Vacon 100 HVAC Installation guide

Type
Installation guide

This manual is also suitable for

vacon • 0
24-hour support +358 (0)40 837 1150 • Email: [email protected]
INDEX
Document: DPD00472B
Draft release date: 31.1.11
EN: Vacon 100 main switch ............................................................................... 2
1. General ......................................................................................................................2
2. Installation.................................................................................................................2
3. Cable requirements................................................................................................... 6
FI: Vacon 100 -pääkytkin................................................................................... 8
1. Yleistä......................................................................................................................... 8
2. Asennus ..................................................................................................................... 8
3. Kaapelivaatimukset ................................................................................................. 12
DE: Vacon 100 Hauptschalter.......................................................................... 14
1. Allgemeine Informationen....................................................................................... 14
2. Installation............................................................................................................... 14
3. Kabelanforderungen................................................................................................ 19
FR: Interrupteur principal du Vacon 10 .......................................................... 20
1. Général .................................................................................................................... 20
2. Installation............................................................................................................... 20
3. Caractéristiques des câbles.................................................................................... 24
SV: Vacon 100 nätbrytare................................................................................ 26
1. Allmänt .................................................................................................................... 26
2. Installation............................................................................................................... 26
3. Krav på kablar ......................................................................................................... 30
NL: Hoofdschakelaar Vacon 100 ..................................................................... 32
1. Algemeen................................................................................................................. 32
2. Installatie ................................................................................................................. 32
3. Kabelvereisten......................................................................................................... 36
13006.emf
NOTE! You can download the English and French product manuals with applicable safety,
warning and caution information from www.vacon.com/downloads
.
REMARQUE Vous pouvez télécharger les versions anglaise et française des manuels produit
contenant l’ensemble des informations de sécurité, avertissements et mises en garde
applicables sur le site www.vacon.com/downloads
.
EN: Vacon 100 main switch vacon • 2
en
EN: VACON 100 MAIN SWITCH
1. General
The main switch is used for switching off the input power of the drive. This option is available
for frames MR4-MR7 with IP54 protection class and maximum output current 88A, see the ex-
act data in Table 2. The main switch is both CE and UL listed.
Main switch operation principle:
Chapter 2 presents the installation steps, the maximum cable sizes and tightening torques are
given in Chapter 3.
CAUTION! The main switch is a safety device, it is not allowed to use the main switch when
the drive is in operation.
NOTE! An additional auxiliary contact switch is provided with the main switch option. This
contact switch helps in receiving status information of the main switch for PLC, etc.
2. Installation
Table 1. Installation:
1
Remove the cover of the
drive.
2
Remove the two screws
of the main switch and
tilt the switch to the left.
f
2
f
1
L1
L2
L3
U/T1
V/T2
W/T3
3 • vacon EN: Vacon 100 main switch
en
3
Connect the motor cable
“M” (see step 4). Tighten
the screws according to
the tightening torques
given in Table 2. Check
also the tightening of the
factory-installed main
switch cable!
Note! Remember to use
cable grommets pro-
vided with the drive, see
the Vacon 100 installa-
tion manual for detailed
cable installation
instructions!
4
Attaching the cables: fold
the cable shield back-
wards onto the cable and
attach the cable with a
cable clamp on the
shield.
Note! See detailed cable
installation instructions
in the Vacon 100 installa-
tion manual!
5
Install the supply cable
“S” and lead it to the
main switch as shown in
the picture.
Note 1! Protect the
cables as close to the
main switch as possible
with an insulation tube.
Note 2! See detailed
cable installation
instructions in the Vacon
100 installation manual!
M
EN: Vacon 100 main switch vacon • 4
en
6
The motor and supply
cable installation seen
from above.
7
Attach the main switch
screws.
8
Tighten the supply cable
screws on the main
switch according to the
tightening torques given
in Table 2. Please also
check the tightening of
the factory-installed
cable connection screws
on the right side of the
main switch.
MS
2T1
4T2
6T3
1L1
3L2
5L3
5 • vacon EN: Vacon 100 main switch
en
9
MR4: Lead the data cable
“D” under the main
switch and attach it.
MR5-MR7: Lead the data
cable to the terminal
around the main switch
Note 1! Protect the data
cable as close to the ter-
minal as possible with
the cable insulation tube!
Note 2! See detailed
cable installation
instructions in the Vacon
100 installation manual!
10
The data cable installa-
tion in MR4 seen from
above.
11
Close the cover of the
drive
M
S
D
MS
D
2T1
4T2
6T3
1L1
3L2
5L3
EN: Vacon 100 main switch vacon • 6
en
3. Cable requirements
The following table shows the maximum sizes for the cables to be used with the main switch.
Note! Use only copper cables with the main switch option, no aluminium cables allowed!
Table 2. Cable data for the main switch option
Frame Type Maximum mains and
motor cable size
Tightening
torque of the
main switch
screws, Nm
Insulation tube size
for supply cable,
diameter/length,
mm
MR4
0003 2—0004 2 3*1.5+1.5
0.8 10/70
0005 2—0008 2 3*1.5+1.5
0009 2—0012 2 3*2.5+2.5
0003 4—0004 4 3*1.5+1.5
0005 4—0008 4 3*1.5+1.5
0009 4—0012 4 3*2.5+2.5
MR5
0018 2 3*6+6
0.8 16/80
0024 2 3*6+6
0031 2 3*10+10
0016 4 3*6+6
0023 4 3*6+6
0031 4 3*10+10
MR6
0048 2 3*16+16
2 20/80
0062 2 3*25+16
0038 4 3*10+10
0046 4 3*16+16
0061 4 3*25+16
MR7
0075 2 3*35+16
6 25/80
0088 2 3*35+16
0072 4 3*35+16
0087 4 3*35+16
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38

Vacon 100 HVAC Installation guide

Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI