Honeywell TH1110DN User manual

Category
Thermostats
Type
User manual
® U.S. Registered Trademark. Patents pending.
Copyright © 2011 Honeywell International Inc.
All rights reserved.
Installation
Guide
PRO TH2000DH/TH1000DH Series
Thermostats
69-2609EFS-03
This manual covers the following models
• TH1100DH:ForHeatonlysystems
• TH2110DH/TH1110DH:For1Heat/1Coolsystems
• TH2210DH/TH1210DH:For2Heat/1Coolheatpumpsystemsonly
(Pullthermostatfromwallplateandturnovertofindmodelnumber.)
System Types
TH2110DH/TH1110DH:
• Gas,oil,orelectricheatwithair
conditioning
• Warmair,hotwater,high-efficiency
furnaces,1Heat/1Coolheatpumps,
steam,gravity
• Heatonly
• Heatonlywithfan
• Coolonly
• 750mVheatingsystems
TH2210DH/TH1210DH:
• 2Heat/1Coolheatpumps
TH1100DH:
• Gas,oil,orelectricheat
• Warmair,hotwater,steam,gravity
• Heatonly
• 750mVheatingsystems
Must be installed by a trained, experienced technician
Readtheseinstructionscarefully.Failuretofollowtheseinstructions
candamagetheproductorcauseahazardouscondition.
Need Help?
Forassistancewiththisproductpleasevisithttp://customer.honeywell.com
orcallHoneywellCustomerCaretoll-freeat1-800-468-1502
Installation Guide
2
69-2609EFS—03
ENGLISH
M32805
Wallplate installation
Removethewallplatefromthethermostat
asshownatleft,thenfollowdirections
belowformounting.
1. Pullwiresthroughwirehole.
2. Positionwallplateonwall,levelandmarkhole
positions with pencil.
3. Drillholesatmarkedpositionsasshownbelow,
thentapinsuppliedwallanchors.
4. Placewallplateoveranchors,insertandtighten
mountingscrews.
Pullatbottomtoremovethermostat
fromwallplate.
CAUTION: ELECTRICAL HAZARD
Cancauseelectricalshockorequipmentdamage.Disconnectpowerbeforebeginning
installation.
Drill3/16"holesfordrywall.Drill7/32"holesforplaster.
MERCURY NOTICE
Ifthisproductisreplacingacontrolthatcontainsmercuryinasealedtube,donot
place the old control in the trash. Contact the Thermostat Recycling Corporation at
www.thermostat-recycle.orgor800-238-8192forinformationonhowandwhereto
properlyandsafelydisposeofyouroldthermostat.
M32731
TO REMOVE WALLPLATE
PULL HERE
Wallanchors
MountingscrewsWirehole
PRO TH2000DH/TH1000DH Series
3
69-2609EFS—03
ENGLISH
Power options
TH2110DH/TH1110DH:
B Changeovervalveenergizedin
heating
O Changeovervalveenergizedin
cooling
G Fanrelay
Y Compressor contactor
W Heat relay
C 24Vaccommon.For2-transformer
systems,usecommonwirefrom
coolingtransformer.
R 24Vacpowerfromheating
transformer
Rc 24Vacpowerfromcooling
transformer
TH2210DH/TH1210DH:
B Changeovervalveenergizedin
heating
O Changeovervalveenergizedin
cooling
G Fanrelay
Y Compressor contactor
Aux/E Auxiliaryheatrelay
C 24Vaccommon
R 24Vacpower
TH1100DH:
W Heat relay
C 24Vaccommon
R 24Vacpower
Terminal designations
Wiring
M32808
RWYG
B
RcO C
TH2110DH/
TH1110DH
CYGO
BR
Aux/
E
M32809
TH2210DH/TH1210DH
Not
Used
M32806
WC
KEEP WIRES IN
THIS SHADED AREA
REMOVE FACOTRY-
INSTALLED JUMPER
ONLY FOR TWO-
TRANSFORMER
SYSTEMS
CONNECT C FOR PRIMARY
AC POWER (OPTIONAL IF
BATTERIES ARE INSTALLED)
TH2110DH TERMINAL
BLOCK SHOWN
XXXX
M32807
INSERT BATTERIES FOR
PRIMARY OR BACKUP POWER
M32810
RW C
TH1100DH
Not
Used
Installation Guide
4
69-2609EFS—03
ENGLISH
Wiring
2H/1C Heat
Pump System
TH2210DH/TH1210DH
B Changeovervalveenergizedin
heating[5]
O Changeovervalveenergizedin
cooling[5]
G Fanrelay
Y Compressor contactor
Aux/E Auxiliaryheatrelay
C 24Vaccommon[3]
R Power[1]
1H/1C System
TH2110DH/
TH1110DH
(1 transformer)
G Fanrelay
Y Compressor contactor
W Heat relay
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
1H/1C System
TH2110DH/
TH1110DH
(2 transformers)
G Fanrelay
Y Compressor contactor
W Heat relay
C 24Vaccommon[3,4]
R Power(heatingtransformer)[1,2]
Rc Power(coolingtransformer)[1,2]
Heat Only System
TH1100DH
W Heat relay
C 24Vaccommon[3]
R Power[1]
1H/1C Heat
Pump System
TH2110DH/TH1110DH [7]
B Changeovervalveenergizedin
heating[5]
O Changeovervalveenergizedin
cooling[5]
G Fanrelay
Y Compressorcontactor[6]
W [W+Yjoinedbyjumper]
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
Heat Only
System
TH2110DH/TH1110DH
W Heat relay
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
Heat Only
System with
Fan TH2110DH/TH1110DH
G Fanrelay
W Heat relay
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
Cool Only
System
TH2110DH/TH1110DH
G Fanrelay
Y Compressor contactor
C 24Vaccommon[3]
R [R+Rcjoinedbyjumper]
Rc Power[1]
NOTES
Wirespecifications:
Use18-to22-gaugethermostatwire.
Shieldedcableisnotrequired.
[1] Powersupply.Providedisconnectmeans
andoverloadprotectionasrequired.
[2] Removejumperfor2-transformersystems.
[3] Optional24Vaccommonconnection.
[4] Commonconnectionmustcomefrom
coolingtransformer.
[5] UseeitherOorBterminalsforchangeover
valve.
[6] Useasmallpieceofwire(notsupplied)to
connectWandYterminals.
[7] SetfanoperationswitchtoHeat Pump
(seepage5).
Wiring guide — conventional and heat pump systems
CYGO
BR
Aux/
E
M32809
TH2210DH/TH1210DH
Not
Used
RcCYW
GR
M32811
RcCYW
GR
M32812
RcCYWGO
BR
M32813
RcC
WR
M32814
RcCW
GR
M32815
RcCY
GR
M32816
See[notes]below
M32817
RW C
Not
Used
PRO TH2000DH/TH1000DH Series
5
69-2609EFS—03
ENGLISH
W/
Aux
Not
Used
Heat Off Cool Auto On
Fan
M32705
W/
Aux
Not
Used
M32757
Heat Off Cool Auto On
Fan
TH2110DH/TH1110DH only:
• Gas or Oil:Forgasoroil
heatingsystems,leavethefan
operationswitchinthisfactory-
setposition.(Thissettingisfor
systemsthatcontrolthefanina
callforheat.)
• Electric or Heat Pump:Change
theswitchtothissettingforheat
pumporelectricheatsystems.
(Thissettingisforsystemsthat
allow the thermostat to control
thefaninacallforheat,ifa
fanwireisconnectedtotheG
terminal.)
Alignthe2tabsatthetopofthewall-
plate with corresponding slots on the
backofthethermostat,thenpushgen-
tlyuntilthethermostatsnapsinplace.
Thermostat mounting
Setfanoperationswitch.
Pushexcesswire
backintothewall
opening.
Plugwallopening
withnon-flammable
insulation.
Fan operation settings
XXXX
M32818
GAS OR OIL
ELECTRIC OR HEAT PUMP
GAS OR OIL
ELECTRIC OR HEAT PUMP
Installation Guide
6
69-2609EFS—03
ENGLISH
5
5
M32819
Followtheprocedurebelowtoconfigurethethermostattomatchthe
installedheating/coolingsystem,andcustomizefeatureoperationasdesired.
Function
number
Setting
Tobegin,press and hold the s and tbuttonsuntilthedisplaychanges.
Press the s or tbuttontochangethesetting.
Press the s and tbuttonssimultaneouslyforonesecondto
advancetothenextfunction.
Press and hold the s and tbuttonstoexitandsavesettings.
Installer setup
M32713
Heat Off Cool Auto On
Fan
M32758
Heat Off Cool Auto On
Fan
NOTE:Ifyoudonotpressanybuttonfor60secondswhileyouarein
thesetupmenu,thethermostatautomaticallysavesanychangesmade
andexitsthemenu.
PRO TH2000DH/TH1000DH Series
7
69-2609EFS—03
ENGLISH
Setup function Settings & options (factory default in bold)
5 Heating cycle rate
(CPH:cycles/hour)
TH2110DH, TH1110DH
and TH1100DH
5 For gas or oil furnaces of less than 90% efficiency
1 Forsteamorgravitysystems
3 Forhotwatersystems&furnacesofover90%efficiency
6 Forelectricfurnaces
[Othercyclerateoptions:2or4CPH]
6 Auxiliary heat
cycle rate (CPH)
TH2210DH and
TH1210DH
5 For gas or oil furnaces of less than 90% efficiency
1 Forsteamorgravitysystems
3 Forhotwatersystems&furnacesofover90%efficiency
6 Forelectricfurnaces
[Othercyclerateoptions:2or4CPH]
9 Compressor
cycle rate (CPH)
3 Recommended for most compressors
[Othercyclerateoptions:1,2,4,5,or6CPH]
13 Early Start (TH2110DH
and TH2210DH)
1 On **See page 8
0 Off
14 Temperature
display
0 Fahrenheit
1 Celsius
15 Compressor
protection
5 Five-minute compressor off time (See page 8)
0 Nocompressorofftime
20 Clock display
(TH2110DH and
TH2210DH)
0 12-hour display
1 24-hourdisplay
25 Lower temperature
range (TH1100DH only)
0 Standard range 40°F to 90°F (4.5°C to 32°C)
1 Lowerrange(forgaragemode)35°Fto90°F
(1.5°Cto32°C)
40 Restore program
schedule to default
(TH2110DH and
TH2210DH)
0 Off
1 On-programscheduledefaultsettingsarelistedinthe
operatingmanual
Installer setup
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressorprotectionisbypassedduringtesting.Topreventequipmentdamage,
avoidcyclingthecompressorquickly.
Installation Guide
Automation and Control Solutions
Honeywell International Inc.
1985DouglasDriveNorth
GoldenValley,MN55422
http://customer.honeywell.com
® U.S. Registered Trademark
© 2011 Honeywell International Inc.
69-2609EFS—03M.S.Rev.06-11
Printed in U.S.A.
Early Start (SetupFunction13):Earlystartallowstheheatingorcoolingtoturnonbeforethe
programstarttime,sothetemperatureisreachedatthetimeyouset.
Compressor Protection(SetupFunction15):Forcesthecompressortowaitafewminutes
beforerestarting,topreventdamage.Duringthewaittime,themessageCoolOnorHeatOn
(heatpumpsonly)willflashonthedisplay.
Please contact your distributor to order replacement parts.
Cover plate assembly*...................................... PartNumber50002883-001
*Usetocovermarksleftbyoldthermostats.
Temperature Ranges
• Heat:40°to90°F(4.5°to32°C)
• Cool:50°to99°F(10°to37°C)
Operating Ambient Temperature
• 32°to120°F(0°to48.9°C)
Shipping Temperature
• -20°to120°F(-28.9°to48.9°C)
Operating Relative Humidity
• 5%to90%(non-condensing)
Physical Dimensions
• 3-7/16”Hx4-10/16”Wx1-3/16”D
87mmHx119mmWx30mmD
Electrical Ratings
System Voltage(50/60Hz) RunningCurrent
Heat(1ststage) 20-30Vac 0.02-1.0A
(Powerpile) 750mVDC 100mADC
Auxiliaryheat 20-30Vac 0.02-1.0A
Cooling 20-30Vac 0.02-1.0A
Accessories & replacement parts
Special functions
Specifications
3
69-2609EFS—03
ESPAÑOL
Serie PRO TH2000DH/TH1000DH
Opciones de fuentes de energía
TH2110DH/TH1110DH:
B Válvulainversoraalimentadadurante
larefrigeración
O Válvulainversoraalimentadadurante
larefrigeración
G Relédelventilador
Y Interruptorautomáticodelcompresor
W Relédecalor
C 24VCA.Paralossistemasde
2transformadores,utilicecables
comunesdesdeeltransformador
delarefrigeración.
R Corrientede24VCAdeltransformador
decalefacción
Rc Corrientede24VCAdeltransformador
derefrigeración
TH2210DH/TH1210DH:
B Válvulainversoraalimentada
durantelarefrigeración
O Válvulainversoraalimentada
durantelarefrigeración
G Relédelventilador
Y Interruptorautomáticodel
compresor
Aux/E Reléauxiliardecalor
C 24VCA
R Corrientede24VCA
Designación de terminales
Cableado
M32808
RWYG
B
RcO C
TH1110DH
CYGO
BR
Aux/
E
M32809
TH2210DH/TH1210DH
Not
Used
TH1100DH:
W Relédecalor
C 24VCA.
R Corrientede24VCA
M32810
RW C
TH1100DH
Not
Used
MS32806
WC
SE MUESTRA EL
BLOQUE DE
TERMINALES DEL
MODELO TH2110DH
MANTENGA LOS CABLES EN
ESTA ÁREA SOMBREADA
QUITE EL PUENTE
INSTALADO EN LA
FÁBRICA SÓLO EN
LOS SISTEMAS
CON DOS
TRANSFORMADORES
CONECTE C PARA SUMINISTRAR
CORRIENTE CA (OPCIONAL SI LAS
BATERÍAS ESTÁN INSTALADAS)
XXXX
MS32807
COLOQUE LAS BATERÍAS PARA SUMINISTRO
DE ENERGÍA PRINCIPAL O DE RESPALDO
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24

Honeywell TH1110DN User manual

Category
Thermostats
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI