4 Rev. 1.1 03/12/2010
If deceleration during closing is programmed, the control unit
will add 1 second at a power level corresponding to the set
value (after the decelerated closing procedure has been
completed) in order to overcome the lock, if present.
F) T. MOT. PED. (SOFT START):
The control unit is supplied by the manufacturer with the soft
start function disabled. To enable the function proceed as
follows: make sure that Extended menu 1 is enabled (T.
PAUSA and RIT. ANTE LEDs flash alternately), use the SEL
button to navigate to the T. MOT. PED. LED when flashing and
press the SET button: the T. MOT. PED. LED remains lit
constantly and programming is complete. This means the
control unit, every time the motor starts, will control the start-up
speed of the motor, gradually increasing its power from
minimum to maximum in the first 2 seconds of operation.
Repeat the procedure to restore the previous configuration.
EXTENDED MENU 2
The control unit is supplied by the manufacturer with the option
of directly selecting only the functions listed in the main menu.
To enable the functions of Extended menu 2, proceed as
follows: access Extended menu 1 (as described in the
corresponding paragraph), then press the SET button again
and hold for 5 seconds. After this time period has elapsed, the
T. PAUSA and RIT. ANTE LEDs will begin to flash. The user
has a period of 30 seconds in which to select the functions of
Extended menu 2 using the SEL and SET buttons; after a
further 30 seconds the control unit returns to the main menu.
---------------------- EXTENDED MENU 2 -----------------
Reference LED LED Off LED On
A) 1-2 MOTORS remote PGM = OFF remote PGM = ON
B) AUT / P-P photocells test = OFF photocells test = ON
C) CODE flashing/courtesy light = OFF flashing/courtesy light = ON
D) PED. CODE pause flashing = OFF pause flashing = ON
E) T. MOT. PED. El. Lock CMD = OFF El. Lock CMD = ON
F) T.MOT.PED. PUL=PUL - PED=PED PUL=AP - PED=CH
G) T. PAUSA simultaneous ON/OFF flashing
H) RIT. ANTE simultaneous ON/OFF flashing
A) 1 – 2 MOTORS
(remote programming of radio control):
The control unit allows the transmission code to be
programmed by remote, without using the SEL key.
To programme the radio control remotely, proceed as follows:
send the radio control code continuously for more than 10
seconds and the control unit will enter the programming mode
as described above for the CODE LED in the main menu.
The control unit is supplied by the manufacturer with remote
programming of the transmission code not enabled; to enable
the function proceed as follows: make sure that Extended
menu 2 is enabled (T. PAUSA and RIT. ANTE LEDs flash
simultaneously), use the SEL button to navigate to 1-2
MOTORS LED when flashing and press the SET button: the 1-
2 MOTORS LED switches on and programming is complete.
Repeat the procedure to restore the previous configuration.
B B) AUT / P-P (Photocells Test):
The control unit is supplied by the manufacturer with the
Photocells Test programming deactivated; if wanting to enable
such function (in compliance with Standard EN 12453) it is
firstly necessary to move the jumper located on the board from
position 1-2 to position 2-3. If wanting to enable the test only on
DS1, proceed as follows: ensure to have enabled Extended
Menu 2 (highlighted by the simultaneous flashing of PAUSE T.
LED and DOORS DEL. LED), with the SEL key positioned on
the flashing of AUT/S-S LED press the SET key, the AUT/S-S
LED will simultaneously switch on permanently and the
programming is completed. In this way, the DS1 test will be
carried out before automation starts any movement. If wanting
to enable the test for both photocells (DS1 and DS2), repeat
the operation described above, pressing the SEL key twice
(obtaining the quick flashing of AUT/S-S LED) instead of once.
In this way, the test on both photocells will be carried out before
automation starts any movement.
Repeat the operation if wanting to restore the previous
configuration. If not used, inputs DS1 and DS2 must be linked
up using jumpers and the Photocells Test deactivated.
Important: ensure the appropriate jumper is positioned
correctly, in accordance or not, with the programming of the
Photocells Test.
C) CODE (advance flashing / courtesy light):
The control unit is supplied by the manufacturer with the
advance flashing and courtesy light functions disabled. To
enable the advance flashing function proceed as follows: make
sure that Extended menu 2 is enabled (T. PAUSA and RIT.
ANTE LEDs flash simultaneously), use the SEL button to
navigate to CODE LED when flashing and press the SET
button: the CODE LED switches on and programming is
complete. To enable the courtesy light function, repeat the
procedure above, pressing the SEL button twice (the CODE
LED flashes rapidly) instead of once. Repeat the procedure to
restore the initial configuration.
Advance flashing operation: The 230 V a/c flashing beacon
output will always be enabled 3 seconds before the automation
begins moving in any direction.
Courtesy light operation: The 230 V a/c flashing beacon
output will be enabled for 3 minutes every time an opening
command is given.
D) PED. CODE (flashing beacon operation):
The control unit is supplied by the manufacturer with the
flashing beacon function during pause time disabled. To enable
the function proceed as follows: make sure that Extended
menu 2 is enabled (T. PAUSA and RIT. ANTE LEDs flash
simultaneously), use the SEL button to navigate to the PED.
CODE LED when flashing and press the SET button: the PED.
CODE LED is illuminated in a constant manner and
programming is complete. Repeat the procedure to restore the
previous configuration.
E) T. MOT (electric lock PED. CMD activation):
The control unit is supplied by the manufacturer with the
electric lock pedestrian command function disabled. To enable
the function proceed as follows: make sure that Extended
menu 2 is enabled (T. PAUSA and RIT. ANTE LEDs flash
simultaneously), use the SEL button to navigate to the T. MOT.
LED when flashing and press the SET button: the T. MOT. LED
remains lit in a constant manner and programming is complete.
The electric lock pedestrian command function is used when,
for example, a sliding gate has been fitted with a door for
pedestrian passage next to it. This means the gate can be
opened using the PUL commands and the pedestrian door can
be opened by enabling the electric lock function using the PED
commands. Repeat the procedure to restore the previous
configuration.
F) T. MOT. PED. (PUL and PED commands operation):
The control unit is supplied by the manufacturer with an
enabled PUL command input for the connection of a cyclical
main command button (NA) and PED input for the connection
of a cyclical pedestrian command button (NA). If you wish to
select a different operating mode for the PUL and PED inputs,
proceed as follows: make sure that Extended menu 2 is
enabled (T. PAUSA and RIT. ANTE LEDs flash
simultaneously), use the SEL button to navigate to the T. MOT.
PED. LED when flashing and press the SET button: the T.
MOT. PED. LED remains lit constantly and programming is
complete.
This means the PUL input will allow connection of a button (NA)
only for the opening movement and the PED input will be used
for the connection of a button (NA) only for the closing
movement. Repeat the procedure to restore the previous
configuration.