nxs

Vacon nxs User manual

  • Hello! I am an AI chatbot trained to assist you with the Vacon nxs User manual. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
vacon nx
ac drives
optc2/c8
modbus/n2 option board
user manual
INDEX Document code: DPD00899A
Date 19.01.2012
1. GENERAL ........................................................................................................................... 3
2.
RS-485 OPTION BOARD TECHNICAL DATA ........................................................................ 4
2.1 General ......................................................................................................................................... 4
3.
RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS ................................................... 5
3.1 RS-485 OPTC2 option board ......................................................................................................... 5
3.2 RS-485 OPTC8 option board ......................................................................................................... 6
3.3 Grounding ..................................................................................................................................... 7
3.3.1 Grounding by clamping the cable to the converter frame .................................................7
3.3.2 Grounding only one point on the net ..................................................................................9
3.3.3 Grounding jumper X1 ....................................................................................................... 10
3.4 Bus terminal resistors................................................................................................................ 11
3.5 Bus Biasing ................................................................................................................................. 12
3.6 LED indications ........................................................................................................................... 13
4.
INSTALLATION OF VACON NX RS-485 BOARD ................................................................. 14
5.
COMMISSIONING .............................................................................................................. 16
5.1 Fieldbus board parameters ........................................................................................................ 16
6.
MODBUS ........................................................................................................................... 19
6.1 Modbus RTU protocol, introduction ............................................................................................ 19
6.1.1 Supported functions ......................................................................................................... 21
6.1.2 Exception responses ........................................................................................................ 23
6.2 Modbus interface ........................................................................................................................ 25
6.2.1 Modbus registers ............................................................................................................. 25
6.2.2 Process data .................................................................................................................... 25
6.2.3 Process data in ................................................................................................................ 26
6.2.4 Process data out .............................................................................................................. 27
6.2.5 Parameters ...................................................................................................................... 30
6.2.6 Actual values .................................................................................................................... 30
6.2.7 Example messages .......................................................................................................... 31
6.3 Start-up test ............................................................................................................................... 33
7.
METASYS N2 ..................................................................................................................... 34
7.1 Metasys N2 Protocol Introduction .............................................................................................. 34
7.2 Metasys N2 interface .................................................................................................................. 34
7.2.1 Analogue Input (AI) .......................................................................................................... 34
7.2.2 Binary Input (BI) ............................................................................................................... 34
7.2.3 Analogue Output (AO)....................................................................................................... 35
7.2.4 Binary Output (BO) ........................................................................................................... 35
7.2.5 Internal Integer (ADI) ....................................................................................................... 35
7.3 N2 POINT MAP ............................................................................................................................ 36
7.3.1 Analogue Inputs (AI) ......................................................................................................... 36
7.3.2 Binary Inputs (BI) ............................................................................................................. 37
7.3.3 Analogue Outputs (AO) ..................................................................................................... 37
7.3.4 Binary Outputs (BO) ......................................................................................................... 38
7.3.5 Internal Integers (ADI) ..................................................................................................... 38
8.
FAULT TRACKING ............................................................................................................. 39
APPENDIX 1 ............................................................................................................................................ 40
general vacon 3
24-hour support +358 (0)40 8371 150 Email: va[email protected]
1
1. GENERAL
Instead of sending and receiving information to and from frequency converters through I/O, you can
connect them to a fieldbus.
Vacon NX frequency converters can be connected to the RS-485 bus using a fieldbus board. The con-
verter can then be controlled, monitored and programmed from the host system.
If you purchase your RS-485 Option Board separately, please note that it shall be installed in
slot E on
the control board of the frequency converter.
WARNING!
Internal components and circuit boards are at high potential when the frequency
converter is connected to the power source. This voltage is extremely dangerous
and may cause death or severe injury if you come into contact with it.
4 • vacon technical data
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
2
2. RS-485 OPTION BOARD TECHNICAL DATA
2.1 General
Connections
Interface
OPTC2
: Pluggable connector (5.08mm)
OPTC8
: 9-pin DSUB connector (female)
Data transfer
method
RS-485, half-duplex
Transfer cable Twisted pair (1 pair and shield)
Electrical isolation 500 VDC
Communications
Modbus RTU
Metasys N2
As described in document “Modicon Modbus Protocol
Reference Guide”
Find it for example at: http://public.modicon.com/
As described in Metasys N2 System Protocol Specifica-
tion
Baud rate 300, 600, 1200, 2400, 4800, 9600, 19200 and 38400 kbaud
Addresses 1 to 247
Environment
Ambient operating
temperature
–10°C…55°C
Storing tempera-
ture
–40°C…60°C
Humidity <95%, no condensation allowed
Altitude Max. 1000 m
Vibration 0.5 G at 9…200 Hz
Safety
Fulfils EN50178 standard
Table 1. RS-485 technical data
layout and connections vacon 5
24-hour support +358 (0)40 8371 150 Email: va[email protected]
3
3. RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS
Vacon RS-485 Fieldbus Board is connected to the fieldbus through either a 5-pin pluggable bus con-
nector (board OPTC2) or a 9-pin female sub-D-connector (board OPTC8).
The communication with the control board of the frequency converter takes place through the stan-
dard Vacon Interface Board Connector.
3.1 RS-485 OPTC2 option board
Figure 1. Vacon RS-485 option board OPTC2
Signal
Connector
NC* 1* No connection
VP 2 Supply voltage plus (5V)
RxD/TxD –N 3 Receive/Transmit data – A
RxD/TxD –P 4 Receive/Transmit data – B
DGND 5 Data ground (reference potential for VP)
*You can use this pin (1) to bypass the cable shield to the next slave
Table 2. OPTC2 bus connector signals
X4
X1
Bus connector
Jumpers Interface board connector
Grounding plate
1
2
3
4
5
6 • vacon layout and connections
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
3
3.2 RS-485 OPTC8 option board
Figure 2. Vacon RS-485 option board OPTC8
Signal
Connector
Description
Shield 1 Cable shield
RxD/TxD-N 3 Receive/ A
DGND 5 Data ground (reference potential for VP)
VP 6 Supply voltage plus (5V)
RxD/TxD-P 8 Receive/ Transmit data/ B
Table 3. OPTC8 bus connector signals
X4
X1
Bus connector
Jumpers Interface board connector
Grounding plate
12345
9 8 7 6
layout and connections vacon 7
24-hour support +358 (0)40 8371 150 Email: va[email protected]
3
3.3 Grounding
3.3.1
Grounding by clamping the cable to the converter frame
This manner of grounding is the most effective and especially recommended when the distances be-
tween the devices are relatively short or if the device is the last device on
the net.
Note: Normally, the option board has already been installed in slot D or slot E of the control board. It
is not necessary to detach the whole board for the grounding of the bus cable shield. Just detach the
terminal block.
1 Strip about 5 cm of the cable and cut off the grey cable shield.
Remember to do this for both bus cables (except for the last device). See pictures below.
2 Leave no more than 1 cm of the cable outside the terminal block and strip the data cables at
about 0.5 cm to fit in the terminals. See pictures below.
Note: Do this for both bus cables.
Figure 3.
Figure 4.
3 Insert the data cables of both cables into terminals #3 (Line B) and #4 (Line A).
4 Strip the cable at such a distance from the terminal that you can fix it to the frame with the
grounding clamp. See
1 2 3 4 5
B
A
Cut here
Strip this part
8 • vacon layout and connections
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
3
Figure 5.
layout and connections vacon 9
24-hour support +358 (0)40 8371 150 Email: va[email protected]
3
3.3.2
Grounding only one point on the net
In this manner of grounding, the shield is connected to ground only at the last device on the net in the
same way as described in chapter 3.3.1. Other devices of the net just pass the shield.
We recommend you to use an Abico connector to fit the shields into the terminal.
1 Strip about 5 cm of the cable and cut off the grey cable shield. Remember to do this for both
bus cables (except for the last device).
2 Leave no more than 1 cm of the cable outside the terminal block and strip the data cables at
about 0.5 cm to fit in the terminals. See Figure 6.
Note: Do this for both bus cables.
Figure 6.
3 Fix both the cables on the frame with the clamp. See Figure 7.
Figure 7.
1 2 3 4 5
B
A
Shield
10 • vacon layout and connections
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
3
3.3.3
Grounding jumper X1
The Grounding jumper X1 on the OPTC8 is used for grounding selection. If position ON is selected it
means that the D-sub connector PIN1 is connected directly to ground. Selection of position OFF
means that PIN1 is connected to ground via an RC-filter. Jumper X1 has no effect on OPTC2.
Figure 8. Grounding jumper X1
X4
X1
ON
OFF
12345
9 8 7 6
layout and connections vacon 11
24-hour support +358 (0)40 8371 150 Email: va[email protected]
3
3.4 Bus terminal resistors
If Vacon is the last device of the fieldbus line the bus termination must be set. Use jumper X4 (ON po-
sition) or external termination resistors (e.g. in DSUB-9 connector). See Figure 9.
Figure 9. Using jumper X4 to set the bus termination.
X4
X1
12345
9 8 7 6
ON
OFF
12 • vacon layout and connections
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
3
3.5 Bus Biasing
Bus biasing is required to ensure faultless communication between devices at RS-485 bus. Bus bias-
ing makes sure that the bus state is at proper potential when no device is transmitting. Without bias-
ing, faulty messages can be detected when the bus is in idle state. RS-485 bus state should be
neather +0,200..+7V or –0,200..-7V. Illegal bus state is <200mV..-200mV.
Number of nodes Bias resistance
2-5 1.8 kohm
5-10 2.7 kohm
11-20 12 kohm
21-30 18 kohm
31-40 27 kohm
Table 4. Bias resistor size vs number of node
Fail safe
biasing in OPTC2 option board
Connect resistor biasing resistors between pins #2 and #4 as well as pins #3 and #5 as shown in pic-
ture.
Matters related to this are discussed in the application note
Failsafe Biasing of Differential Buses
(an-
847.pdf) published by National Semiconductor (www.national.com).
DATA-
DATA+
5
1
2
3
4
5
A
B
layout and connections vacon 13
24-hour support +358 (0)40 8371 150 Email: va[email protected]
3
3.6 LED indications
The two LED indications next to the connector show the present statuses of the RS-485 board (yellow)
and the Fieldbus Module (green).
Figure 10. LED indications on the RS-485 board
RS-485 board status LED (BS) YELLOW
LED is:
Meaning:
OFF Option board not activated
ON Option board in initialisation state waiting for activation
command from the frequency converter
Blinking fast
(once/sec)
Option board is activated and in RUN state
Option board is ready for external communication
Blinking
slow
(once/5 secs)
Option board is activated and in FAULT state
Internal fault of option board
Fieldbus status LED (FS) GREEN
LED is:
Meaning:
OFF Fieldbus module is waiting for parameters from the fre-
quency converter
No external communication
ON Fieldbus module is activated
Parameters received and module activated
Module is waiting for messages from the bus
Blinking fast
(once/sec)
Module is activated and receiving messages from the bus
Blinking
slow
(once/5 secs)
Module is in FAULT state
No messages from Master within the watchdog time
Bus broken, cable loose or Master off line
X4
X1
1
2
3
4
5
Yellow
Green
14 • vacon installation
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
4
4. INSTALLATION OF VACON NX RS-485 BOARD
A
Vacon NX frequency converter
B
Remove the cable cover.
C
Open the cover of the control unit.
installation vacon 15
24-hour support +358 (0)40 8371 150 Email: va[email protected]
4
D
Install RS-485 option board in slot E on the control board of the frequency con-
verter. Make sure that the grounding plate (see below) fits tightly in the clamp.
E
Make a sufficiently wide opening for
your cable by cutting the grid as wide as
necessary.
F
Close the cover of the control unit and
the cable cover.
X4
X1
1
2
3
4
5
16 • vacon modbus
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
5
5. COMMISSIONING
READ FIRST CHAPTER 8 'COMMISSIONING' IN VACON NX USER'S MANUAL (Document nr. ud00701,
please visit http://www.vacon.com/925.html).
Note! You must select Fieldbus as the active control place, if you wish to control the frequency con-
verter through fieldbus. See Vacon NX User’s Manual, Chapter 7.3.3.1.
5.1 Fieldbus board parameters
The Vacon RS-485 board is commissioned with the control keypad by giving values to appropriate pa-
rameters in menu
M7 (for locating the expander board menu see Vacon NX User's Manual, Chapter
7).
Expander board menu (M7)
The
Expander board menu
makes it possible for the user 1) to see what expander boards are con-
nected to the control board and 2) to reach and edit the parameters associated with the expander
board.
Enter the following menu level
(G#) with the
Menu button right
. At this level, you can browse through
slots A to E with the
Browser buttons
to see what expander boards are connected. On the lowermost
line of the display you also see the number of parameter groups associated with the board.
If you still press the
Menu button right
once you will reach the parameter group level where there are
two groups: Editable parameters and Monitored values. A further press on the
Menu button right
takes you to either of these groups.
RS-485 parameters
To commission the RS-485 board, enter the level P7.5.1.# from the
Parameters
group (G7.5.1). Give
desired values to all RS-485 parameters (see Figure 11 and Table 5).
Figure 11. Changing the RS-485 board commissioning parameter values
Expander Board
G1
G5
READY
I/Oterm
NXOPTC5
READY
I/Oterm
G1
G2
Slave address
READY
I/Oterm
126
enter
CHANGE VALUE
CONFIRM CHANGE
Parameters
READY
I/Oterm
P1
P4
Slave address
READY
I/Oterm
126
commissioning vacon 17
24-hour support +358 (0)40 8371 150 Email: va[email protected]
5
#
Name
Default
Range
Description
1 COMMUNICATION
PROTOCOL
1
1 Modbus RTU
2 N2
Protocol
2
SLAVE ADDRESS
1
1…247
3 BAUD RATE
6
1 300 baud
2 600 baud
3 1200 baud
4 2400 baud
5 4800 baud
6 9600 baud
7 19200 baud
8 38400 baud
Communication speed
When N2 protocol is used
Baudrate
must be set to 9600.
4 PARITY TYPE
0
0 – None
1 Even
2 Odd
Describes what kind of parity checking
is used.
When N2-protocol is used
Pari
ty
type
must be set to 0 = None
5 COMMUNICATION
TIMEOUT
20
0—OFF
1—300 s
See chapter Communication timeout
below
6 OPERATE MODE 1 1 Normal Reserved for later use
Table 5. RS-485 parameters
The parameters of every device must be set before connecting to the bus. Especially the parameters
Communication Protocol
,
Slave Address
and
Baud Rate
must be the same as in the master configura-
tion.
Communication timeout
The RS-485 board initiates a communication error if communication is broken for as long as defined
by the
Communication Timeout
.
Communication Timeout
is disabled when given the value 0.
Communication status
To see the present status of the RS-485 fieldbus, enter the
Comm.Status
page from
Monitor
menu
(G7.5.2). See Figure 12 and Table 6 below.
Figure 12. Communication status
Monitor
READY
I/Oterm
V1
V1
READY
I/Oterm
0.841
Comm. status
Error messages
Good messages
18 • vacon modbus
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
5
Good messages
0…999 Number of messages received without
communication errors
Error messages
0…64 Number of messages received with
CRC or parity errors
Table 6. RS-485 message indications
modbus vacon 19
24-hour support +358 (0)40 8371 150 Email: va[email protected]
6
6. MODBUS
6.1 Modbus RTU protocol, introduction
The MODBUS protocol is an industrial communications and distributed control system to integrate
PLCs, computers, terminals, and other monitoring, sensing, and control devices. MODBUS is a Mas-
ter-Slave communications protocol. The Master controls all serial activity by selectively polling one or
more slave devices. The protocol provides for one master device and up to 247 slave devices on a
common line. Each device is assigned an address to distinguish it from all other connected devices.
The MODBUS protocol uses the master-slave technique, in which only one device (the master) can
initiate a transaction. The other devices (the slaves) respond by supplying the request data to the
master, or by taking the action requested in the query. The master can address individual slaves or
initiate a broadcast message to all slaves. Slaves return a message (‘response’) to queries that are
addressed to them individually. Responses are not returned to broadcast queries from the master.
A transaction comprises a single query and single response frame or a single broadcast frame. The
transaction frames are defined below.
Master's
message
Slave
response
START
START
ADDRESS ADDRESS
FUNCTION FUNCTION
DATA
DATA
CRC
CRC
END
END
Figure 13. The basic structure of a Modbus frame
Valid slave device addresses are in the range of 0 ... 247 decimal. The individual slave devices are as-
signed addresses in the range of 1 ... 247. A master addresses a slave by placing the slave address in
the address field of the message. When the slave sends its response, it places its own address in this
address field of the response to let the master know which slave is responding.
The function code field of a message frame contains two characters (ASCII) or eight bits (RTU). Valid
codes are in the range of 1 ... 255 decimal. When a message is sent from a master to a slave device
the function code field tells the slave what kind of action to perform. Examples are to read the ON /
OFF states of a group of discrete coils or inputs; to read the data contents of a group of registers; to
20 • vacon modbus
Tel.+358 (0)201 2121 Fax +358 (0)201 212 205
6
read the diagnostic status of the slave; to write to designated coils or registers; or to allow loading,
recording, or verifying the program within the slave.
When the slave responds to the master, it uses the function code field to indicate either a normal (er-
ror-free) response or that some kind of error occurred (called an exception response). For a normal
response, the slave simply echoes the original function code. For an exception response, the slave
returns a code that is equivalent to the original function code with its most significant bit set to a logic
1.
The data field is constructed using sets of two hexadecimal digits, in the range of 00 to FF hexadeci-
mal. These can be made from a pair of ASCII characters, or from one RTU character, according to the
network's serial transmission mode.
The data field of messages sent from a master to slave devices contains additional information which
the slave must use to take the action defined by the function code. This can include items like discrete
and register addresses, the quantity of items to be handled, and the count of actual data bytes in the
field.
If no error occurs, the data field of a response from a slave to a master contains the data requested. If
an error occurs, the field contains an exception code that the master application can use to determine
the next action to be taken.
Two kinds of checksum are used for standard Modbus networks. The error checking field contents
depend upon the transmission method that is being used.
/