Seneca K109TC User manual

Type
User manual

Seneca K109TC is a 4-point temperature-insulated converter for thermocouples that can convert a temperature signal into a voltage or current signal, making it suitable for various industrial applications. It features a compact size, easy DIN rail mounting, and convenient configuration options through DIP-switch settings. The device offers precise temperature measurement with different thermocouple types, including J, K, E, N, S, R, B, and T. Additionally, it provides a passive output that can be used for alarm or thermostat functions.

Seneca K109TC is a 4-point temperature-insulated converter for thermocouples that can convert a temperature signal into a voltage or current signal, making it suitable for various industrial applications. It features a compact size, easy DIN rail mounting, and convenient configuration options through DIP-switch settings. The device offers precise temperature measurement with different thermocouple types, including J, K, E, N, S, R, B, and T. Additionally, it provides a passive output that can be used for alarm or thermostat functions.

ENGLISH - 1/8MI00111 -E3
K109TC
TEMPERATURE-INSULATED CONVERTER FOR THERMOCOUPLES
The K109TC instrument is a 4-point galvanic insulator. It converts a temperature signal
read by a thermocouple into a signal normalised in voltage or current; besides it has a
passive output which commutates at the overcoming of a threshold set through a button on
the front.
The module's main features are its compact size (6.2 mm), attachment to a 35 mm DIN
rail, bus-connector power supply option, quick connection by spring terminals, and easy
configuration in the field by DIP-switch.
Technical Features
General Description
Power supply :
Consumption :
19,2..30 Vdc
max 24 mA at 24 Vdc
Input :
Tables :
Measurement Range :
Minimum span :
Impedance :
Test Current :
CMRR :
(1)
DMRR :
(1) (2)
Thermocouples types: J, K, E, N, S, R, B, T
EN60584-1 (ITS-90)
Depending on the thermocouple type (see Range and
Precision of the Input Table), on the dip-switches
selection (see section)Setting of the Dip-Switches
100 °C
10 MW
<50 nA
>135 dB, refered to power-supply side
>40 dB
(1) The values are valid at the set rejection frequency, with filter ON.
(2) For disturbance values such as the input signal peak does not exceed the limit of
acceptability.
Range and Precision of the Input
Admitted Range
Thermocouple
J
K
E
N
S
R
B
T
0,12 °C0,025 % + 0,29 °C
ResolutionMean Error
-210..1200 °C
-200..1372 °C
-200..1000 °C
-200..1300 °C
-50..1768 °C
-50..1768 °C
-200..400 °C
250..1820 (*)°C
0,17 °C0,025 % + 0,4 °C
0,92 °C0,025 % + 0,2 °C
0,19 °C0,025 % + 0,42 °C
0,66 °C0,025 % + 1,34 °C
0,59 °C0,025 % + 1,19 °C
0,9 °C0,025 % + 1,87 °C
0,13 °C0,025 % + 0,31 °C
(*): Up to 250 °C, the output is considered equivalent to a null temperature.
EN
MI00111 -E3 ENGLISH - 2/8
Insulation Voltage :
Protection Index :
Operating Conditions :
Storage Temperature :
Altitude :
LED Signalling :
Connections :
Conductor Section :
Wire stripping :
Standards :
Box :
Dimensions, Weight :
1,5 kV (50 Hz for 1 min)
IP20
Temperature -20..+65 °C
Humidity 10..90 % at 40 °C non-condensing.
-40..+85 °C
Up to 2000 slm
Fault/Anomaly, state of the auxiliary output
Spring terminals
0,2..2,5 mm2
8 mm
EN61000-6-4/2002 (electromagnetic emission, industrial surroundings)
EN61000-6-2/2005 (electromagnetic immunity, industrial surroundings)
EN61010-1/2001 (safety)
All the circuits must be provided with double insulation from the circuits
under dangerous voltage. The power supply transformer must be built to
compliance with EN60742: “Insulation transformers and Safety
transformers”.
Notes:
- Use with copper conductor.
- Use in Pollution Degree 2 Environment .
- Power Supply must be Class 2.
- When supplied by an Isolated Limited Voltage/Limited
Current power supply a fuse rated max 2.5Ashall be
installed in the field.
PBT (black colour)
6,2 x 93,1 x 102,5 mm, 46 g.
ADC :
Class/Base Prec. :
Thermal Drift :
Response Time : (10..90 %):
Cold junction error :
14 bits
0,1 %
120 ppm/K
< 25 ms (without filter)
< 55 ms (with repeat filter 50 Hz)
1,5 °C Max
0..5 Vdc, 1..5 Vdc, 0..10 Vdc e 10..0 Vdc
Minima load resistance 2 kΩ
0..20 mA, 4..20 mA, 20..0 mA e 20..4 mA
Maximum load resistance 500 Ω
approximately 12,5 V
approximately 25 mA
1 mV for voltage output, 2 A for current outputm
mA or 5 V out put: 350 ppm of the end scale
10 V output : 200 ppm of the end scale
Applicable Voltage : 24 Vac Nominal
Current: 60 mA Max
Voltage Output :
Current Output :
Maximum Voltage :
Maximum Current :
Resolution :
Error :
Static Aux Output :
MI00111 -E3 ENGLISH - 3/8
The auxiliary output has been designed in order to pilot an indicator, a relay of greater
power or the input of a supervisor control system. Through this output the K109 TC
instrument may generate an alarm or may be utilized like a thermostat. The stateNormal
of the output depends on the configuration for the fault of the primary output, so on the
setting of the correspondent dip-switch SW2.7 (see table).Details of Dip-Switch SW2.7
Since during the regulation of the threshold the primary output assumes the value of the
threshold, it is advisable to connect an instrument of measure (a multimeter for example)
to the primary output. Therefore the value in V or mA of the threshold depends on the
scale of the chosen output. The switching is instantaneous to the overcoming of the set
up value.
Description
AUXILIARY OUTPUT
The regulation of the threshold is performed through a button present under the frontal
cover and accessible through the hole by using a little screwdriver. The operation has to
be performed when the module is correctly supplied. It will be necessary to follow the next
procedure:
Pressed and released the button, the primary output starts to represent the value of
threshold. At this point the red led flashes slowly.
If within 5 seconds there is no pression, the system returns to the normal
functioning.
On the contrary at every further pressure, there is an increment or decrement of
approximately 0,2 %; the direction of the variation depends on the Normal state of the
output and therefore on the dip-switch SW2.7 so that the commutation occurs exactly
at the set value, leaving the effect of the hysteresis only at the reset.
If the button is not released but continues to be pressed, after 2 seconds a
continuous increment of 3% starts.
Reached the maximum/minimum value of the chosen scale, the cycle starts again.
During the regulation of the threshold, the auxiliary output follows the normal
functioning, opening and closing, as previously set.
After 5 seconds of button’s inactivity, the set value is memorized and the instrument
continues with the normal functioning.
Note:
The threshold may not be modified in case of internal fault. If the power supply is not
sufficient during the regulation or before the 5 seconds of button’s inactivity are elapsed,
the new value will not be memorized.
Setting of the threshold
Details of Dip-Switch SW2.7
Regulation Type
Furnace (*) Towards the high Closed (led ON) Decrement
Normal State Set Threshold
Refrigerator (*)
Towards the bottom Opened (led OFF) Increment
OFF
SW2.7
ON
Fault
(*) In case of choice of direct output (0/4..20 mA), 0/1..5/10 V)
MI00111 -E3 ENGLISH - 4/8
Installation rules
This module has been designed for assembly on a DIN 46277 rail. Assembly in vertical
position is recommended in order to increase the module's ventilation, and no raceways or
other objects that compromise aeration must be positioned in the vicinity.
Do not position the module above equipment that generates heat; we recommend
positioning the module in the lower part of the control panel or container compartment.
We recommend rail-type assembly using the corresponding bus connector (Code K-BUS)
that eliminates the need to connect the power supply to each module.
K109TC
TC transmitter
with galvanic insulation
0
1
SW1 SW2
K109TC
TC transmitter
with galvanic insulation
0
1
SW1 SW2
1 -Attach the module in the upper part of
the rail.
2 - Press the module downwards.
1 -Apply leverage using a screwdriver (as
shown in the figure).
2 - Rotate the module upwards.
Inserting the module in the rail Removing the module from the rail
Using the K-BUS
1 - Compose the K-BUS connectors as required in order to obtain the number of positions
necessary (each K-BUS permits the insertion of no. 2 modules).
2 - Insert the K-BUS connectors in the rail by positioning them on the upper side of the rail
and then rotating them downwards.
sIMPORTANT: Pay particular attention to the po ition of the protrudent terminals of the
K-BUS. The K-bus must be inserted in the guide with the protrudent terminals on the left
(as shown in the figure) otherwise the modules are turned upside downs.
-Never connect the power supply directly to the bus connector on the DIN
rail.
-Never tap power supply from the bus connector either directly or by using
the module's terminals.
!
MI00111 -E3 ENGLISH - 5/8
It is understood that this configuration is valid only with all the DIP switches at position
0. If also one Dip is moved, it is necessary to set all the other parameter as indicated
on the following tables.
Thermocouple Type :
Line Rejection :
Input Filter :
Measurement Range :
Output Signal :
Output Signal in case of
fault :
Over-Range :
Auxiliary Output
Threshold :
J
50 Hz
Present
0...1000 °C
4..20 mA
Towards the top of the output range
YES: a 2.5% over-range value is acceptable;
a 5% over-range value is considered a malfunction.
0% of the nominal scale
MEASUREMENT RANGE START
6SW1 7 8
Note: for all following tables
The indication indicates that the DIP-switch is set in Position 1 (ON).
No indication is provided when the DIP-switch is set in Position 0 (OFF).
INPUT FILTER (*)
LINE REJECTION
5
4
SW1
SW1
Absent
50 Hz
Present
60 Hz
(*) The input filter stabilizes the measurement and guarantees the repeating of the
disturbance signal overlapping the measurement signal but slows down the response
time. If the maximum response speed is not required, it is advisable to insert it.
THERMOCOUPLE TYPE
1SW1 2 3
K
S
J
R
T
B
E
N
* If all the dip-switches are set to OFF position, the default configuration is valid;
otherwise the value of this parameter is 0 °C, as for the other thermocouple types.
J Type
Default *
K Type
0 °C 0 °C 0 °C 0 °C 0 °C 0 °C 0 °C
R Type S Type T Type B Type E Type N Type
0 °C
100 °C
200 °C
300 °C
500 °C
-100 °C
-200 °C
100 °C
200 °C
400 °C
600 °C
800 °C
-100 °C
-200 °C
100 °C
200 °C
300 °C
400 °C
600 °C
800 °C
1000 °C
100 °C
200 °C
300 °C
400 °C
600 °C
800 °C
1000 °C
50 °C
100 °C
200 °C
-50 °C
-150 °C
-100 °C
-200 °C
400 °C400 °C
500 °C
600 °C
800 °C
1000 °C
1200 °C
1400 °C
100 °C
200 °C
300 °C
400 °C
500 °C
-100 °C
-200 °C
100 °C100 °C
200 °C
300 °C
500 °C
700 °C
-100 °C
-200 °C
All the module DIP switches are at pos. 0 as default configuration. This set corresponds
to the following default configuration :
SETTING OF THE DIP-SWITCHES
Factory setting
MI00111 -E3 ENGLISH - 6/8
MEASUREMENT RANGE END
1SW2 2 3
(*) See the table below for the corresponding values.
Nominal Value Over-range ±2,5 % Over-range ±5 %
20 mA 20,5 mA 21 mA
4 mA 3,5 mA 3 mA
0 mA 0 mA 0 mA
10 Vdc 10,25 Vdc 10,5 Vdc
5 Vdc 5,125 Vdc 5,25 Vdc
1 Vdc 0,875 Vdc 0,75 Vdc
0 Vdc 0 Vdc 0 Vdc
OUTPUT SIGNAL IN CASE OF FAULT
7SW2
Towards the top of the output range
Towards the bottom of the output range
OVER-RANGE (*)
8SW2
YES: a 2.5% over-range value is acceptable; a 5%
over-range value is considered a malfunction.
NO: the malfunction alone causes a 2.5%
over-range value.
OUTPUT
4SW2 5 6
0..20 mA
20..0 mA
4..20 mA
20..4 mA
0..10 V
1..5 V
10..0 V
0..5 V
J Type
1200 °C
K Type
1350 °C 1750 °C 1750 °C 400 °C 1800 °C 1000 °C 1300 °C
R Type Type S T Type B Type E Type N Type
1000 °C
800 °C
600 °C
500 °C
400 °C
300 °C
200 °C
1200 °C
1000 °C
800 °C
700 °C
500 °C
300 °C
200 °C
1500 °C
1300 °C
1100 °C
900 °C
700 °C
500 °C
300 °C
1500 °C
1300 °C
1100 °C
900 °C
700 °C
500 °C
300 °C
350°C
300 °C
250 °C
200 °C
150 °C
100 °C
50 °C
1600 °C
1500 °C
1300 °C
1100 °C
900 °C
700 °C
500 °C
800 °C
600 °C
500 °C
400 °C
300 °C
200 °C
100°C
1200 °C
1000 °C
800 °C
600 °C
500 °C
400 °C
200 °C
Output Signal Limits
LED indications on the front
Red LED Meaning
Fast flashing Internal fault: power supply not sufficient, out of range
offset or reference . Error on reading or writing in flash
(at the start or on threshold setting)
Slow flashing DIP-switch setting error
Set Threshold in progress
Steady light Disconnected thermocouple, out of range input or
temperature compensation
Output limiting in progress
Output
Fault
YES
YES
NO (*)
YES
NO
(*): In this modality the output signal represents the value of the threshold.
MI00111 -E3 ENGLISH - 7/8
Electrical Connections
The module has been designed for spring-type terminal
electrical connections.
Proceed as follows to make the connections:
1 - Strip the cables by 0.8 mm
2 - Insert a screwdriver in the square hole and press it
until the cable lock spring opens.
3 - Insert the cable in the round hole.
4 - Remove the screwdriver and make sure that the cable
is tightly fastened in the terminal.
Power supply
There are various ways to provide the K
Series modules with power.
1 - Direct power supply to the modules by
connecting 24 Vdc power supply directly to
Terminals 7 ( + ) and 8 ( - ) of each module.
Yellow LED Meaning
ON The auxiliary output is closed
OFF The auxiliary output is opened
2 - Using the K-BUS connector accessory for the distribution of the power supply to the
modules via bus connector, in this way eliminating the need to connect power supply to
each module.
The bus can be supplied from any of the modules; the total absorption of the bus must be
less than 400 mA. Higher absorption values can damage the module. An appropriately
sized fuse must be connected in series to the power supply.
3 - Using the K-BUS connector accessory for the distribution of the power supply to the
modules via bus connector and the K-SUPPLY accessory for the connection of the power
supply. The K-SUPPLY accessory is a 6.2 mm wide module that contains a set of
protections designed to protect the modules connected via bus against over-voltage
loads.
The bus connector can be provided with power using the K-SUPPLY module if the total
absorption of the bus is less than 1.5 A. Higher absorption values can damage both the
module and the bus. An appropriately sized fuse must be connected in series to the power
supply.
8 mm
0,2..2,5 mm2
15
6
7
8
2
3
4
POWER
SUPPLY
+
-
19.2..30 Vdc
Set Threshold
Red Led
Yellow Led
Input
The module accepts input from the
following types of thermocouples: J, K, E,
N, S, R, B, T.
The use of shield cables is recommended
for the electronic connections.
Output
Voltage connection - Current connection
(applied current)
The use of shield cables is recommended
for the electronic connections.
Auxiliary Output
The auxiliary output has been designed to
pilot an indicator or a relay of greater power
or the input of a supervisor control system.
15
6
7
8
2
3
4
POWER
SUPPLY
OUTPUT
INPUT
V / I
+
-
15
6
7
8
2
3
4
POWER
SUPPLY
OUTPUT
INPUT +
TC
15
6
7
8
2
3
4
POWER
SUPPLY
OUTPUT
INPUT
AUX
AUX
Disposal of Electrical & Electronic Equipment (Applicable throughout the European Union and other
European countries with separate collection programs)
This symbol, found on your product or on its packaging, indicates that this product should not be treated as
household waste when you wish to dispose of it. Instead, it should be handed over to an applicable
collection point for the recycling of electrical and electronic equipment. By ensuring this product is
disposed of correctly, you will help prevent potential negative consequences to the environment and
human health, which could otherwise be caused by inappropriate disposal of this product. The recycling of
materials will help to conserve natural resources. For more detailed information about the recycling of this
product, please contact your local city office, waste disposal service or thè retail store where you
purchased this product.
This document is property of SENECA srl. Duplication and reprodution are forbidden, if not authorized. Contents of the
present documentation refers to products and technologies described in it. All technical data contained in the document
may be modified without prior notice Content of this documentation is subject to periodical revision.
SENECA s.r.l.
Via Austria, 26 - 35127 - PADOVA - ITALY
Tel. +39.049.8705355 - 8705359 - Fax +39.049.8706287
e-mail: [email protected] - www.seneca.it
ENGLISH - 8/8
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8

Seneca K109TC User manual

Type
User manual

Seneca K109TC is a 4-point temperature-insulated converter for thermocouples that can convert a temperature signal into a voltage or current signal, making it suitable for various industrial applications. It features a compact size, easy DIN rail mounting, and convenient configuration options through DIP-switch settings. The device offers precise temperature measurement with different thermocouple types, including J, K, E, N, S, R, B, and T. Additionally, it provides a passive output that can be used for alarm or thermostat functions.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI