Lenovo ThinkAgile VX 4-Socket 4U Certified Node User manual

Type
User manual

This manual is also suitable for

User Guide for
ThinkAgile VX7820 Appliance,
ThinkAgile VX 4-Socket 4U Certified Node
Machine Types: 7Z12 and 7Z13
Note
Before using this information and the product it supports, be sure to read and understand the safety
information and the safety instructions, which are available at:
http://thinksystem.lenovofiles.com/help/topic/safety_documentation/pdf_files.html
This equipment is not suitable for use in locations where children are likely to be present.
In addition, be sure that you are familiar with the terms and conditions of the Lenovo warranty for your server,
which can be found at:
http://datacentersupport.lenovo.com/warrantylookup
First Edition (May 2020)
© Copyright Lenovo 2020.
LIMITED AND RESTRICTED RIGHTS NOTICE: If data or software is delivered pursuant to a General Services
Administration (GSA) contract, use, reproduction, or disclosure is subject to restrictions set forth in Contract No. GS-35F-
05925.
Contents
Safety . . . . . . . . . . . . . . . . . . v
Safety inspection checklist . . . . . . . . . . . vi
Chapter 1. Introduction . . . . . . . . . 1
Typical vSAN architecture . . . . . . . . . . . . 1
VX deployment architecture . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . 3
Configurations . . . . . . . . . . . . . . . . 8
Configuration 1. Four-socket Performance . . . 8
Configuration 2. Four-Socket Upgradable . . . 12
Configuration 3. Four-Socket Upgradable /
Storage Rich . . . . . . . . . . . . . . 14
Management options. . . . . . . . . . . . . 17
Lifecycle management . . . . . . . . . . . . 18
Recommended procedure for updating a
ThinkAgile VX cluster . . . . . . . . . . . 18
Firmware updates . . . . . . . . . . . . . . 19
Tech Tips . . . . . . . . . . . . . . . . . 22
Security advisories . . . . . . . . . . . . . 22
Chapter 2. Server components . . . . 23
Front view . . . . . . . . . . . . . . . . . 24
Front operator panel . . . . . . . . . . . 26
Rear view . . . . . . . . . . . . . . . . . 29
Internal connectors . . . . . . . . . . . . . 32
System-board connectors . . . . . . . . . 32
Storage-board-assembly connectors . . . . 33
I/O tray connectors. . . . . . . . . . . . 34
Storage interposer connectors . . . . . . . 38
RAID card connectors . . . . . . . . . . 38
Drive backplane connectors . . . . . . . . 39
Internal cable routing. . . . . . . . . . . . . 40
Cable routing for common components . . . 42
Cable routing for drives . . . . . . . . . . 45
Parts list. . . . . . . . . . . . . . . . . . 55
Power cords . . . . . . . . . . . . . . 60
Chapter 3. Network/Infrastructure
Planning . . . . . . . . . . . . . . . . 61
Chapter 4. Server setup checklist. . . 63
Server package contents . . . . . . . . . . . 63
Cable the server . . . . . . . . . . . . . . 64
Power on the server (connect input power) . . . . 64
Power off the server (disconnect input power) . . . 65
Chapter 5. System configuration . . . 67
Set the network connection for the Lenovo XClarity
Controller . . . . . . . . . . . . . . . . . 67
Management options. . . . . . . . . . . . . 68
Manage the lifecycle . . . . . . . . . . . . . 68
Update the firmware . . . . . . . . . . . . . 68
Configure the firmware . . . . . . . . . . . . 68
Memory configuration . . . . . . . . . . . . 70
Independent memory mode . . . . . . . . 70
Memory mirroring . . . . . . . . . . . . 70
Memory sparing . . . . . . . . . . . . . 70
Configure DC Persistent Memory Module
(DCPMM) . . . . . . . . . . . . . . . 70
RAID configuration . . . . . . . . . . . . . 75
Install the operating system . . . . . . . . . . 75
Back up the server configuration . . . . . . . . 76
Chapter 6. Installing and configuring
vCSA . . . . . . . . . . . . . . . . . . 77
Using the ThinkAgile Installer . . . . . . . . . 77
Downloading and setting up the ThinkAgile
Installer . . . . . . . . . . . . . . . . 77
Running the ThinkAgile Installer . . . . . . . 78
Installing and configuring vCSA manually . . . . . 81
Adding the ThinkAgile VX7820 Appliance/VX 4U
Certified Node to an existing vCSA instance. . . . 82
Chapter 7. Installing and setting up
Lenovo XClarity Administrator. . . . . 83
Deploying Lenovo XClarity Administrator . . . . . 83
Managing ThinkAgile VX7820 Appliance/VX 4U
Certified Node Servers . . . . . . . . . . . . 84
Chapter 8. Installing and setting up
Lenovo XClarity Integrator. . . . . . . 87
Deploying Lenovo XClarity Integrator for VMware
vCenter . . . . . . . . . . . . . . . . . . 87
Chapter 9. Hardware replacement
procedures . . . . . . . . . . . . . . . 89
Installation Guidelines . . . . . . . . . . . . 89
System reliability guidelines . . . . . . . . 90
Handling static-sensitive devices . . . . . . 91
Adapter replacement. . . . . . . . . . . . . 91
Remove a PCIe adapter from slot 1 to 4 . . . 92
Remove a PCIe adapter from slot 5 to 8 . . . 93
Remove a LOM adapter from slot 9 . . . . . 95
Remove a PCIe adapter from slot 10 to 15 . . 96
Remove an I/O adapter from slot 16 to 17 . . . 97
Install a PCIe adapter in slot 1 to 4. . . . . . 99
© Copyright Lenovo 2020 i
Install a PCIe adapter in slot 5 to 8. . . . . . 100
Install a LOM adapter in slot 9 . . . . . . . 101
Install a PCIe adapter in slot 10 to 15. . . . . 102
Install an I/O adapter in slot 16 to 17 . . . . . 104
System battery (CR2032) replacement . . . . . . 105
Remove the system battery . . . . . . . . 105
Install the system battery . . . . . . . . . 107
System board replacement . . . . . . . . . . 109
Remove a system board . . . . . . . . . 109
Install a system board . . . . . . . . . . 111
System board filler replacement . . . . . . . . 112
Remove a system board filler. . . . . . . . 113
Install a system board filler. . . . . . . . . 114
Upper/lower compute tray replacement . . . . . 115
Remove a compute tray . . . . . . . . . . 115
Install a compute tray. . . . . . . . . . . 117
Fan replacement . . . . . . . . . . . . . . 119
Remove a fan . . . . . . . . . . . . . . 119
Install the fan . . . . . . . . . . . . . . 120
Fan cage replacement . . . . . . . . . . . . 121
Remove a fan cage (upper tray) . . . . . . . 121
Remove a fan cage (lower tray) . . . . . . . 123
Install a fan cage (upper tray) . . . . . . . . 125
Install a fan cage (lower tray) . . . . . . . . 128
Front bezel replacement . . . . . . . . . . . 130
Remove the front bezel . . . . . . . . . . 130
Install the front bezel . . . . . . . . . . . 130
Front cover replacement . . . . . . . . . . . 131
Remove the front cover . . . . . . . . . . 131
Install the front cover . . . . . . . . . . . 132
Front operator panel replacement. . . . . . . . 134
Remove the front operator panel . . . . . . 134
Install the front operator panel . . . . . . . 135
Front USB/VGA assembly replacement . . . . . 137
Remove the front USB/VGA assembly . . . . 137
Install the front USB/VGA assembly . . . . . 138
Hard disk drive backplane replacement . . . . . 139
Remove a hard disk drive backplane (upper
tray) . . . . . . . . . . . . . . . . . 139
Remove a hard disk drive backplane (lower
tray) . . . . . . . . . . . . . . . . . 141
Install a hard disk drive backplane (upper
tray) . . . . . . . . . . . . . . . . . 143
Install a hard disk drive backplane (lower
tray) . . . . . . . . . . . . . . . . . 145
Hot-swap drive replacement . . . . . . . . . . 147
Remove a hot-swap drive . . . . . . . . . 147
Install a hot-swap drive . . . . . . . . . . 148
Remove a hot-swap drive filler . . . . . . . 150
Install a hot-swap drive filler . . . . . . . . 151
I/O tray replacement . . . . . . . . . . . . . 152
Remove the I/O tray . . . . . . . . . . . 152
Install the I/O tray . . . . . . . . . . . . 154
M.2 backplane replacement . . . . . . . . . . 163
Remove the M.2 backplane . . . . . . . . 163
Install the M.2 backplane . . . . . . . . . 165
M.2 backplane retainer adjustment . . . . . 166
M.2 drive replacement . . . . . . . . . . . . 166
Remove an M.2 drive . . . . . . . . . . . 166
Install an M.2 drive . . . . . . . . . . . . 167
Memory air baffle replacement . . . . . . . . . 170
Remove a memory baffle . . . . . . . . . 170
Install a memory air baffle . . . . . . . . . 171
Memory module replacement . . . . . . . . . 173
Remove a memory module . . . . . . . . 173
Install a memory module . . . . . . . . . 175
Midplane replacement . . . . . . . . . . . . 179
Remove a midplane . . . . . . . . . . . 179
Install a midplane . . . . . . . . . . . . 181
Power supply replacement . . . . . . . . . . 183
Remove a power supply. . . . . . . . . . 183
Install a power supply. . . . . . . . . . . 185
Remove a power supply filler . . . . . . . . 188
Install a power supply filler. . . . . . . . . 189
Processor and heat sink replacement . . . . . . 190
Remove a processor and heat sink . . . . . 190
Install a processor and heat sink . . . . . . 193
RAID/HBA card replacement. . . . . . . . . . 200
Remove a RAID/HBA card (upper tray) . . . . 200
Remove a RAID/HBA card (lower tray) . . . . 201
Install a RAID/HBA card (upper tray) . . . . . 203
Install a RAID/HBA card (lower tray) . . . . . 205
RAID flash power module replacement . . . . . . 207
Remove a RAID flash power module (upper
tray) . . . . . . . . . . . . . . . . . 207
Remove a RAID flash power module (lower
tray) . . . . . . . . . . . . . . . . . 208
Install a RAID flash power module (upper
tray) . . . . . . . . . . . . . . . . . 209
Install a RAID flash power module (lower
tray) . . . . . . . . . . . . . . . . . 211
Riser replacement . . . . . . . . . . . . . . 212
Remove the riser for slot 1 to 4 (riser 1) . . . . 212
Remove the riser for slot 10 to 15 (riser 2) . . . 213
Remove the riser bracket for slot 14 to 15
(riser 2) . . . . . . . . . . . . . . . . 215
Remove the riser for slot 16 to 17 (riser 3) . . . 217
Install the riser for slot 1 to 4 (riser 1) . . . . . 218
Install the riser for slot 10 to 15 (riser 2) . . . . 220
Install the riser bracket for slot 14 to 15 (riser
2) . . . . . . . . . . . . . . . . . . 221
Install the riser for slot 16 to 17 (riser 3) . . . . 222
ii User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
Storage board assembly replacement . . . . . . 224
Remove a storage board assembly . . . . . 224
Install a storage board assembly . . . . . . 225
Storage interposer replacement . . . . . . . . 226
Remove a storage interposer (upper tray) . . . 226
Remove a storage interposer (lower tray) . . . 228
Install a storage interposer (upper tray) . . . . 229
Install a storage interposer (lower tray) . . . . 230
Storage tray replacement . . . . . . . . . . . 232
Remove a storage tray . . . . . . . . . . 232
Install the storage tray (fully removed) . . . . 234
TCM/TPM adapter replacement (for Chinese
Mainland only) . . . . . . . . . . . . . . . 235
Remove the TCM/TPM adapter (for Chinese
Mainland only) . . . . . . . . . . . . . 235
Install the TCM/TPM adapter (for Chinese
Mainland only) . . . . . . . . . . . . . 236
Upper tray filler replacement . . . . . . . . . . 237
Remove the upper tray filler . . . . . . . . 237
Install the upper tray filler . . . . . . . . . 239
Complete the parts replacement . . . . . . . . 240
Chapter 10. Problem
determination . . . . . . . . . . . . . 243
Event logs . . . . . . . . . . . . . . . . . 243
Light path diagnostics . . . . . . . . . . . . 245
Power supply LEDs . . . . . . . . . . . 247
System-board LEDs . . . . . . . . . . . 249
General problem determination procedures . . . . 249
Resolving suspected power problems . . . . 250
Resolving suspected Ethernet controller
problems . . . . . . . . . . . . . . . 250
Troubleshooting by symptom . . . . . . . . . 251
Power on and power off problems. . . . . . 251
Processor problems . . . . . . . . . . . 253
Memory problems . . . . . . . . . . . . 253
Hard disk drive problems . . . . . . . . . 255
Monitor and video problems . . . . . . . . 257
Keyboard, mouse, or USB-device
problems . . . . . . . . . . . . . . . 258
Optional-device problems . . . . . . . . . 259
Serial-device problems . . . . . . . . . . 260
Intermittent problems. . . . . . . . . . . 261
Power problems . . . . . . . . . . . . . 262
Network problems . . . . . . . . . . . . 262
Observable problems. . . . . . . . . . . 263
Software problems. . . . . . . . . . . . 265
Appendix A. Hardware
disassembling for recycle . . . . . . . 267
Disassemble the system board for recycle . . . . 267
Disassemble the system board filler for recycle . . 268
Disassemble the front cover for recycle . . . . . 268
Appendix B. Getting help and
technical assistance . . . . . . . . . . 271
Before you call . . . . . . . . . . . . . . . 271
Collecting service data . . . . . . . . . . . . 272
Contacting Support . . . . . . . . . . . . . 273
Appendix C. Notices. . . . . . . . . . 275
Trademarks . . . . . . . . . . . . . . . . 276
Important notes . . . . . . . . . . . . . . . 276
Particulate contamination . . . . . . . . . . . 276
Telecommunication regulatory statement. . . . . 277
Electronic emission notices . . . . . . . . . . 277
Taiwan BSMI RoHS declaration. . . . . . . 278
Taiwan import and export contact information . . . 278
Index . . . . . . . . . . . . . . . . . . 279
© Copyright Lenovo 2020 iii
iv User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
Safety
Before installing this product, read the Safety Information.
Antes de instalar este produto, leia as Informações de Segurança.
在安装本产品之前,请仔细阅读 Safety Information (安全信息)。
Læs sikkerhedsforskrifterne, før du installerer dette produkt.
Lees voordat u dit product installeert eerst de veiligheidsvoorschriften.
Ennen kuin asennat tämän tuotteen, lue turvaohjeet kohdasta Safety Information.
Avant d'installer ce produit, lisez les consignes de sécurité.
Vor der Installation dieses Produkts die Sicherheitshinweise lesen.
Prima di installare questo prodotto, leggere le Informazioni sulla Sicurezza.
Les sikkerhetsinformasjonen (Safety Information) før du installerer dette produktet.
Antes de instalar este produto, leia as Informações sobre Segurança.
© Copyright Lenovo 2020 v
Antes de instalar este producto, lea la información de seguridad.
Läs säkerhetsinformationen innan du installerar den här produkten.
Safety inspection checklist
Use the information in this section to identify potentially unsafe conditions with your server. As each machine
was designed and built, required safety items were installed to protect users and service technicians from
injury.
CAUTION:
This equipment must be installed or serviced by trained personnel, as defined by the NEC, IEC 62368-
1 & IEC 60950-1, the standard for Safety of Electronic Equipment within the Field of Audio/Video,
Information Technology and Communication Technology. Lenovo assumes you are qualified in the
servicing of equipment and trained in recognizing hazards energy levels in products. Access to the
equipment is by the use of a tool, lock and key, or other means of security, and is controlled by the
authority responsible for the location.
Important: Electrical grounding of the server is required for operator safety and correct system function.
Proper grounding of the electrical outlet can be verified by a certified electrician.
Use the following checklist to verify that there are no potentially unsafe conditions:
1. Make sure that the power is off and the power cord is disconnected.
2. Check the power cord.
Make sure that the third-wire ground connector is in good condition. Use a meter to measure third-
wire ground continuity for 0.1 ohm or less between the external ground pin and the frame ground.
Make sure that the power cord is the correct type.
To view the power cords that are available for the server:
a. Go to:
http://dcsc.lenovo.com/#/
b. In the Customize a Model pane:
1) Click Select Options/Parts for a Model.
2) Enter the machine type and model for your server.
vi
User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
c. Click the Power tab to see all line cords.
Make sure that the insulation is not frayed or worn.
3. Check for any obvious non-Lenovo alterations. Use good judgment as to the safety of any non-Lenovo
alterations.
4. Check inside the server for any obvious unsafe conditions, such as metal filings, contamination, water or
other liquid, or signs of fire or smoke damage.
5. Check for worn, frayed, or pinched cables.
6. Make sure that the power-supply cover fasteners (screws or rivets) have not been removed or tampered
with.
© Copyright Lenovo 2020 vii
viii User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
Chapter 1. Introduction
The ThinkAgile VX7820 Appliance and VX 4U Certified Node are high performance 4U rack servers that
support up to four Intel Xeon processors. They are enterprise-class servers designed for customers requiring
four processors, large amounts of memory, and numerous I/O connections. In addition, they are designed to
simplify vSAN deployment and management for customers through predefined server configurations that are
optimized around specific types of workloads. They are preinstalled with VMware ESXi and conform to best
practices and compliance guidelines for vSAN.
Note: A VMware vSAN cluster requires a minimum of three servers. The best practice is to use three or more
servers of the same machine type and configuration to provide a balanced and high-performance solution.
In addition, the servers are designed to utilize the Lenovo system management tools to create a unified
hardware management solution for vSAN deployments:
Lenovo XClarity Administrator, which provides firmware compliance functionality to ensure that the
ThinkAgile VX MT 7Z12 and 7Z13 Series servers are running the appropriate level of firmware for Lenovo
XClarity Controller, UEFI, and PCIe devices.
Lenovo XClarity Integrator, which provides VMware vCenter plug-in functionality so that ThinkAgile VX
MT 7Z12 and 7Z13 Series servers can be managed directly from vCenter.
The ThinkAgile VX MT 7Z12 and 7Z13 Series hardware is based on the SR950 rack server.
Figure 1. ThinkAgile VX7820 Appliance/VX 4U Certified Node
The server comes with a limited warranty. For details about the warranty, see:
https://support.lenovo.com/us/en/solutions/ht503310
For details about your specific warranty, see:
http://datacentersupport.lenovo.com/warrantylookup
Typical vSAN architecture
A typical vSAN architecture includes three or more servers that are implemented as a single vSAN cluster.
Each server contributes storage to the vSAN cluster from the local disks on the server:
Hybrid Cluster The server provides a combination of solid state disks (SSDs) for caching and hard disk
drives (HDDs) for storage capacity.
All-Flash Cluster The server provides SSDs for caching and SSDs for storage capacity.
The following figure provides a conceptual view of the vSAN architecture:
© Copyright Lenovo 2020 1
The following figure provides a conceptual view of the vSAN architecture:
https://storagehub.vmware.com/t/vmware-vsan/vmware-r-vsan-tm-design-and-sizing-guide/
VX deployment architecture
When deploying a ThinkAgile VX MT 7Z12 and 7Z13 Series solution, the best practice is to use three or more
servers of the same machine type and configuration to provide a balanced and high-performance solution.
The systems are connected through switches for management and data:
A dedicated management network is used by the Lenovo XClarity Administrator to communicate with the
Lenovo XClarity Controller (XCC) on each of the ThinkAgile VX7820 Appliance/VX 4U Certified Node.
A redundant 10Gbps Ethernet network is used for VMware vSphere management and vSAN data traffic.
The redundant Ethernet network is implemented through two top-of-rack switches, such as the Lenovo
ThinkSystem NE1032 RackSwitch.
For more information about the Lenovo ThinkSystem NE1032 RackSwitch, see the following website:
https://lenovopress.com/lp0605-lenovo-thinksystem-ne1032-rackswitch
The following figure shows a typical ThinkAgile VX Series deployment:
2
User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
Specifications
The following information is a summary of the features and specifications of the server. Depending on the
model, some features might not be available, or some specifications might not apply.
Table 1. Server Specifications
Specification
Description
Size
4U server
Height: 175.8 mm (6.9 in.)
Depth:
EIA flange to rear: 800.0 mm (31.5 in.)
Overall: 853.0 mm (33.6 in.)
Width:
Top cover: 447.0 mm (17.6 in.)
EIA flange: 483.0 mm (19.0 in.)
Weight Approximately 32.6 kg (71.9 lbs.) to 58.7 kg (129.4 lbs.) depending on your
configuration.
Processor (depending on the
model)
Supports multi-core Intel Xeon processors, with integrated memory controller and
Ultra Path Interconnect (UPI)
Two processors, minimum (expandable up to four).
Designed for the LGA 3647-0 socket
Scalable up to 112 cores (with four processors installed)
For a list of supported processors, see
http://www.lenovo.com/us/en/serverproven/
and the “Processor Options” section of the ThinkAgile VX7820 Appliance/VX 4U
Certified Node product guide on
http://lenovopress.com/.
Note: If 82xx processors are installed, 60 mm x 38mm, 19K internal hot-swap fans
(01PG490) must also be installed to meet CPU cooling requirements at 35°C. If 16K
internal hot-swap fans are currently installed, you must validate that the system has
version 2 of the ThinkSystem 2-CPU, 24-DIMM, Compute System Board (01CV978)
installed in each compute tray before upgrading the fans from 16K to 19K.
Chapter 1. Introduction 3
Table 1. Server Specifications (continued)
Specification
Description
Memory
Minimum: 32 GB
Maximum:
3.1 TB using registered DIMMs (RDIMMs) or load reduction DIMMs (LRDIMMs)
12.3 TB using three-dimensional-stacking registered DIMMs (3DS RDIMMs)
18.4 TB using Intel® Optane
TM
DC persistent memory modules (PMMs)
Type:
PC4-21300 (DDR4-2666), operating speed depends on processor model and
UEFI settings
Single-rank or dual-rank
Registered DIMM (RDIMM), load reduced DIMM (LRDIMM), or three-
dimensional-stacking registered DIMM (3DS RDIMM)
Slots: 24 dual inline in each compute tray (48 DIMMs, maximum)
Supports (depending on the model):
16 GB, 32 GB, 64 GB RDIMMs
64 GB LRDIMMs
64 GB, 128 GB, 256 GB 3DS RDIMMs
128 GB, 256 GB, and 512 GB Intel® Optane
TM
DC persistent memory modules
(DCPMMs)
Drive expansion
Up to six SAS/SATA/NVMe drive backplanes:
Up to 24 2.5-inch hot-swap drive bays:
Up to 24 SATA/SAS drives (dependent on installed drive backplanes)
Up to 12 NVMe drives (dependent on installed drive backplanes)
See “Configurations” on page 8 for more details.
4 User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
Table 1. Server Specifications (continued)
Specification
Description
Expansion slots
Up to seventeen expansion slots (dependent on server configuration):
Slot 1 - 4: PCI Express 3.0 for PCIe riser-card with the following slots available
depending on the riser installed:
1. x8/x8/x8/x8 PCIe full-height riser kit provides:
Slot 1: PCI Express 3.0 x8
Slot 2: PCI Express 3.0 x8
Slot 3: PCI Express 3.0 x8
Slot 4: PCI Express 3.0 x8
2. x16/x16 PCIe full-height riser kit provides:
Slot 3: PCI Express 3.0 x16
Slot 4: PCI Express 3.0 x16
3. x16/x16/x16/x16 PCIe full-height riser kit (8-processor systems only)
provides:
Slot 1: PCI Express 3.0 x16
Slot 2: PCI Express 3.0 x16
Slot 3: PCI Express 3.0 x16
Slot 4: PCI Express 3.0 x16
Slot 5: PCI Express 3.0 x16 (low profile)
Slot 6: PCI Express 3.0 x16 (low profile)
Slot 7: PCI Express 3.0 x8 (low profile)
Note: You should not install a RAID or Host Bus Adapter card in this slot.
Slot 8: ML2 x16 network adapter (with NC-SI support)
Slot 9: LOM adapter
Slot 10 - 15: PCI Express 3.0 for PCIe riser-card with the following slots available
depending on the riser-card installed:
1. x8/x8/x8/x8 PCIe full-height riser kit provides:
Slot 10: PCI Express 3.0 x8
Slot 11: PCI Express 3.0 x8
Slot 12: PCI Express 3.0 x8
Slot 13: PCI Express 3.0 x8
2. x16/x16 PCIe full-height riser kit provides:
Slot 12: PCI Express 3.0 x16
Slot 13: PCI Express 3.0 x16
3. x16/x16/x16/x16 PCIe and ML2 x16 full-height riser kit (8-processor systems
only) provides:
Slot 10: PCI Express 3.0 x16
Slot 11: PCI Express 3.0 x16
Slot 12: PCI Express 3.0 x16
Slot 13: PCI Express 3.0 x16
Slot 14: PCI Express 3.0 x16
Slot 15: ML2 x16 network adapter (no NC-SI support)
Chapter 1. Introduction 5
Table 1. Server Specifications (continued)
Specification
Description
Slot 16 - 17: x8/x8 PCIe low-profile riser kit (processor-rich systems only)
provides:
Slot 16: PCI Express 3.0 x8
Slot 17: PCI Express 3.0 x8
See “Configurations” on page 8 for more details.
Integrated functions
Lenovo XClarity Controller, which provides service processor control and
monitoring functions, video controller, and remote keyboard, video, mouse, and
remote drive capabilities.
Light-path diagnostics
Standard connectors (front of server):
DB-15 VGA port
USB 2.0 ports (two):
USB 2.0 for Lenovo XClarity Controller management
USB 2.0
Standard connectors (rear of server):
DB-15 VGA port
DB-9 serial port
RJ-45 system-management network port. This connector is dedicated for
Lenovo XClarity Controller functions and runs at 1 gigabit (Gb) speed.
USB 3.0 ports (two)
Internal SAS HBAs The following RAID options are available for this server:
ThinkSystem 430-8i Internal SAS HBA
ThinkSystem 430-16i Internal SAS HBA
Fans
Up to twelve (60 mm x 38 mm) internal hot-swap system fans (dependent on server
configuration)
The six upper fans are not installed for the four-processor-limited server
configuration.
Only three upper fans are installed for the storage-rich configuration.
Two types of fans are supported:
60 mm x 38mm, 16K internal hot-swap fans (01CX965)
60 mm x 38mm, 19K internal hot-swap fans (01PG490)
Notes:
Different fan types cannot be mixed within a system. All fans must be either 16K
fans or 19K fans.
Before upgrading fans from 16K to 19K, you must make sure that the system has
version 2 of the ThinkSystem 2-CPU, 24DIMM, Compute System Board
(01CV978) installed in each compute tray.
6 User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
Table 1. Server Specifications (continued)
Specification
Description
Power supplies
This server supports three types of hot-swap power supply units:
1100-watt power supply
input voltage 110V, 220V, or 240V ac
1600-watt power supply
input voltage 220V or 240V ac
2000-watt power supply
input voltage 220V ac
The power subsystem supports balanced N+N redundancy operation, where N =
1 or 2.
CAUTION:
1. 240 V dc input (input range: 180-300 V dc) is ONLY supported in Chinese
Mainland.
2. Power supplies with 240 V dc are not hot-swappable. To remove the power
cord, ensure you have turned off the server or disconnected the dc power
sources at the breaker panel.
3. In order for the ThinkSystem products to operate error free in both a DC or
AC electrical environment, a TN-S earthing system which complies to
60364-1 IEC 2005 standard has to be present or installed.
Minimal configuration for
debugging
Two processors in processor sockets 1 and 2
Two DRAM DIMMs in slot 8 and 20
One power supply in slot 1
One drive with HBA adapter and backplane
Six system fans (fans 1 to 6)
Acoustical noise emissions
(base configuration)
Sound power, idling: 6.1 bels
Sound power, operating: 6.1 bels
Note: The options supported in this server vary in function, power consumption, and
required cooling. Any increase in cooling required by these options will increase the
fan speed and generated sound level. The actual sound pressure levels measured in
your installation depend upon a variety of factors, including: the number of racks in
the installation; the size, materials, and configuration of the room; the noise levels of
other equipment; the room ambient temperature and barometric pressure; and the
location of employees in relation to the equipment.
Chapter 1. Introduction 7
Table 1. Server Specifications (continued)
Specification
Description
Heat output Approximate heat output:
Minimum configuration: 935 BTU, 275 W (in BTU per hour and watts)
Minimum configuration of two microprocessors, two memory modules, one M.2
adapter, and no PCIe adapters.
