Bard LV1000-100 Installation Support Materials

Type
Installation Support Materials
Page 1 of 36
Bard Manufacturing Company, Inc.
Bryan, Ohio 43506
www.bardhvac.com
Date: 4-18-17
INSTALLATION
SUPPORT
MATERIALS
LV1000-100 CONTROLLER
Part of the Bard Free Cooling Unit System
NOTE: LV1000 Controller is required for operation when multiple
FUSION-TEC
TM
HR**AP wall-mount units are used.
Page 2 of 36
FIGURES AND TABLES
Figure 1.1 Typical LV1000 Component Location ........7
Figure 1.2 LV1000 Fused Power Supply Terminal ......8
Figure 1.3 Remote Indoor Sensor Installation ............ 9
Figure 1.4 Additional Remote Sensor Installation ....10
Figure 1.5 WIRING: Communication Wiring
(Daisy Chain Method) ............................ 12
Figure 1.6 WIRING: Communication Wiring
(Alternate Method) ................................12
Figure 1.7 Communication Wire Filter Placement ....13
Figure 1.8 WIRING: Communication Wiring:
Controller Termination ........................... 14
Figure 1.9 WIRING: Communication Wiring:
1st Unit Termination .............................15
Figure 1.10 WIRING: Communication Wiring:
Additional Unit Termination ...................16
Figure 1.11 Controller Circuit Install ........................17
Figure 1.12 Controller Grounding Posts ....................17
Figure 1.13 WIRING: LV1000 Wiring Diagram...........19
Figure 1.14 LV1000 Display and Interface ................ 20
Figuer 1.15 Quck Menu Icons .................................21
Figure 1.16 Setting Controller Date and Time ............ 21
Figure 1.17 Configuring Indoor Humidity 1 Sensor ....21
Figure 1.18 Configuring Indoor Humidity 2 Sensor ....22
Figure 1.19 Configuring Indoor Humidity 3 Sensor ....22
Figure 1.20 Configuring Indoor Temp 1 Sensor .......... 22
Figure 1.21 Configuring Indoor Temp 2 Sensor .......... 23
Figure 1.22 Configuring Indoor Temp 3 Sensor .......... 23
Figure 1.23 Entering Total Number of Units .............. 23
Figure 1.24 Verifying Units .....................................24
Figure 2.1 Adjusting Alarm Setpoints .....................26
Figure 2.2 Changing Input Values ..........................28
Figure 2.3 Adjusting Units Running When
Generator Is Active ...............................29
Figure 2.4 Adjusting Economizers Running When
Generator Is Active ...............................29
Figure 2.5 Changing Output Values ........................30
Figure 2.6 Adjusting Setpoints ..............................32
Figure 2.7 Adjusting Unit Rotation Parameters ........ 34
Figure 2.8 Adjusting Setpoints ..............................35
SECTION 1: Installation Instructions ......................................................................................................... 5
List of Necessary Materials/Tools ........................................................................................................................ 6
LV1000 Controller Installation ............................................................................................................................ 7
System Start-Up ............................................................................................................................................. 20
SECTION 2: Service Instructions ............................................................................................................... 25
Alarms ........................................................................................................................................................... 26
Alarm Adjustment ..................................................................................................................................... 28
Humidifier Output .................................................................................................................................... 31
Control Operation ............................................................................................................................................ 32
Temperature Control ................................................................................................................................. 33
Humidity Control ...................................................................................................................................... 34
Fan Control .............................................................................................................................................. 35
Hour Counting .......................................................................................................................................... 35
Additional Programming .................................................................................................................................. 36
CONTENTS
Table 1.1 Terminal Block Index ...............................18
Table 2.1 Temperature and Humidity Sensors ........... 26
Table 2.2 Cooling Staging ....................................... 33
Table 2.3 Heating Staging ......................................35
Free Cooling Unit System
This Bard Free Cooling Unit system is composed of FUSION-TEC wall-mounted air conditioners matched with an
LV1000 first on/next on controller. The wall mounts are specifically engineered for telecom/motor control center
rooms.
NOTE: The LV1000 controller and FUSION-TEC wall-mount units are designed specifically to work together. The
LV1000 controller cannot run other Bard models or other brands of systems, nor can other controllers run
the FUSION-TEC wall-mount units. They are a complete system, and must be used together.
Controller
LV1000 controller and accessories included shown below.
Remote Temperature/
Humidity Sensor*
(with 35' shielded cable)
Bard P/N 8403-079
Communication
EMI Filters
Bard P/N 8301-055
TEC-EYE
TM
Hand-Held
Diagnostic Tool
Bard P/N 8301-059
LV1000 Series
* One remote temperature/humidity sensor and 35' of shielded cable are included with the LV1000 controller.
Up to two additional remote temperature/humidity sensors can be purchased and installed. Temperature-only
sensors (Bard P/N 8301-058) may be used instead of the additional temperature/humidity sensors, but will
also need to be purchased separately.
LV1000 Series
Programmable Logic
Controller
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
These instructions should be carefully read before
beginning the installation. Note particularly any tags
and/or labels attached to the equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Additional Publications for information
on codes and standards.
Shipping Damage
Upon receipt of equipment, the cartons should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact
the last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
Additional Publications
These publications can help when installing the
furnace. They can usually be found at the local library
or purchased directly from the publisher. Be sure to
consult the current edition of each standard.
National Electrical Code ......................ANSI/NFPA 70
Standard for the Installation of Air Conditioning
and Ventilating Systems ...................ANSI/NFPA 90A
Standard for Warm Air Heating
and Air Conditioning Systems ............ANSI/NFPA 90B
Page 3 of 36
GENERAL INFORMATION
Load Calculation for Residential Winter
and Summer Air Conditioning ............. ACCA Manual J
Duct Design for Residential Winter and Summer
Air Conditioning and Equipment Selection
....................................................... ACCA Manual D
For more information, contact these publishers:
Air Conditioning Contractors of America (ACCA)
1712 New Hampshire Ave. N.W.
Washington, DC 20009
Telephone: (202) 483-9370 Fax: (202) 234-4721
American National Standards Institute (ANSI)
11 West Street, 13th Floor
New York, NY 10036
Telephone: (212) 642-4900 Fax: (212) 302-1286
American Society of Heating, Refrigeration and Air
Conditioning Engineers, Inc. (ASHRAE)
1791 Tullie Circle, N.E.
Atlanta, GA 30329-2305
Telephone: (404) 636-8400 Fax: (404) 321-5478
National Fire Protection Association (NFPA)
Batterymarch Park
P. O. Box 9101
Quincy, MA 02269-9901
Telephone: (800) 344-3555 Fax: (617) 984-7057
Page 4 of 36
ANSI Z535.5 Definitions:
DANGER: Indicate[s] a hazardous situation which, if
not avoided, will result in death or serious injury. The
signal word “DANGER” is to be limited to the most
extreme situations. DANGER [signs] should not be used
for property damage hazards unless personal injury risk
appropriate to these levels is also involved.
WARNING: Indicate[s] a hazardous situation which,
if not avoided, could result in death or serious injury.
WARNING [signs] should not be used for property
damage hazards unless personal injury risk appropriate
to this level is also involved.
CAUTION: Indicate[s] a hazardous situation which, if
not avoided, could result in minor or moderate injury.
CAUTION [signs] without a safety alert symbol may be
used to alert against unsafe practices that can result in
property damage only.
NOTICE: [this header is] preferred to address practices
not related to personal injury. The safety alert symbol
shall not be used with this signal word. As an
alternative to “NOTICE” the word “CAUTION” without
the safety alert symbol may be used to indicate a
message not related to personal injury.
SECTION 1:
INSTALLATION
INSTRUCTIONS
Page 5 of 36
LIST OF NECESSARY MATERIALS/TOOLS
Additional hardware and miscellaneous supplies are needed for installation. These items are field supplied and must
be sourced before installation. This list also includes tools needed for installation.
List of Materials/Tools
Personal protective equipment/safety devices
Miscellaneous hand and power tools and jobsite or
shop materials
Electrical supplies:
- Circuit breaker for the shelter AC breaker
box (see unit electrical specifications for
requirements)
- 16 gauge minimum, 14 gauge maximum
power wire to connect controller to shelter
power source
- Communication wire: 2-wire, 18 gauge,
shielded with drain
- 5-wire, 18 gauge shielded cable with drain for
remote temperature and humidity sensors
- 18 gauge non-shielded wire for connecting
smoke detector, hydrogen detector and/or
generator, if applicable, to controller
-
CAT 6 Ethernet cable of field-determined length
(for remote communication, if applicable)
- Miscellaneous electrical supplies including
rigid/flexible conduit and fittings, 2" x 4"
junction boxes (one per temperature/humidity
sensor), wire connectors and supports
- Fasteners appropriate for the shelter wall
construction to attach the controller to the wall
The following is required and must be sourced prior
to installation of these units.
One (1) 5A circuit breaker for the shelter DC
power plant (for the controller)
Circuit breakers for Emerson Network Power (ENP)
power plants (used in most telecomm shelters built
today) are available directly through the following
distributors:
Emerson Network Power: 440.288.1122
Master Electronics: 888.473.5297 or
www.onlinecomponents.com
Emerson Network Power (ENP) Part Number
5A circuit breaker: P/N 101598
Always confirm the application before ordering.
Page 6 of 36
LV1000 CONTROLLER INSTALLATION
FIGURE 1.1
Typical LV1000 Component Location
Control Board
RJ11 Cable
to Display
-48VDC to 24V
Power Supply
USB
Connection
Terminal Block
Power Supply
Connections
Shelter Inputs
and Outputs
Power Loss Relay
Page 7 of 36
1. Mounting the LV1000 Controller
Because the LV1000 controller utilizes a remote
temperature sensor as opposed to one located in the
controller box, the controller itself can be installed in
any indoor location that is suitable, preferably at eye
level. Four (4) mounting holes are provided for mounting
to the wall and holes for conduit connection are provided
in both the base, sides and top of the controller.
The LV1000 controller includes a fused power supply
terminal in the terminal block. Before connecting wires
to the terminal block, confirm that the fuse in the fuse
holder is in the proper position (active) as shown in
Figure 1.2.
Electrical shock hazard.
Disconnect VAC and VDC power supplies
before servicing.
Failure to do so could result in electric shock
or death.
!
WARNING
LV1000 Controller
The LV1000 controller is part of the Free Cooling
Unit system by Bard. It is used to control up to four
(4) wall-mount air conditioners from one controller.
The microprocessor control provides an easy-to-read
interface with large LCD graphical display. It provides
control for redundancy for the structure and equal wear
on all units. The LV1000 controller is configured for
first on/next on sequence.
Conduit is recommended for all wiring. Route
communication wiring and power supply wiring in their
own separate conduits.
The LV1000 controller is not weatherproof and is
intended for use in weathertight structure.
FIGURE 1.2
LV1000 Fused Power Supply Terminal
Shipping Position
Fuse in Active Position
Page 8 of 36
1 2 3
4 5 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 466
DP1
DP2
2. Installing Remote Indoor Temperature/Humidity Sensor(s)
One remote indoor temperature/humidity sensor and 35' of 18 gauge shielded cable is included with the controller.
This sensor must be installed for proper operation. Mount the temperature/humidity sensor in a location least likely to
be affected by open doors, rack-mounted fans, radiant heat sources, etc. Location height should be approximately 60"
above the floor. The sensor should be installed on a 2" x 4" junction box to allow for control wire conduit (see Figure
1.3). Use shielded cable to connect to controller.
