  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 310, P318 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort310,applicationP318
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................18
2.3Mounting...........................................................19
2.4Placingthetemperaturesensors................................23
2.5Electricalconnections.............................................25
2.6InsertingtheECLApplicationKey..............................31
2.7Checklist............................................................37
2.8Navigation,ECLApplicationKeyP318.........................38
3.0Dailyuse.........................................................46
3.1Howtonavigate...................................................46
3.2Understandingthecontrollerdisplay..........................47
3.3Ageneraloverview:Whatdothesymbolsmean?...........48
3.4Monitoringtemperaturesandsystem
components........................................................49
3.5Manualcontrol.....................................................50
3.6Schedule............................................................51
4.0Settingsoverview............................................52
5.0Settings...........................................................54
5.1IntroductiontoSettings..........................................54
5.2Tanktemperature..................................................55
5.3Flowtemperature..................................................59
5.4Returnlimit.........................................................61
5.5Controlparameters................................................65
5.6Flowmeter..........................................................75
5.7Application.........................................................76
5.8Anti-bacteria........................................................78
6.0Event...............................................................80
6.1IntroductiontoEvent.............................................80
6.2ChargeT.............................................................81
6.3DHWowT.........................................................84
6.4Tanktemperature..................................................87
6.5SupplyT.............................................................90
6.6Anti-bacteria........................................................91
6.7Tsensordefect.....................................................92
6.8Eventoverview.....................................................93
7.0Commoncontrollersettings..............................94
7.1Introductionto‘Commoncontrollersettings................94
7.2Time&Date.........................................................95
7.3Inputoverview.....................................................96
7.4Log...................................................................97
7.5Outputoverride....................................................98
7.6Keyfunctions.......................................................99
7.7System.............................................................101
8.0Miscellaneous................................................108
8.1ECA30/31setupprocedures.................................108
8.2Severalcontrollersinthesamesystem......................116
8.3Frequentlyaskedquestions....................................119
8.4Denitions........................................................121
8.5Type(ID6001),overview.......................................124
8.6ParameterIDoverview..........................................125
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK1
OperatingGuideECLComfort310,applicationP318
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwiththeECLApplicationKey
P318(codeno.087H3835).
TheECLApplicationKeyP318containstwosubtypes:
P318.1,whichisabuffer-basedDomesticHotWater(DHW)
application.
P318.10,whichisanadvancedDomesticHotWater(DHW)
application.
SeetheInstallationGuideforelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310whichalso
allowsM-bus,ModbusandEthernet(Internet)communication.
TheApplicationKeyP318complieswithECLComfort310
controllersasofrmwareversion1.11.Thermware(controller
software)isvisibleatstart-upofthecontrollerandin'Common
controllersettings'in'System'.
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connected.
TheapplicationP318workswithadditionalInternalI/Omodules:
TheextensionmoduleECA32gives0-10Voltsignalforspeed
controlofcontrolpump,chargingpumpandcirculationpump.
TheextensionmoduleECA35gives0-10Voltsignalforspeed
controlofcontrolpump,chargingpumpandcirculationpump.
ECA35canalsogivePWM*signalforspeedcontrolofthe
abovelistedpumptypes.
Apumpcanalsobeconsideredasacirculator.
TheECLComfort310workswitheitheroneECA32oroneECA
35.TheInternalI/Omoduleinquestionisplacedinthebasepart
oftheECLComfort310.
*PWM=PulseWidthModulation
TogetherwiththeECLComfort310theadditionalInternalI/O
modulescanalsobeusedforextradatacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Digitalinput
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>Products>
DistrictHeatingandCooling>Documentation>Tools&Software
>ECLTool.
TheURLis:http://district-heating.danfoss.com/download/tools/
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(codeno.087H3040)
ECLComfort310B,230volta.c.(codeno.087H3050)
ECLComfort310,24volta.c.(codeno.087H3044)
TheB-typehasnodisplayanddial.
2
DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
TheB-typeisoperatedbymeansoftheremotecontrolunit
ECA30/31:
ECA30(codeno.087H3200)
ECA31(codeno.087H3201)
InternalI/Omodules:
ECA32(codeno.087H3202)
ECA35(codeno.087H3205)
BasepartforECLComfort310,230voltand24volt:Codeno.
087H3230.
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK3
OperatingGuideECLComfort310,applicationP318
Automaticupdateofcontrollersoftware(rmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1
Parameterno.
12174
1
2
174
-
Circuit2
Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
4DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK
5
OperatingGuideECLComfort310,applicationP318
2.0Installation
2.1Beforeyoustart
TheECLapplicationkeyP318containstwosubtypes,P318.1and
P318.10.
ThebasicprinciplesforapplicationP318.1:
TemperaturecontrolofDHWbuffer
ThedesiredDHWtemperatureatS6determinesthebuffercharging
procedure.ThebuffertemperaturesensorsS6andS8,thesupply
temperaturesensorS2andthechargingtemperaturesensorS3are
themostimportantsensorsandmustbeconnected.Ifoneofthe
mentionedtemperaturesensorsisnotconnected,thecontrolvalve
M1willclose;alternatively,thecontrolpumpP1/V1willstop.
ThechargingtemperatureatS3isbasedonthedesiredDHW
temperatureatS6andasetchargingdifference.
TheapplicationallowsinternalorexternalDHWcirculation.When
connectedforexternalcirculation,thedesiredS3temperatureis
thesameasthedesiredDHWtemperature,whenchargingisnot
inprogress.
Optional:TemperaturecontrolofthecirculationpipeatS9ensures
thedesiredtemperaturebymeansofON/OFFcontrolofP3or
speedcontrolofV3.Duringthechargingprocessthecirculation
pumpcanbeswitchedOFForrunataminimumspeed.
Startbufferchargingprocess:
1.BuffertemperatureS6temperaturegetslowerthan('Desired
DHWtemperature'+'Startdifference').
Anexample:60°C+(-5)=55°C
2.X1isswitchedON
3.M1openstoapresetposition(alternatively,P1/V1isswitched
ON/presetspeed)inordertoincreasethesupplytemperature
S2.Returntemperaturelimitationisrespected.
4.P2/V2isswitchedONwhensupplytemperatureS2getshigher
than('DesiredDHWtemperature'+'Pumpstartdiff.').
Anexample:60°C+3K=63°C
V2startswithminimumspeed,forexample20%.
5.M1(orP1/V1)controlsthechargingtemperatureatS3.
6.V2increasesthespeedaslongasthechargingtemperatureS3
ishigherthan(desiredchargingtemperature-2K).
Stopbufferchargingprocess:
1.BuffertemperatureS6temperaturegetshigherthan(2K+
'DesiredDHWtemperature'+'Startdifference)
AND
LowerbuffertemperatureS8getshigherthan('DesiredDHW
temperature'+'Stopdifference).
Anexample:S6temperaturehigherthan(2+60°C+(-5)=
57°C)AND(60°C+(-8)=52°C)
2.P2isswitchedOFF,respecting'Char.Ppost-run'.V2changes
to0%.
NOTE:Post-runisnotrespectedifchargingtemperatureS3islower
thandesiredchargingtemperature.
3.X1isswitchedOFF.
4.M1closes(alternatively,P1/V1stops)ormaintainsthedesired
temperatureatS3.
P318.1,ex.a,applicationwithcontrolvalveandinternalDHWcirculation:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Buffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
DHWcirculationreturntemperaturesensor
S12
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm
6DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
Bymeansofaweekschedule,theDHWcirculationcanbeON/
OFFcontrolled.
ThemotorizedcontrolvalveM1isopenedgraduallywhen
thechargingtemperatureislowerthanthedesiredcharging
temperatureandviceversa.
Alternatively,thecontrolpumpP1/V1isincreasedinspeedwhen
thechargingtemperatureislowerthanthedesiredcharging
temperatureandviceversa.
ThereturntemperatureS5canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredchargingtemperatureatS3canbe
adjusted(typicallytoalowervalue);thisresultsinagradualclosing
ofthemotorizedcontrolvalveor,alternatively,alowerspeedof
thecontrolpump.
TheON-OFFoutputX1isONatDHWheatingdemand.
Asanoption,thedesiredDHWtemperaturecanbesetexternally.
Avoltagesignal(1-10Volt)canbeappliedtoinputS12(ECA32/
35).Thescaleforvoltageversustemperaturecanbeset.
Ananti-bacteriafunctionfortheDHWbufferisavailablefor
activationonselecteddaysoftheweek.
Theanti-bacteriafunctioncanbesettoincludetheDHW
circulation.
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK7
OperatingGuideECLComfort310,applicationP318
P318.1,ex.b,applicationwithcontrolvalveandexternalDHWcirculation:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Buffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
DHWcirculationreturntemperaturesensor
S12
0-10VinputfordesiredtemperatureatS6
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
X1
Heatdemandsignal
A1
Alarm
8DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
P318.1,ex.c,applicationwithcontrolpumpandinternalDHWcirculation:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Buffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
DHWcirculationreturntemperaturesensor
S12
0-10VinputfordesiredtemperatureatS6
P1
Controlpump(ON-OFFcontrolled)
V1
Speedcontrolofcontrolpump(010VorPWM)
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
X1
Heatdemandsignal
A1
Alarm
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK9
OperatingGuideECLComfort310,applicationP318
P318.1,ex.d,applicationwithcontrolpumpandexternalDHWcirculation:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Buffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
DHWcirculationreturntemperaturesensor
S12
0-10VinputfordesiredtemperatureatS6
P1
Controlpump(ON-OFFcontrolled)
V1
Speedcontrolofcontrolpump(010VorPWM)
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
X1
Heatdemandsignal
A1
Alarm
10DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
P318.1,ex.e:Primarysideisacombinationofa3-portcontrolvalveanda
controlpump.InternalDHWcirculation:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Buffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
DHWcirculationreturntemperaturesensor
S12
0-10VinputfordesiredtemperatureatS6
M1
Motorized3-portcontrolvalve(3-pointcontrolled)
P1
Controlpump(ON-OFFcontrolled)
V1
Speedcontrolofcontrolpump(010VorPWM)
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
X1
Heatdemandsignal
A1
Alarm
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK11
OperatingGuideECLComfort310,applicationP318
P318.1,ex.f:Primarysideisacombinationofa3-portcontrolvalveanda
controlpump.ExternalDHWcirculation:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
(mandatory)Supplytemperaturesensor
S3
(mandatory)Chargingtemperaturesensor
S5
Returntemperaturesensor
S6
(mandatory)Buffertemperaturesensor
S8
(mandatory)Lowerbuffertemperaturesensor
S9
DHWcirculationreturntemperaturesensor
S12
0-10VinputfordesiredtemperatureatS6
M1
Motorized3-portcontrolvalve(3-pointcontrolled)
P1
Controlpump(ON-OFFcontrolled)
V1
Speedcontrolofcontrolpump(010VorPWM)
P2
Chargingpump(ON-OFFcontrolled)
V2
Speedcontrolofchargingpump(0-10VorPWM)
P3
Circulationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
X1
Heatdemandsignal
A1
Alarm
12
DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
ThebasicprinciplesforapplicationP318.10:
TemperaturecontrolofDHW
ThedesiredDHWtemperatureatS3determinesthetemperature
control.
TheDHWowtemperaturesensorS3andtheDHWcirculation
returntemperaturesensorS9arethemostimportantsensorsand
mustbeconnected.IfS3isnotconnected,thecontrolvalveM1will
close;alternatively,thecontrolpumpP1/V1willstop.IfS9isnot
connected,theDHWcirculationpumpwilloperateat100%.
TemperaturecontroloftheDHWcirculationpipeatS9ensuresthe
desiredtemperaturebymeansofspeedcontrolofV3.
ThemotorizedcontrolvalveM1isopenedgraduallywhenthe
DHWowtemperatureislowerthanthedesiredDHWtemperature
andviceversa.
Alternatively,thecontrolpumpP1/V1isincreasedinspeedwhen
theDHWowtemperatureislowerthanthedesiredDHWow
temperatureandviceversa.
ThereturntemperatureS5canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredDHWtemperatureatS3canbeadjusted
(typicallytoalowervalue);thisresultsinagradualclosingofthe
motorizedcontrolvalveor,alternatively,alowerspeedofthe
controlpump.
ThesupplytemperatureS2isusedtocompensatetheproportional
bandXpinordertoimprovethetemperaturecontrolatdifferent
supplytemperatures.
ThewaterowsignalfromF1canbeusedtooverridethecontrol
valveinordertooptimizetheDHWtemperaturecontrol.This
pro-activefunctionalitycompensatesforthedelaybeforetheow
temperaturesensorS3measuresachangeintemperature.
Asanoption,thedesiredDHWtemperaturecanbesetexternally.
Avoltagesignal(1-10Volt)canbeappliedtoinputS12(ECA32/
35).Thescaleforvoltageversustemperaturecanbeset.
Ananti-bacteriafunctionfortheDHWcircuitisavailablefor
activationonselecteddaysoftheweek.Theanti-bacteriafunction
canbesettoincludetheDHWcirculation.
P318.10,ex.a,DHWapplicationwithcontrolvalve:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
Supplytemperaturesensor
S3
(mandatory)DHWowtemperaturesensor
S5
Returntemperaturesensor
S9
(mandatory)DHWcirculationreturntemperature
sensor
S12
0-10VinputfordesiredtemperatureatS3
F1
ColdWatermeter(pulsesignal)
P3
Speedcontrolofchargingpump(0-10VorPWM)
P3
DHWcirculationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
A1
Alarm
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK13
OperatingGuideECLComfort310,applicationP318
P318.10,ex.b,DHWapplicationwithcontrolpump:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
Supplytemperaturesensor
S3
(mandatory)DHWowtemperaturesensor
S5
Returntemperaturesensor
S9
(mandatory)DHWcirculationreturntemperature
sensor
S12
0-10VinputfordesiredtemperatureatS3
F1
ColdWatermeter(pulsesignal)
P1
Controlpump(ON-OFFcontrolled)
V1
Speedcontrolofcontrolpump(0-10VorPWM)
P3
DHWcirculationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
A1
Alarm
14DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
P318.10,ex.c,DHWapplicationwithcontrolvalveandcontrolpump:
Theshowndiagramisafundamentalandsimpliedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ECLComfort310controller
ECA32
Built-inextensionmodule,0-10Voutputs
ECA35
Built-inextensionmodule,0-10Voutputsand
PWMoutputs
S2
Supplytemperaturesensor
S3
(mandatory)DHWowtemperaturesensor
S5
Returntemperaturesensor
S9
(mandatory)DHWcirculationreturntemperature
sensor
S12
0-10VinputfordesiredtemperatureatS3
F1
ColdWatermeter(pulsesignal)
P1
Controlpump(ON-OFFcontrolled)
V1
Speedcontrolofcontrolpump(0-10VorPWM)
P3
DHWcirculationpump(ON-OFFcontrolled)
V3
Speedcontrolofcirculationpump(0-10Vor
PWM)
M1
Motorizedcontrolvalve(3-pointcontrolled)
A1
Alarm
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK
15
OperatingGuideECLComfort310,applicationP318
P318,ingeneral
UptotwoRemoteControlUnits,ECA30/31,canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.TheECLControllersintheECL485bus
systemcanworkasmasterandslaves.TheapplicationP318can
workaloneorasaslave.
Heat-meters:
Upto5heat-meterscanbeconnectedtotheM-busterminals.
DatacanbetransferredtotheSCADAsystemviaModbusandTCP/
IPtotheECLPortal.
TheP318applicationhaseventindicationsfor
Chargingtemperature(P318.1)
Tank(buffer)temperature(P318.1)
DHWowtemperature(P310.10)
Supplytemperature
Anti-bacteria
Typically,aneventisregisteredifasettemperatureconditionis
notaccepted.Theeventscanbeprioritizedtobeindicatedas
informationoranalarm.
ThealarmA1(=relay6)canbeactivatedif:
aneventoccurs
atemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
16DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
PWM(PulseWidthModulation)
A200HzfrequencyisappliedtothePWMcontrolledpump.The
dutycycle(thepercentageoftheperiodtime)determinesthe
pumpspeed.
Pumpspeed,PWMor010Voltcontrolled
Sometypesofspeedcontrolledpumpsarelimitedtoaminimum
speed,forexample30%(PWMor3.0Volt).Eveniftheapplied
control%getslowerthan30%,thepumpspeedremainsonthe
minimumlevel*.
Furthermore,whentheappliedcontrol%getsbelow,forexample,
10%,thepumpswitchesOFF.Inordertogetthepumpswitched
ONagain,theappliedcontrol%mustexceed20%.
Thisbehaviorcan,atlowloadoratoobigpump,causeunstable
temperatureregulation.Toavoidthis,theP318hasafunction
wheretheappliedcontrolsignalisconvertedintoapulsedsignal.
Thepumpisshortlystoppedandthenstartedagain.Theresultisa
pumpspeedcontrolalsobelowtheminimumspeedlevel.
Theparameters"PWMperiod"(ID11565)and"Adapttime"(ID
11065)areusedforthisfunctionality.
*)Seethepumpmanufacturer'sdatasheet
Inputconguration
Inputs(asfromS7andup)whicharenotpartoftheapplicationcan
beconguredtobePt1000,0-10Volt,frequency(pulsecounter)
orDigitalinput.Thisfeaturemakesitpossibletocommunicate
extrasignals,suchastemperatures,pressures,ON/OFFconditions,
viaModbusandECLPortal.
ThecongurationisdonebymeansoftheECLTool(freesoftware
fordownload)ordirectlyinadedicatedmenuintheECLPortalor
theconnectionforModbus(BMS/SCADA).
Commissioning
WhentheP318hasbeenuploadedtheECLComfort310controller
startsinManualmode.Thiscanbeusedtoverifythecontrolled
componentsforcorrectfunctionality.
Dependingonsystemtype,itisrecommendedtochangesome
factorysettingsindividuallyinordertooptimizethefunctionality.
Thesesettingchanges,ifrequired,arelistedbelowthesystem
typesinthesection'Identifyingthesystemtype'.
Theapplicationkeymustbeinsertedinordertochangesettings.
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverviewappendix.
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK17
OperatingGuideECLComfort310,applicationP318
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentcongurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtonaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletocongureadditionalsystems.Inthischapteryou
ndthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,ndthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Adviceforsettings:
Factorysettingsinthesubtypearerelatedtoexamplea.
Someoftheapplicationexamplesneedchangeofdedicated
settings.
Seethedocumentationfortheapplication,deliveredwiththe
applicationkey.
P318.1,ex.a,cande
InternalDHWcirculation(DHWcirculationreturnpipeisconnected
totheDHWtank)
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(1):
InternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
11054
OFF
P318.1,ex.b,dandf
ExternalDHWcirculation(DHWcirculationreturnpipeisconnected
totheheat-exchanger)
Issue:
Navigation:
IDno.:
Recommended
setting:
DHWcircuit(1):
ExternalDHWcirculation
MENU\Settings\Application:'Cont.Tcontrol'
11054
ON
Controlvalve(M1)orcontrolpump(P1/V1):
Nospecicsettingrelatedtocontrolitem.
18DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
OperatingGuideECLComfort310,applicationP318
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
DanfossDistrictEnergy
VI.JM.Q3.02
DEN-SMT/DK19
OperatingGuideECLComfort310,applicationP318
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
20DEN-SMT/DK
VI.JM.Q3.02
DanfossDistrictEnergy
/