Installation
Supplies Required:
• (3) 8m wall fasteners and bolts
• Pipe sealant
• Piping to 1/2" BSP water supply inlet on
unit
• Piping to 1-1/4 - 11 BSP drain outlet for
eyewash
• Sign-mounting hardware
Step 1: Install inlet drain fittings
NOTE: The top of the eyewash heads should
be 1067mm (42") from the floor.
1. Position the inlet drain fitting over the 1-
1/4" drain outlet pipe from wall.
2. Using the inlet drain fitting as template,
mark bolt hole locations on the wall OR
install three suitable fasteners (supplied
by installer) for 8m bolts in the wall at
marked hole locations (see illustrations
on pages 3–4).
3. Bolt the inlet drain fitting to the wall or
wall fasteners using 8m bolts (supplied
by installer).
4. After the inlet drain is secured, assemble
the flag handle, washer and nut.
Step 2: Connect water supply
1. Connect the water supply piping (supplied by installer) to the 1/2" BSP inlet on the eyewash.
2. Connect the drain piping (supplied by installer) to the 1-1/4 - 11 BSP drain outlet on the
eyewash.
3. Mount the safety sign to the wall or pipe using sign-mounting hardware (supplied by installer).
4. Open the water supply lines. Test for leaks and adequate water flow.