Maximum configuration: 21837 BTU, 6400 W (in BTU per hour and watts)
Maximum configuration with four 1600-watt power supplies configured for non-
redundant operation under maximum loading.
Environment
Air temperature:
Server on: 5° to 45°C (41° to 113°F); altitude: 0 to 3050 m (10,006 ft) derate
maximum dry bulb temperature 1°C (33°F) per 125 m (410 ft) above 950 m
(3,117 ft). Maximum rate of change 20°C (68°F) per hour
Server off: to 45°C (41° to 113°F)
Shipment: -40°C to 60°C (-40°F to 140°F)
Humidity range (noncondensing):
Server on: Minimum = higher (more moisture) of -12°C (10°F) dew point and 8%
to 90% relative humidity; maximum dew point: 24°C (75°F)
Server off: 8% to 90% relative humidity; maximum dew point: 27°C (80°F)
Shipment: 5% to 100%
Notes:
Airborne particulates and reactive gases acting alone or in combination with other
environmental factors such as humidity or temperature might pose a risk to the
server. For information about the limits for particulates and gases, see
Particulate
contamination
.
ASHRAE compliance information (see the “Operating Environment” section of
ThinkAgile VX7820 Appliance/VX 4U Certified Node product guide on
http://
lenovopress.com/
for specific ASHRAE compliance levels for each server
configuration):
The server is designed for thermal compliance in ASHRAE A4 ambient
environments. Certain processor and adapter configurations will limit product
environmental support to ASHRAE A2 ambient conditions.
If 82xx processors are installed, 60 mm x 38mm, 19K internal hot-swap fans
(01PG490) must also be installed to meet CPU cooling requirements at 35°C.
205W processors used in an eight-socket configuration might experience a
slight drop in performance under extreme workloads when the ambient
temperature is above 30°C.
NVMe devices are supported up to an ambient temperature of 35°C.
Configurations
The ThinkAgile VX7820 Appliance/VX 4U Certified Node is available in several configurations.
Configuration 1. Four-socket Performance
The highest-performing four-socket server, at the lowest cost when up to 12 drives is enough and without
the need for a simple upgrade.
8
User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
Figure 2. Four-socket performance configuration
This four-socket configuration supports the following combinations:
Two processors (1, 2) support:
12 drives (bay 0-11) with two NVMe enabled (bay 8, 10)
Extension slots
Three processors (1, 2, 4)
Four processors (1, 2, 3, 4)
Supports 2, 3 or 4 processors (if using 5100 Series processors, 4 processors must be selected)
4 sockets configured in mesh topology for best performance
12 drive bays, 6 of which support NVMe drives (4 NVMe with 3 processors and 2 NVMe with 2 processors)
15 rear PCIe slots with 4 processors (10 rear slots with 3 processors, 6 rear slots with 2 processors)
Filler installed in the upper tray area
Processor configurations
This configuration supports 2, or 4 processors.
2-processor configuration. Processors are installed in location 1 and 2.
3-processor configuration. Processors are installed in locations 1, 2, and 4.
4-processor configuration. Processors are installed in locations 1, 2, 3, and 4.
Chapter 1. Introduction 9
Figure 3. Processor numbering (viewed from the front of the server)
PCIe slot connectivity
The following table shows the processor to PCIe slot connectivity:
PCIe
slot Slot location
Description
1 Riser 1 4
1
Not connected for 2x16. Slots 1 and 2 are not connected if the 2x16 riser is used in
riser slot 1
2 4
1
Not connected for 2x16. Slots 1 and 2 are not connected if the 2x16 riser is used in
riser slot 1
3 4
1
4 4
1
5
I/O tray
2
6 2
7 1
8 (ML2)
1
9 (LOM) 1 (PCH)
10 Riser 2 3
2
11 3
2
12 3
2
13 3
2
14 Not connected.
15 (ML2)
Not connected.
16 2x8 Riser 3
2
17 1
M.2
I/O tray 1 (PCH)
Storage
adapter
Upper tray Not connected.
10 User Guide for ThinkAgile VX7820 Appliance, ThinkAgile VX 4-Socket 4U Certified Node
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296