Green
7 DC - 7 --------- 7 White-Brown
8 DC - 8 --------- 8 Brown
Installation
8
ICSLan Device Control Boxes
Network Configuration
9
ICSLan Device Control Boxes
Network Configuration
Overview
EXB modules support two IP addressing modes: Static IP, and DHCP (with link-local fallback).
By default, EXB Modules are set to DHCP Mode.
The modules can be configured for either of these modes via two methods:
The front-panel ID Pushbutton (see the Toggling Between Static and DHCP IP Addressing on
page 14).
Telnet command (see the Terminal (Telnet) Commands on page 53).
Default Parameters For Static IP Mode
DHCP Mode
When in DHCP mode (the default setting), the module will attempt to get a DHCP lease (consisting of IP
address, gateway, and other network parameters). Should it fail to obtain a lease from a DHCP server, it will
then configure itself for a link-local address.
EXB modules utilize a modified link-local addressing procedure: the first address to be tried is a
known address in the link-local space: 169.254.2.2. That address will be probed, and if unclaimed
will be used by the EXB module.
If 169.254.2.2 is already claimed, the EXB module will choose a random address within the
169.252.x.x link-local address space (again probing to ensure that it is unclaimed).
Once operating with a link-local address, the device will periodically re-try DHCP, and re-assign the IP to a
valid DHCP grant if successful.
At any time, if the device determines that its IP address has changed, it will disconnect from the Master (if
necessary, depending on the connection state), and then reconnect to the Master.
TCP/IP Address Configuration
EXB modules support IPV4 network addresses, gateway addresses, DNS server addresses, and network name.
EXB modules support Nexus Discovery Protocol (NDP) capabilities as well as IP discovery via NetLinx
Studio.
"Link-Local Fallback" is a method by which an IP host can derive a local network-
unique IP address, by negotiating with the other IP hosts on the same network, as a
fallback from DHCP. Link-Local can also be used in its own right as the primary
method of IP address allocation. See "DHCP Mode" below for details.
Default Parameters For Static IP Mode
Address: 192.168.1.2
Netmask: 255.255.255.0
Gateway: 192.168.1.1
DNS1: 192.168.1.1
DNS2: 192.168.1.1
DNS3: 192.168.1.1
NDP stands for "NetLinx Discovery Protocol", a device discovery method used by
NetLinx Masters. With NDP Beacon enabled, the Master will transmit NDP beacons
for AMX's proprietary device discovery.
Network Configuration
10
ICSLan Device Control Boxes
Telnet IP Configuration Commands
The SET IP (page 58) and GET IP (page 56) Telnet commands listed in the following table can be sent
directly to the device via a Telnet terminal session. These commands can be used for initial network
configuration of the EXB Modules.
The default Telnet port is 23. A value of 0 disables the telnet server.
Telnet is enabled by default.
See the Terminal (Telnet) Commands section on page 53 for details.
Master Connection Modes
The mode of communication used for connection to the Master is specified via the SET CONNECTION Telnet
command (see page 57).
The options are “AUTO”, “URLTCP”, “URLUDP” or “NDP”, as described below.
Note that default connection mode setting is NDP.
AUTO - This mode utilizes TCP communication; it looks for a matching System Number and
attempts to come online with the first master it sees with that System Number.
URLTCP - TCP; the Master is specified via URL.
URLUDP - UDP; the Master is specified via URL.
NDP - UDP; this mode utilizes the NDP binding process to assign the EXB Module (the physical
device) to a Master via NetLinx Studio. Once bound, communications are conducted via UDP.
TCP vs. UDP
TCP - Protocol has built-in retry mechanism.
UDP - Protocol does not have a built-in retry mechanism, but consumes fewer resources on the
Master. AMX’s UDP implementation of NetLinx employs a retry mechanism to provide the
reliability of TCP, with the resource efficiency of UDP.
URL vs. NDP vs. Auto
Determining which connection method to use for Master Connection Mode is essentially a matter of deciding
what information the device should use to identify the correct target Master for connection.
The default mode is NDP; the mode can be changed via the SET CONNECTION Telnet command (see
page 57).
URL - The device connects to the Master with the specified URL. The device must be configured
with the URL of a specific Master via the SET CONNECTION Telnet command (see page 57).
NDP - The device connects to the Master it's been bound to based on the Masters MAC address.
The binding is configured via NetLinx Studio. Once bound, the device must be unbound using
either NetLinx Studio or the Telnet NDP UNBIND command before being re-bound to a different
Master.
Alternatively, NDP devices can be bound/unbound via options on the Masters Web Configuration
pages (System > Manage NetLinx). Refer to the NetLinx Integrated Controllers- WebConsole &
Programming Guide (System - Manage NetLinx section) for details.
Auto - The device connects to the first Master it finds with the specified System Number. The
device must be configured with the desired system number via the SET CONNECTION Telnet
command (see page 57).
Use of this method requires that only one Master has any particular system number, and is visible to
the subnet. If this is the case, then Auto is the most simple choice. However, with Auto, you are not
hard-bound to a particular Master. Therefore, if at some point in the future, another Master is
configured with the same system number, the result is that the EXB Module could show up on that
other Master.
In URL modes, the Master can use either an IP address or a DNS name.
Network Configuration
11
ICSLan Device Control Boxes
Factory Default Parameters
Factory Default Parameters are the values stored in the unit at the time it leaves the factory. EXB Modules can
be restored the unit to their factory default parameters in several ways:
via the ID Pushbutton (see the Performing a Factory Reset section on page 14)
via the RESET FACTORY telnet command (see page 56)
The factory default parameters are listed below:
Factory Default Parameters
Parameter Value
MAC Address As set in factory
Serial Number As set in factory
Ethernet mode Auto (i.e., speed, duplex, both, auto)
IP Addressing Mode DHCP
IP Address (for static mode) 192.168.1.2
Netmask (for static mode) 255.255.255.0
Gateway (for static mode) 192.168.1.1
DNS1 (for static mode) 192.168.1.1
DNS2 (for static mode) 192.168.1.1
DNS3 (for static mode) 192.168.1.1
DNS Domain amx.com
Hostname Last seven digits of the model-serial number - unique for each unit
Master Connection Mode NDP - See the Master Connection Modes section on page 10 for details.
Master URL (for TCP and UDP
URL modes)
“” (blank)
Master Connection port number
for TCP and UDP URL modes
1319
Friendly-Name “” (blank)
Note: If the Friendly Name is non-blank, both Friendly Name and Location
are concatenated to make NDPSTRING2, otherwise NDPSTRING2 is
generated from the unit’s serial number.
Location “”
Stored MAC address of Master
(used for NDP binding)
00:00:00:00:00:00
ICSP Device Number 0 (receive dynamic device number from Master)
System Number 0
Username for Master Blank (empty string)
A blank username and password implies that no encryption will be used
Password for Master Blank (empty string)
A blank username and password implies that no encryption will be used
Telnet port 23
A value of 0 disables the telnet server. Telnet is enabled by default.
Telnet username Blank (empty string)
A blank username and password implies that the telnet server will not query
for username password
Telnet password Blank (empty string)
CTOF time 5 (0.5 seconds)
CTON time 5 (0.5 seconds)
Baud Data Rate/Format 9600, 8, N, 1
Network Configuration
12
ICSLan Device Control Boxes
Device IDs
Using the ID Pushbutton
Use the ID Pushbutton (on the front panel of all EXB Modules) to perform various initial configuration
settings, as described in the following sections. The ID Pushbutton provides several functions, depending on
when and for how long the pushbutton is pressed and held:
Momentary press: If the device is in ID mode, a momentary press causes the module to identify
itself to the system. Note that a momentary press at any other time is ignored.
See the Using "Identify Mode" to Set the Device Address on the EXB Modules section (below) for
details.
10-Second Press and Hold (during runtime): If the ID Pushbutton is held for 10 seconds or longer
and then released during runtime (i.e., after boot completes), the unit will toggle between Static IP
and DHCP Mode IP addressing - after the button is released.
Note that after applying the new setting, the module will automatically reboot.
By default, EXB Modules are set to DHCP Mode (with link-local fallback).
See the Toggling Between Static and DHCP IP Addressing section on page 14 for details.
10-Second Press and Hold (during boot-up): If the ID Pushbutton is held for 10 seconds or longer
at boot, the module will reset to factory default parameters and reboot after release.
Press and hold the ID Pushbutton while plugging in the Ethernet / PoE connector. Begin counting
only when the LEDs begin to flash (as opposed to the moment that the connector is inserted).
Note that once the module has started booting up, all LEDs flash in unison at the rate of once per
second. After 10 flashes at this rate, the LEDs will flash in unison at a faster rate. At the point that
the blink rate increases (approximately 10 seconds after boot-up), release the pushbutton.
See the Performing a Factory Reset section on page 14 for details.
20-Second Press and Hold (during boot-up): If the ID Pushbutton is held for 20 seconds or longer
at boot, the module will reset to the factory default firmware image and reboot after release.
Press and hold the ID Pushbutton while plugging in the Ethernet / PoE connector. Begin counting
only when the LEDs begin to flash (as opposed to the moment that the connector is inserted).
Note that once the module has started booting up, all LEDs flash in unison at the rate of once per
second. After 10 flashes at this rate, the LEDs will blink in unison at a faster rate. After 10 seconds
of flashing at the increased rate, all LEDs go to solid on. At the point that the LEDs go to solid on
(approximately 20 seconds after boot-up), release the pushbutton.
See the Resetting the Unit to the Factory Default Firmware Image section on page 14 for details.
Device IDs
Model ID (16-bits)
EXB-COM2 0x0164
EXB-I/O8 0x0168
EXB-IRS4 0x0166
EXB-MP1 0x0165
EXB-REL8 0x0167
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70