![](//vs1.manuzoid.com/store/data-gzf/8be41bacd5dbd25ad85ed52a218ac9fb/2/002136674.htmlex.zip/bga.jpg)
10
ALPINE Installation, Operating & Service Instructions
106307-03- 11/22
F. The boiler should be located so as to minimize
the length of the vent system. Locate combustion
air pipe termination away from areas that may
contaminate combustion air, (see Table 3-1). In
particular, avoid areas near chemical products
containing chlorines, chlorofluorocarbons, paint
removers, cleaning solvents and detergents.
Avoid areas containing saw dust, loose insulation
fibers, dry wall dust, etc.
NOTICE: Avoid operating this boiler in an
environment where sawdust, loose insulation
fibers, dry wall dust, etc. are present. If boiler
is operated under these conditions, the burner
interior and ports must be cleaned and inspected
daily to ensure proper operation.
G. General.
1. Alpine boilers are intended for installations in
an area with a floor drain, or in a suitable drain
pan to prevent any leaks or safety relief valve
discharge resulting in property damage.
2. Alpine boilers are not intended to support
external piping and venting. All external piping
and venting must be supported independently
of the boiler.
3. Alpine boilers must be installed level to
prevent condensate from backing up inside
the boiler.
4. Boiler Installation:
a. For basement installation provide a
solid level base such as concrete where
floor is not level or where water may be
encountered on the floor around boiler.
Table 3-2: Vent Pipe Clearances to Combustible Material
Boiler Clearances to Combustible (and Non-
Combustible) Material:
Models ALP399C and ALP500C:
These boilers are listed for closet installation with
the following minimum clearances – Top = 1 in.
(25 mm), Front = 1 in. (25 mm), Left Side = 10 in.
(250 mm), Right Side = 2 in. (50 mm), Rear = *6
in. (150 mm)
Models ALP600C, ALP700C and ALP800C:
These boilers are listed for alcove installation with
the following minimum clearances – Top = 1 in.
(25 mm), Front = Open, Left Side = 10 in. (250
mm), Right Side = 2 in. (50 mm), Rear = *6 in.
(150 mm).
Note:
When boiler is vented vertically, the minimum
clearance from the rear of the jacket is increased
to 18 in. (460 mm) with a short radius 90° elbow
provided in order to provide adequate space at boiler
rear for installation of vent and air intake piping and
service access.
Boiler Service Clearances – Applicable to all Boiler
Models:
Top = 24 in. (610 mm), Front = 24 in. (610 mm),
Left Side = 24 in. (610 mm), Right Side = 24 in. (610
mm), Rear = 24 in. (610 mm)
The above clearances are recommended for service
access but may be reduced to the Combustible
Material Clearances provided:
1. The boiler front is accessible through a door.
2. Access is provided to the condensate trap
located on the left side of boiler.
3. Access is provided to thermal link located at
the boiler rear.
Listed Direct
Vent System Vent Pipe Material Vent Pipe
Direction Enclosure Vent Pipe
Nominal Diameter
Minimum Clearance to
Combustible Material
Standard
Two-Pipe CPVC/PVC Vent and PVC Combustion
Air Intake
CPVC/PVC
Vertical or
Horizontal
Unenclosed
at all Sides
3 in. (80 mm),
4 in. (100 mm or 110 mm),
6 in.( 150 mm or 160 mm)
1 in. (25 mm)
Optional
Two-Pipe Rigid Polypropylene Vent (or, Flexible
Polypropylene Liner for Vertical Venting only) and
Rigid Polypropylene or PVC Combustion Air Intake
Rigid Polypropylene (or,
Flexible Polypropylene
Liner for Vertical Venting
only)
3 in. (80 mm),
4 in. (100 mm or 110 mm),
6 in.( 150 mm or 160 mm)
1 in. (25 mm)
Optional
Two-Pipe Stainless Steel Vent and Galvanized Steel
or PVC Combustion Air Intake
Stainless Steel
3 in. (80 mm),
4 in. (100 mm or 110 mm),
6 in.( 150 mm or 160 mm)
1 in. (25 mm)
Floor must be able to support weight of
boiler, water and all additional system
components.
b. Boiler must be level to prevent condensate
from backing up inside the boiler.
c. Provide adequate space for condensate
piping or a condensate pump if required.
3 Pre-installation and Boiler Mounting (continued)
WARNING
Asphyxiation Hazard. Adequate combustion
and ventilation air must be provided to assure
proper combustion. Install combustion air
intake per Section 4 “Venting”.
!