Installation and Maintenance
FläktGroup DC_10548GB 20220221_R1 Specifications are subject to alteration without notice
Installation notes
The device has been constructed and tested according to IEC 60730-1
“Automatic electrical regulating and control devices for household use
and similar applications - part 1: General applications “, is CE-certified
and has left the factory in a safety-technically impeccable condition.
To maintain this condition, the content of these safety notes and
the rating plates, labels and safety notes on the device must be
observed when handling the device (transport, storage, installation,
commissioning, operation, maintenance, decommissioning); otherwise,
persons may be endangered and the product as well as other facilities
may be damaged.
These safety notes apply in the Federal republic of Germany. When
used in other countries, observe the relevant national rules there.
In addition to the notes in these operating instructions, observe the
general safety and accident prevention provisions.
If the information of these safety notes is insufficient, you may at any
time contact the manufacturer at the indicated address.
• Please check the packaging and report any damage without delay.
• The device must only be installed and taken into operation by an
electrician who is familiar with the dangers.
• Ensure before commissioning that the device has no damage. In
doubt, bring in an electrician or contact the address below.
• Before commissioning, check if the operating voltage of the device
and the mains voltage match.
• There may be condensation if the device is taken from a cold
environment to a warm one suddenly. Wait until the temperature has
adjusted. Commissioning under condensation poses danger to life!
• If it can be assumed that safe operation is no longer possible,
the device must be taken out of operation and secured against
inadvertent operation.
It is to be assumed that safe operation is no longer possible,
- if the device has visible damage,
- if the device no longer works,
- after storage under harmful conditions,
- after severe transport stress.
• Before cleaning: switch off the mains! Use a light cleaning agent
with a moist cloth for cleaning. Never clean while dripping wet!
Observe that the device is installed as far as possible from strong
interference sources. These may be magnetic coils, transformers,
frequency converters, etc.
Attention!
Observe sufficient protection from electrostatic
electricity (ESD) when installing the device.
Wiring notes:
Always observe that the wire connection is made only by the
intended screws; other assignment than indicated in the mechanical
disassembly may cause malfunction of the control or impairment of
other devices in the environment. No line connection must be routed
across the electronics within the housing. Control and signal lines, also
outside of the housing, must never be placed together in one cable
duct or collar together with load-conducting lines. All lines must be
sized according to the standard for current capacity.
Changes reserved
Intended use
This control was developed for installation into an exhaust hood to
control UV-C elements. They are switched depending on external
control contacts and their functions are monitored.
Up to 3 fields with 4 frames each with lamp outputs up to 2000VA can
be connected. The device is set up modular and consists of:
• A control box installed in a plastic housing (IP65)
• A display unit in a plastic housing
Function description
After activation of the power supply (main switch), the system starts
into automatic mode.
The green LED “On” in the front of the display element and a relay
output “Ready for operation” signal the readiness for operation of the
control (relay contact is closed).
Activation and deactivation of the control electronics takes place via
the button “On/Off” in the display element.
Attention!
Only auxiliary energy is switched.
If a fault is present, e.g. door open, pressure drop in the fan, external
fault message of the module, lamp current undercut (the lamp current
is continually monitored via an integrated power measurement on the
electronic unit), is signalled via the corresponding LED in the display
unit and output via a relay contact “Fault” (quiescent current contact,
opens in case of error).
Attention!
If no faults are present, the photozone lamps
are switched on after a delay time of approx.
1 minute and all other LEDs in the display unit
have gone out.