FIGURE 1.3
Remote Indoor Temperature/Humidity Sensor Installation
1. Connect wires from the 18 gauge shielded cable to terminals #24, #25, #18, #19 and #30.
2. Connect the other end of the shielded cable to the sensor
terminals. Be sure wires are connected to proper terminals
as shown in table above. Sensor jumpers need to be
positioned for 0-1 V. With sensor oriented as shown in
image to right, move both jumpers to left position (DP1 and
DP2 set to OFF).
This applies to all temperature/humidity sensors connected
to the LV controller.
Sensor is best mounted on a junction box, and it is
recommended that the cable be in conduit.
TB#
Wire
Mark
Sensor Description
24 B6 NTC OUT Indoor Temperature 1
25 GND NTC OUT Ground
18 B2 OUT H Indoor Humidity 1 Signal: 0-1 VDC
19 GND M (G) Indoor Humidity 1 Common
30 +VDC + (G) Indoor Humidity 1 Power
Jumper
Page 9 of 36
Up to two additional temperature/humidity sensors may be added. Be sure the sensors are connected to the proper
terminals on the terminal block and sensor as listed below. See page 9 for information on correct sensor jumper
position.
FIGURE 1.4
Additional Remote Temperature and Temperature/Humidity Sensor Installation
For proper operation, the remote indoor temperature/humidity sensor must be configured properly with the
controller. If only the single remote indoor temperature/humidity sensor supplied with the controller is installed,
the configuration setting is "0". This is the default setting. Up to two additional temperature and humidity sensors
can be purchased and installed. Alternately, temperature-only sensors can be purchased and installed instead of
the combination sensors. For information on remote indoor sensor configuration, see page 21.
Use shielded cable to
connect additional sensors to controller.
#3
Optional Remote
Temperature/Humidity Sensor
Terminals 28, 29, 22, 23 & 32
TB#
Wire
Mark
Sensor Description
28 B8 NTC OUT Indoor Temperature 3
29 GND NTC OUT Ground
22 B4 OUT H Indoor Humidity 3 Signal: 0-1 VDC
23 GND M (G) Indoor Humidity 3 Common
32 +VDC + (G) Indoor Humidity 3 Power
#2
Optional Remote
Temperature/Humidity Sensor
Terminals 26, 27, 20, 21 & 31
TB#
Wire
Mark
Sensor Description
26 B7 NTC OUT Indoor Temperature 2
27 GND NTC OUT Ground
20 B3 OUT H Indoor Humidity 2 Signal: 0-1 VDC
21 GND M (G) Indoor Humidity 2 Common
31 +VDC + (G) Indoor Humidity 2 Power
Temperature-only sensors can be used in place of the additional temperature/humidity sensors. #2 temperature-only sensor
will connect to TB# 26 and 27. #3 temperature-only sensor will connect to TB# 28 and 29. The wire connections for the
temperature-only sensors are not polarity sensitive.
1 2 3 4 5 7 8 9 10 11
12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
6
3
2
3
3 3
3
2
2
2
2
Page 10 of 36
3. Additional LV1000 Connections
There are factory-installed jumpers across terminals #8 and #9 (smoke detector), #10 and #11 (hydrogen detector)
and #12 and #13 (generator run). Remove the factory-installed jumpers before connecting to the detectors and/or
generator (if applicable).
INPUTS
LV1000 Connections Sensor Connections
Description
Wire Mark Terminal Terminal
Smoke
DI1 8
Varies by sensor used. See general
wiring guideine in Figure x.x
Smoke Detector Input
GND 9 Ground
Hydrogen
DI2 10 Hydrogen Detector Input
GND 11 Ground
Generator
DI3 12 Generator Run Input
GND 13 Ground
Anti-Theft
DI4 14 Anti-Theft Device
GND 15 Ground
Power Loss
Relay - A1 230VAC Power Loss Relay
Relay - A2 230VAC Power Loss Relay
OUTPUTS
LV1000 Connections
External
Connections
Description
Wire Mark Terminal Terminal
Humidifier
NO1 34
Varies. See general wiring
guideine in Figure x.x
Humidifier Output
C1 35 Common
HVAC Fail
NO2 36 Alarm Relay – HVAC Fail
C1 37 Common
HVAC Maintenance
NO3 38
Alarm Relay –
HVAC Maintenance
C1 39 Common
Anti-Theft
NO4 40 Alarm Relay – Anti-Theft
C2 41 Common
COMMUNICATIONS
LV1000 Connections
External
Connections
Description
Wire Mark Terminal Terminal
Fieldbus 1*
FB-1 (–) 42 1 Wall Unit Daisy Chain
FB-1 (+) 43 2 Wall Unit Daisy Chain
Fieldbus 2*
FB-2 (–) 44 IPv6 SNMP Board
FB-2 (+) 45 + Ground
Ground FB-2 (–) 46 Shield Shield for Daisy Chain
* Polarity Sensitive
Page 11 of 36
4. Communication Wiring
Connect the communication wiring from the wall-mount units to the controller in the manner shown in Figures 1.5,
1.6 or 1.7. The communication wire should be 2-wire, 18 gauge shielded cable with drain. Any color can be used.
Be sure to match "+" and "-" symbols on controller terminal blocks to prewired unit control terminal block (see
Figures 1.9 and 1.10 on pages 15 and 16). Attach communication wire filters as shown in Figures 1.5, 1.6 or 1.7.
Filters go inside the unit or controller box; they are shown out of unit for identification purposes only. Do not run
communication wiring in same conduit as supply wiring.
Route communication wiring and power supply wiring in
their own separate conduits.
FIGURE 1.6
Communication Wiring (Alternate Method)
Filter
Filter
Wall-Mount Unit
Wall-Mount Unit
LV
Controller
In addition to the "daisy chain" method of connecting the communication wiring shown in Figure 1.5, the wall-mount
units can also be connected in the manner shown in Figure 1.6. If connecting wall-units this way, be sure to place
the communication wire filters in the positions shown in Figure 1.6. See Figure 1.7 for more information on the
correct placement of the communication wire filters depending on the wiring method used.
LV1000 Controller
Wall-Mount Unit
Wall-Mount Unit
FIGURE 1.5
Communication Wiring (Daisy Chain Method)
Filter
Filter
Page 12 of 36
FIGURE 1.7
Placement of Communication Wire Filters (Daisy Chain and Alternate Methods)
LV1000
* LV1000 can be in any position other than start and end
Place filter here
Daisy Chain Wiring (up to four units)
Alternate Wiring (up to four units)
Unit 1 Unit 2 Unit 3 Unit 4
Place filter here
Unit 1 Unit 2 Unit 3 Unit 4
LV1000*
Place filter here
Place filter here
NOTE: Line filters can be on either the unit or controller, whichever device is on the end of the chain. No matter
how many units there are, the two end devices will only have ONE communication cable, whereas the
center devices will all have TWO (as shown above). Filters go inside the unit or controller; shown out of
unit above for identification only.
Page 13 of 36
1. Using the field-provided shielded cable, make a small service loop after entering the controller and attach the provided
EMI filter at the intersection of the loop.
FIGURE 1.8
Communication Wiring: Termination at the Controller
2. Connect one wire to terminal #44 (NEGATIVE), the other wire to terminal #45 (POSITIVE) and the drain wire to
ground terminal #46.
The steps outlined on the following pages show how to connect the communication wiring using the daisy chain
method shown in Figure 1.5. If using the alternate method (as shown in Figure 1.6), the connections to the
controller and each wall-mount unit will be the same but the filters need to be placed in the positions shown in
Figure 1.7.
- + G
To Wall-Mount Unit 1
Control Board RS485
1 2 3 4 5 7 8 9 10 11 12 13 14 15 16 17 18 19
20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
6
NOTE: The drain only gets grounded one time,
anywhere in the chain.
Page 14 of 36
FIGURE 1.9
Communication Wiring: Termination at the First Wall-Mount Unit
1. From the controller, extend the shielded cable through a separate conduit
and route to the provided terminal block next to the wall-mount control
board.
Note that the terminal block label is clearly marked “+” and “-”. These
connections are polarity-sensitive. Two-wire communication from control
board is prewired to terminal block. Make sure to match "+" and "-"
symbols on controller terminal block.
2. Connect the wires matching the terminal
designations (+/-) of the controller
terminals. Leave the drain wire loose.
3. Connect another cable in a similar
fashion (“daisy chain”) to route in
conduit to the second wall-mount unit.
Connect both drain wires with wire nut.
From LV1000
Controller
1 2 4 5 7 9 108 12 14 16 173 6
11
13 15
Unit 1 Terminal Block
From LV1000
Controller
1 2 4 5 7 9 108 12 14 16 173 6
11
13 15
Unit 1 Terminal Block
To Wall-Mount Unit 2
From LV1000
Controller
1 2 4 5 7 9 108 12 14 16 173 6
11
13 15
Unit 1 Terminal Block
Wall-Mount Unit 1
+
+
+
Page 15 of 36
1. Route the cable from the first wall-mount unit to the
terminal block of the second wall-mount unit. If this is
the last unit to be connected, make a small service loop
and attach EMI filter as shown.
FIGURE 1.10
Communication Wiring: Termination at Additional Wall-Mount Units
2. Connect the wires matching the terminal
designations (+/-) of the controller terminals.
Cap the loose drain with a wire nut or
electrical tape.
3. Continue daisy chaining units by connecting
"+" to "+", "-" to "-" and wire nutting drain
together until last unit which is capped with
a wire nut. Attach EMI filter as shown above
at last unit. Up to four wall-mount units can
be connected and controlled by one LV1000
controller.
From Wall-Mount
Unit 1
1 2 4 5 7 9 108 12 14 16 173 6
11
13 15
Unit 2 Terminal Block
Wall-Mount Unit 2
From Wall-Mount
Unit 1
1 2 4 5 7 9 108 12 14 16 173 6
11
13 15
Unit 2 Terminal Block
+
+
Page 16 of 36
FIGURE 1.12
Controller Grounding Posts
A reliable earth ground must be connected in
addition to any grounding from conduit. Attach
earth ground to dedicated lugs on side of controller
box. Failing to ground the controller box properly
could result in damage to the equipment.
FIGURE 1.11
LV1000-100 Controller Supply Wiring
The controller requires a separate -48VDC power supply, an additional 5-amp DC breaker (field supplied) and minimum 16
gauge supply wire.
-48VDC termination at controller: Bring the -48VDC power supply wires through conduit to the controller box. Land the
positive (+) 48VDC wire to terminal #1 and the negative (-) 48VDC wire to terminal #2.
NOTE: If the DC wiring is not terminated correctly on the specific polarity-indicated terminals of the
block, the controller will not activate and will not function. Verify polarity of connections and wait to
initialize controller until "system start up."
5. Supply Wiring
The LV1000 controller is powered by -48VDC from the shelter. A field-supplied 5 amp DC circuit breaker is required.
Field-supplied supply wiring should be minimum 16 gauge, maximum 14 gauge (see Figure 1.11). A reliable
earth ground must be connected in addition to any grounding from conduit. Grounding posts are included with the
controller for this purpose; install as shown in Figure 1.12. Failing to ground the controller box properly could result
in damage to the equipment.
1 2 3 4 5 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 466
+
Page 17 of 36
TABLE 1.1
Terminal Block Index
TB#
Wire
Mark
Description
1 48+ 48VDC +Input
2 48– 48VDC – Input
3 - Ground
4 - 24VDC +
5 - 24VDC –
6 24+ 24VDC +
7 24– 24VDC –
8 DI1 Smoke Detector Input
9 GND Smoke Detector Common
10 DI2 Hydrogen Detector Input
11 GND Hydrogen Detector Common
12 DI3 Generator Run Input
13 GND Generator Run Common
14 DI4 Anti Theft Input
15 GND Anti Theft Common
16 - RESERVED FOR POWER LOSS INPUT
17 GND
RESERVED FOR POWER LOSS INPUT –
COMMON
18 B2 Humidity Sensor 1
19 GND Ground
20 B3 Humidity Sensor 2
21 GND Ground
22 B4 Humidity Sensor 3
23 GND Ground
TB#
Wire
Mark
Description
24 B6 Temperature Sensor 1
25 GND Ground
26 B7 Temperature Sensor 2
27 GND Ground
28 B8 Temperature Sensor 3
29 GND Ground
30 VDC+ Sensor Power Distribution
31 VDC+ Sensor Power Distribution
32 VDC+ Sensor Power Distribution
33 VDC+ Sensor Power Distribution
34 NO1 Humidifier Output Relay
35 C1 Common
36 NO2 HVAC Fail
37 C1 Common
38 NO3 HVAC Maintenance
39 C1 Common
40 NO4 HVAC Anti Theft
41 C2 Common
42 FB1R- RS485 RX- / TX- (Fieldbus 1)
43 FB1R+ RS485 RX+ / TX+ (Fieldbus 1)
44 FB2R- RS485 RX- / TX- (Fieldbus 2)
45 FB2R+ RS485 RX+ / TX+ (Fieldbus 2)
46 - Ground Communication Shield
Page 18 of 36
FIGURE 1.13
LV1000 Wiring Diagram
Page 19 of 36
SYSTEM START-UP
Before the Bard Free Cooling Unit system can be set up
for operation, each wall-mount unit must have already
been installed, given a unique address and had a run
test performed (see FUSION-TEC manual 2100-670).
After those procedures have been completed with each
unit, the system start-up can proceed.
The LV1000 controller will be used to set up the Bard
Free Cooling Unit system.
LV1000 Controller
The microprocessor control used in the FUSION-
TEC wall-mount air conditioners allows for complete
control and monitoring through the use of the LV1000
controller.
The menu driven interface provides users the ability
to scroll through two menu levels: Quick Menu and
Main Menu. The menus permit the user to easily view,
control and configure the wall-mount unit system.
The controller is completely programmed at the factory;
the default setpoints and their ranges are easily
viewed and adjusted from the controller display. The
program and operating parameters are permanently
stored on FLASH-MEMORY in case of power failure.
The controller is designed to manage temperature and
humidity levels to a user-defined setpoint via control
output signals to the wall-mount air conditioning
system.
ALARM KEY
Allows viewing of active alarms
Silences audible alarms
Resets active alarms
MENU KEY
Allows entry to Main Menu
ESCAPE KEY
Returns to previous menu level
Cancels a changed entry
UP KEY
Steps to next screen in the display
menu
Changes (increases) the value of a
modifiable field
ENTER KEY
Accepts current value of a
modifiable field
Advances cursor
DOWN KEY
Steps back to previous screen in
the display menu
Changes (decreases) the value of
a modifiable field
DOWN KEY
ALARM KEY
MENU KEY
UP KEY
ENTER KEY
ESCAPE KEY
FIGURE 1.14
LV1000 Controller Display and Interface
TEC-EYE
TM
interface key functions are the same as above.
The TEC-EYE
TM
diagnostic tool is shipped inside the
controller. See FUSION-TEC manual 2100-670 for
more information on using the TEC-EYE
TM
.
LV1000 Menu Structure
Quick Menu
Data Log
Unit Information
Setpoints
Main Menu
System Configuration
Advanced System Configuration
I/O Configuration
On/Off
Alarm Logs
Settings
Logout
In addition to the menu structure above, there are also
Status and Alarm screens.
Interface Acronyms
MAT – Mixed air temperature
RAT – Return air temperature
SAT – Supply air temperature
OAT – Outdoor air temperature
OAH – Outdoor air humidity
Blower – Indoor Blower Status
Damper – Free cooling damper position status
Page 20 of 36
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36

Bard LV1000-100 Installation Support Materials

Type
Installation Support Materials

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI