1 PACKAGE CONTENTS
CAUTION!
Do not mount on conductive surface.
Do not open the enclosure frequently.
Circuit of KDP KNX 01 is a low voltage circuit. Never
connect it with standard 220V circuit or put it into a same
Wiring Tube with the circuit.
Presence detector for KNX
Home & Building Control System
KDP KNX 01
INSTRUCTION
MANUAL
TECHNICAL SPECIFICATIONS
21 - 30VDC (supply by KNX bus)
Rated Voltage
Current
Consumption
EIB / KNX
Operate: Approx. 10mA
Standby: Approx. 5mA
Light Measuring
Sensitivity
Operating
Temperature
o o
-20 C to +50 C
Environmental
Protection
IP44
Detection Range 360° circular, up to Φ9m at height of
2.5m
Adjustable via ETS in 4 steps or IR
remote control
-11KNX
10 - 2000Lux
Connection Type
Bus connection terminal
Φ0.8mm, single core
Output
5 channels
2 channels for HVAC
1 channel for Alarm)
(2 channels for lighting
Settings
Settable by ETS or IR-11KNX remote control
Material and
Colour
Plastic, white
Standard and
Safety
IEC 61000-6-1 / IEC 61000-6-3 /
EN 55014 / EN 50491
Installation and assembly of electrical equipment
must be carried out by qualified electricians.
Contact a qualified electrician in the event of fault
or break down.
3.2.6 2-level (Standby Light) function
In auto mode, when the ambient light level falls below the
pre-set Lux value, detector will enter into 2-level mode
function automatically.
Set “STBY Time” to “infinity (∞) under auto mode, detector
will enter into 2-level mode when the delay off time is
expired, and load will change to turn on according to the
setting of “STBY Light”. During which, if the movement is
detected, load will turn on with the setting illumination
(100% or the dimmed illumination) and then turn to the
setting illumination of “STBY Light” if movement is no
longer detected and the delay off time has expired. It will be
cycled until the ambient light level is higher than the switch
off Lux value and lasts for 5min, then turns off and detector
resumes to auto mode function.
Set “STBY Time” to other position except for “infinity (∞)
under auto mode, the actions of detector are basically same
as above mentioned, but the duration is according to the
selected “STBY Time” value.
Note: When set the IR
KNX remote control to “ “, load
will turn off automatically after reaching the auto off
time.
Set “STBY Light” to “disable” (OFF), load will be off when the
delay off time is expired.
STBY
OFF
The purpose of walk test is to select a proper location and gain
the desired detection coverage. Please set the operating mode
to “Test” via IR remote control IR KNX or ETS-Software, then
refer to the following steps conducting a walk test. Lux setting
value is invalid.
It takes approx. 60sec for detector to warm up after power is
supplied, then it enters into normal operation mode to carry
out a walk test.
4 WALK TEST AND LENS SHIELD
NOTE
4.1 Walk test
FIG.10
Walk test procedure
4.1.1 Tester must be within detection coverage.
4.1.2 Switch on the power.
4.1.3 KDP KNX 01 takes approx. 60sec to
warm up with load and red LED turning on, then turn off
after warming up time.
4.1.4 Walk from outside across to the detection pattern
until red
LED and load turn on for approx. 2sec, then turn off, the
next trigger should be 2sec interval (See FIG.10).
4.1.5 Adjust sensitivity (Meter) setting by IR KNX or ETS to
reach desired coverage.
4.1.6 Adjust Time setting by IR KNX or ETS to change the switch
off delay time.
4.1.7 Refer to point “4.2 Usage of lens shield”, detection range
and angle can be changed by using lens shield .
4.1.8 Repeat the steps 4.1.4 to 4.1.6 until it meets user s
demands.
NOTE
Do not attempt to open or repair the unit without qualified
electrician while it is malfunctioned.
The following conditions may cause lower sensitivity:
In very foggy days, the sensitivity may be less due to
moisture collecting on the lens.
In very hot days, the sensitivity may be less since high
ambient temperature is close to body temperature.
In very cold days when heavy clothing is dressed,
especially the facial area is covered, very little heat will
be emitted from the body causing the unit to be less
sensitivity.
Cleaning: Wipe with dry cloth only. Soap or rough cloth
may damage the detector lens.
4.2 Usage of lens shield
4.2.1
KDP KNX 01
has provided 2 lens shields
for masking the undesired detection area (See FIG.11).
None
Small segment
A+B+C
A+B
A
Φ9m
Φ2m
Φ5m
Φ7m
o
30 per piece
Used lens shield Covered detection range
10
Lux
1000
Lux
50
Lux
150
Lux
500
Lux
1
Min
15
Min
Min
30
3
Min
5
Min
CH1 CH2
RESET
STBY
OFF
Min
15
5
Min
STBY
50%
STBY
30%
STBY
10%
DIM
Button
-
e
on
-
,
Function
To dim the brightness of light
IR KNX is locked: Press “
D
I
M
” button to start
dimming, then pressing “
D
I
M ” button to stop dimm
ing while the light level matches users desire, but
the value will not be saved in detector, and it will b
dimmed automatically according to last illuminati
setting value while the lighting is switched on next
time.
IR KNX is unlocked: Press “
D
I
M ” button to start
dimming, then pressing “
D
I
M “ button to stop dimm
ing while the light level matches users desire and
the value will be saved in detector and it will be
dimmed to this light level automatically while the
lighting is switched on next time.
Under unlocked status, by pressing “
C
H
1
” or “
C
H
2
button firstly to select desired channel for value
setting, then press “
DI
M ” to dim the light. If press
DI
M ” button directly without selecting any channel
both C1 and C2 can dim the light simultaneously.
To reset settings on presence detector
RESET
By pressing “ ” button aiming to the detector, all
settings made by IR on detector will be deleted and
all MEMO (saved) data will be deleted as well.
Afterwards, the detector turns to work according to
the settings by potentiometers.
Channel 1 or channel 2 selection
1. By pressing “
C
H
1 ” under unlock mode to select
C1” for corresponding value setting.
2. By pressing “
C
H
2 ” under unlock mode to select
C2” for corresponding value setting.
Remark:
C3 & C4 are uncontrolled by IR KNX.
Lux adjustments of channel
1. Under unlock mode, press “ ” or “ ” firstly to
select desired channel for value setting. Then,
press corresponding button to select the desired
light level threshold for switching on the
connected load of C1 or C2.
2. Users can set the desired Lux value by pressing
“ ” button.
CH1 CH2
Time adjustments of channel
1. Under unlock mode, press “ ” or “ ” firstly to
select desired channel for value setting. Then,
ypress corresponding button to set the exactly dela
off time of C1 or C2.
2. Users can set the desired delay off time of C1 or
C2 by pressing “ ” button.
CH1 CH2
Load’s illumination time in standby mode
1. Under unlock mode, press “ ” or “ ” firstly to
select desired channel for value setting. Then,
press corresponding button to set the desired load
on time of C1 or C2.
2. Users can set the desired load on time of C1 or
C2 by pressing “ ” button.
CH1 CH2
Load’s illumination of standby mode
1. Under unlock mode, press “ ” or “ ” firstly to
select desired channel for value setting. Then,
press corresponding button to set the desired load
on illumination for standby mode of C1 or C2.
2. Users can set the desired load on illumination for
standby mode of C1 or C2 by pressing “ ”
button.
CH1 CH2
Manual
12
Lens
shield
1
IR remote
controller
(For
optional
purchase)
IR-11
XLU
Quantity
IR-11
TESTTEST
Pattern
Item Detector
1
RESET
A/M
10
LUX
60
Min.
60
Min.
10
Sec.
1
Min.
5
Min.
3
Min.
15
Min.
15
Min.
1sec.
5sec.
30
Min.
30
Min.
2000
LUX
30
LUX
100
LUX
400
LUX
OS-409P -C / 409PA -C / 409S-Ci i
R
EMTI 1
2EMIT
FIG.1-C
73
7676
67
50
76
6
OPTIONAL PURCHASE UNIT
6.1
KDP KNX 01
can be controlled by the
infrared remote
control IR KNX to make the operation
more easier and
convenient (See FIG.13).
IR KNX
1
Min
50%
STBY
30%
STBY
10%
STBY
10
Lux
1000
Lux
50
Lux 150
Lux
500
Lux
Lux
Time
MEMO
IR-11KNX
SEN
SEN
15
Min
OFF
STBY
Min
15
5
Min
Prog.
Min
30
3
Min
5
Min
CH1
DIM CH2
RESET
TEST
OFF
ONON
SEN
SEN
Prog.
RESET
MEMO
MEMO
Function
Button
1. Set the desired Lux, time, STBY and STBY% values
on one detector by using IR remote controller.
2. Then by pressing “ ” button for approx. 3sec
aiming to above detector, the Lux, time, STBY and
STBY% settings of this detector will be saved into
this IR remote controller by detector’s LED flashing.
3. By pressing “ ” button again for approx. 1sec
aiming to a new detector, the saved settings can
be duplicated to the new detector.
4. Transfer the settings to detectors desired by
repeating above last step. If no data is saved in IR
remote controller, detector has no reaction after
press “ ” button.
5. Battery removed for more than 5sec or “ ”
button is pressed, all the data in IR remote
controller will be deleted.
To save latest setting values and duplicate
to other detector
MEMO
MEMO
10
Lux
50
Lux
Under unlocked status, by pressing “ ” button to
sum the same kind value, one time only during
each setting period. Take setting Lux value for
instant, press “ ” + “ ”+ “ ”, the final value
is 60Lux.
“ ” is only valid for setting value of Lux / Time /
STBY / STBY%.
“ ” is invalid without pressing any values of Lux /
Time / STBY / STBY% first.
n
LED flashes quickly for 5sec, and the alternative of
10Lux or 2000Lux value will be stored depending
on under 10Lux or above 2000Lux value.
Actual ambient light level can be read-in as
threshold for switching the connected load, if the
provided Lux values do not match users
requirement.
The steps are as below:
Under unlocked status of IR KNX, press “
CH1
” or
CH2
” button to select the desired load to be
controlled. Press “ ” button till detector s LED
(red LED is for C1 indication and green LED is for
C2 indication) flashing to enter into learning
mode, learning time is 10sec. Then the actual
ambient light level is read-in confirmed by both
load and LED turn on for 5sec to indicate
IR KNX learning successfully and then turn off.
Afterwards, it returns to Auto mode.
Note:
If the ambient light level is out of the range
of 10 - 2000Lux, detector will learn for 10sec, the
Automatically read-in of actual light level
function for lighting control
Download the ETS software
Prog.
Under unlock mode, press “ ” button to download
,the ETS software with blue LED of detector turning on
and then turns off if detector connects with KNX
devices successfully.
Adjustment on sensitivity of detector
SEN
SEN
1. By pressing “ ”or “ ” buttons to set the
sensitivity of detector. Each time the user presses
the button, the sensitivity of sensor would increase
g.or decrease 25% with indication of red LED flashin
2. By pressing “ ” button to increase the sensitivity
of detector.
3. By pressing “ ” button to decrease the sensitivity
of detector.
4. When the sensitivity of detector is at its highest or
lowest level which is confirmed by red LED keeping
on for approx. 2sec.
SEN
SEN
Please disconnect power completely and read the
entire instruction manual carefully before installation.
3 INSTALLATION AND WIRING
3.1 Select a proper location
3.1.1
installation height is 2.5m to gain the optimal detection
o
pattern, reaching up to diameter of 9m and cover 360
detection angle (See FIG.2).
It can be installed at the height of 2 - 5m, the recommended
FIG.2
Since the detector is in response to temperature change, please
avoid the following conditions (See FIG.4-A & FIG.4-B):
Avoid pointing the detector toward the objects which
are highly reflective, such as mirror, glass, etc.
Avoid mounting the detector near heat sources, such as
heating vents, air conditioners, lights, etc.
Avoid aiming the detector toward the objects which may be
swayed in the wind, such as curtain, tall plants, etc.
surfaces
3.1.3 Helpful tips for installation
Top view Side view
Φ4m
Minor motion
Φ9m
360°
Major motion
4.5m 4.5m2m2m 0
2.5m
Minor motion
3.1.2
It is more sensitive to movement across the detector and less
sensitive to movement directly toward to detector which will
reduce the detection coverage (See FIG.3).
Pay attention to the walking direction in the test proceeding.
FIG.3
3.2 Function
3.2.1 Auto / Semi-auto mode (Absence detection function)
This function is enabled with ETS setting. Please refer to section
1 Parameter setting“ and 2Communication objects description“
of part
for detail information.
3.2.2 Test mode
Parameters can be set via the ETS (Engineering Tool Software) or
IR KNX remote control.
Test mode switches to the RUN status after “storing, or 10min
after activating the test mode. Load and red LED are
uncontrolled by Lux setting under the Test mode. Once the
detector is triggered, both load and red LED turn on for 2sec,
then turn off, and the next triggering should be 2sec interval.
3.2.3 Manually ON & OFF and DIM Switching function
This function is enabled with ETS setting. Please refer to section
1 Parameter setting“ and 2Communication objects description“
of part
for detail information.
3.2.4 Master/Slave selection
Can only be set by ETS software. Please refer to section 1
“Parameter setting“ and 2 “Communication objects description
of part
for detail information.
3.2.5 Ambient light appraisal
According to the changeable ambient light level, detector can
postpone delay time of turning on and off load to avoid its
unnecessary on or off switching due to rapid ambient light
change:
Ambient light level changes from bright to dark:
To avoid unnecessary switching ON/OFF load due to
temporary ambient light value change caused via nature, e.g.
a passing cloud, the detector has been designed with a 10sec
delay for activating the light on and the detector will ignore
any movement within the 10sec delay time, and the red LED
will be continuous on as indication, but the detector has no
reaction during the 10sec delay time.
Ambient light level changes from dark to bright:
If the ambient light level continuously exceeds the switch off
Lux value for 5min, there are different reactions according to
the time setting value.
Time setting > 5min, the light will be automatically switched
off after 5min.
Time setting <5min, the light will be automatically switched
off when the set time reached if no movement is detected
during the 5min. But if there is movement detected within the
5min, the time will be reset upon detection and until 5min
later, the light is switched off.
W
FIG.4-BFIG.4-B
FIG.4-A FIG.4-B
4.2.2 After user choosing the desired detection area, the redundant
lens shield should be eliminated.
4.2.3 Fixing lens shield: There is slot around the lens and insert the lens
shield into slot (See FIG.12).
The shadow part of the lens shields in the FIG.11 is referring
to the cutoff parts.
FIG.11
Φ9m
30o
0
Φ7m
Φ5m
Φ2m
Part of the lens shield is used.
o
3
A
B
C
Lighting /
HVAC
device
does not
turn on
Problem
FIG.12
5
TROUBLE SHOOTING
When
KDP KNX 01
works abnormally, check
assumptive
problems and suggested solutions in following table
that will
hopefully solve your problem.
Nuisance
triggered
Red LED
does not
turn on
Avoid aiming the detector
towards any heat sources,
such as air conditionings,
electric fans, heaters or any
highly reflective surfaces.
Make sure there are no
swaying objects within the
detection coverage.
There are heat
sources, highly
reflective objects or
any objects which
may be swayed in
the wind within the
detection coverage.
Possible causeProblem Suggested Solution
1. Not set to Test
mode.
2. Exceeding the
detection range.
3. LED indicating
function is set to
Disable.
1. Set to test mode.
2. Walk in the effective
detection range of Φ9m.
3. Set the LED indicating
function to “Enable” via
ETS software.
Lighting /
HVAC
device
does not
turn off
1. Set auto off time to a
shorter time and check if
the load is switched off or
not according to the
pre-set delay off time.
2. Keep be away from
detection coverage to
avoid activating detector
while doing the test.
3. Refer to wiring diagrams
for correct connection.
1. Auto off time is
set too long.
2. Detector is
nuisance
triggered.
3. Incorrect wiring
1. Power does not
turn on.
2. Incorrect wiring
3. Incorrect Lux
setting.
4. Malfunctioned
load.
5. Unable to detect
movement.
1. Switch on the power.
2. Refer to wiring diagrams
for correct connection.
3. Check if Lux is set to the
correct position.
4. Replace the disabled load
with a new one.
5. Check detection range
setting.
Possible cause Suggested Solution
Button Function
TEST Test mode
Detector load is on (except 8hrs on mode): By
pressing “ ” button, if load switches off and
detector’s LED flashes quickly for 2sec, meaning
the detector is unlocked and enters into IR setting
mode. If load keeps be on and detector’s LED
keeps be on 2sec, detector is locked and no
adjustments of IR are workable.
Detector load is off (except 8hrs off mode): By
pressing “ ” button, if load switches on / off
sequentially and detector’s LED flashes quickly for
2sec, meaning the detector is unlocked and enters
into IR setting mode. If load keeps be off and
detector’s LED keeps be on for 2sec, then the
detector is locked.
Detector will be locked automatically when power
is re-supplied after power went off.
When all IR settings were finished without pressing
“ ” button, the detector will be locked auto-
matically after 2min if no buttons were pressed.
Under locked status, no buttons are workable
(except “ ” & “ ” & “ ” buttons).
DIM
To lock / Unlock IR KNX buttons
Pressing “ ” is inactive under lock mode.
By pressing “ ” button, the load connected to
detector will be turned off for 8hrs.
Detector will return to auto mode after 8hrs. Or
press “ ” button again to exit this “8hrs off mode
e.during this period, detector will return to auto mod
To set load off for 8hrs
Or switching off power supply of presence detector
for 5sec and re-supply it again to lead detector to
auto mode.
Load can be led to on mode by pressing “ ”
button under off mode.
Under unlocked status, pressing “
C
H
1
” or “
C
H
2
button firstly to select desired channel for value
setting, then press “ ” button to switch load off
for 8hrs. lf press “ ” button directly without
selecting channel, both CH1 and CH2 will turn off
for 8hrs simultaneously.
Remark: (1). CH1=C1; CH2=C2
(2). C3 & C4 are uncontrolled by
IR KNX.
CH1 CH2
Short press “TEST”button in first time under unlock
mode, detector will enter into test mode with its red
LED flashing quickly for 2sec (f=3Hz) for indication,
and press it again to quit test mode with its red LED
turning on for 2sec for indication. Detector will quit
ythe test mode and enter into auto mode automaticall
if user does not quit the test mode manually after
10min.
FIG.13
6.2 IR KNX remote control function:
Button Function
Pressing “ ” is inactive under lock mode.
By pressing “ “ button, the load of detector will
be turned on for 8hrs.
Load will be turned off after 8hrs and return to
auto mode or press “ “ button again to exit this
“8hrs on mode” during this period, detector will
return to auto mode. Or switching off power
supply of presence detector for 5sec and re-supply
it again to lead detector to auto mode.
Load can be led to off 8hrs mode by pressing “ ”
button under on mode.
Under unlocked status, pressing “ ” or “ ”
button firstly to select desired channel for value
setting, then press “ ” button to switch load on
for 8hrs. lf press “ ” button directly without
selecting channel, both CH1 and CH2 will keep
on 8hrs simultaneously.
Remark: (1). CH1=C1; CH2=C2
(2). C3 & C4 are uncontrolled by IR KNX .
To set load on for 8hrs
CH1 CH2
KDP KNX 01
2
PRODUCT DESCRIPTION
2.1 Features
The presence detector is used to control devices, such as:
Lighting, HVAC, Alarm.
For use in KNX (EIB), TP (twisted pair) bus system in conjunction
with other KNX components.
Parameter and function settings via ETS (Engineering Tool
Software) or IR KNX remote control.
The IR remote control is available for quick and convenient
setting (for optional purchase).
Wood screws
Φ3x8mm
EVA washer
Junction box
1 2
Wood screws
Φ4x25.4mm
1
Quantity
Item
Quantity
Supporter
1
Pattern
Pattern
22
Item Cable tie
Optional accessories for surface mounting
2.2 Dimension (See FIG.1-A & FIG.1-B
& FIG.1-C)
KDP KNX 01:
Φ75 x 78mm
Wood screws
Φ2.6x14mm
2
Cable clamp
Rubber gasket
Non-dropping
screw
Protection cap
FIG.7
3.4.1.2 Use a screwdriver to loose two screws to take down the
protection cap and take out the cable clamp from it.
3.4.1.3 Break the rubber gasket, then feed cables through it (See
FIG.7).
3.2.7 Constant light control
According to the changeable ambient light level, the load can
dim to bright or dark automatically to match the Lux setting value
(Lux setting value by ETS is measured the mixed light level of
artificial light and the ambient light).
3.2.8 Alarm function
The alarm function can be set to react differently or the same at
switch ON and switch OFF.
The alarm output (object 18) can be locked using object 17.
Options for behaviour at switching lock ON or OFF via object
17 include “no reaction”, “switch OFF”, “switch ON”.
The number of detected movements within a time frame can be
set.
3.3 Wiring diagrams
KNX-BUS
FIG.5
3.4 Installation procedure
3.4.1 Ceiling flush mounting
3.4.1.1 To install a detector, please drill a hole in diameter of 65mm
on ceiling board and keep the power cable outside. Please
strip off 6 - 8mm of cable sheathing for wiring (See FIG.6).
Drill a hole with
Φ=65mm on the
ceiling
Φ=65
30 - 35mm
6 - 8mm
FIG.6
For 2 round cables of
Φ5 - Φ6mm
For one or two flat
cable(s) of 4 x 8mm
Big
grove
Small
grove
Big grove
Small
grove Small grove
For 2 round cables of
Φ5 - Φ6mm
Big
grove
For 2 round cables of
Φ3mm
For round cable of
Φ5 - Φ12.5mm
For round cable of
Φ3 - Φ5mm
For 2 round cables of
Φ3mm
3
of the protection cap to be aligned the symbol
of housing (See FIG.7), then screw the
protection cap tightly.
3.4.1.5 For product with cable clamp, the clamp has offered two
groves for holding cables in different diameters (See
FIG.8-A).
3.4.1.6 Close up two spring clips of detector and insert detector
into the drilled hole on ceiling (See FIG.8-B).
.4.1.4 Please refer to FIG.5 for correct wiring and get “ ” symbol
with
FIG.8-A
Φ65mm Power cable
Spring clips
FIG.8-B
3.4.1.7 Restore the power supply.
3.4.2 Ceiling surface mount
KDP KNX 01 also can be surface mountedwith surface mount
junction box.
Surface Fixing 1 2
FIG.9
43 5
Manual
1
2
Lens
shield
1
IR remote
controller
(For
optional
purchase)
IR-11
XLU
Quantity
IR-11
TESTTEST
Pattern
Item Detector
1
RESET
A/M
10
LUX
60
Min.
60
Min.
10
Sec.
1
Min.
5
Min.
3
Min.
15
Min.
15
Min.
1sec.
5sec.
30
Min.
30
Min.
2000
LUX
30
LUX
100
LUX
400
LUX
OS-409P -C / 409PA -C / 409S-Ci i
R
EMTI 1
2EMIT
KDP KNX 01 (with cable clamp)
FIG.1-B
With surface mounting Junction box (for optional purchase)
FIG.1-A
KDP KNX 01(with cable clamp):
Φ75 x 96mm
1.7 Light control output – Constant lightC1 / C2
1.5 Light control output DimmingC1 / C2
F “Light control output C1 –Dimming” parameter windowsIG.18
1.6 Light control output C1 / C2 – Standby values
F “Light control output C1 –Standby values”
parameter windows
IG.19
Dimming
value during
ON phase
Default:
100%
It is used to set the initial value while switching
on the lighting.
Output setting of absolute
brightness
1% -
100%
Menu Function
Light standby
time
Default:
Disable nDeactivate the standby light functio
and load will turn off directly when
the delay time is elapsed.
Disable
Enable
Standby time
Default:
5min Click the menu of standby delay off
time in the edit interface to set the
utdesired value for Light control outp
C1.
Standby
brightness
Default:
10% sClick the menu of standby brightnes
din the edit interface to set the desire
value for Light control output C1.
1 -
60%
%
Menu Function
30sec -
60min
Select “Disable” means deactivating the
standby light function and load will turn off
directly when the delay time is elapsed.
It is used to set standby brightness delay time
and select STBY time via drop-down list.
Activate the standby light function
and detector enters into standby
light control mode when the delay
time is elapsed.
It is used to set standby brightness and select
STBY light via drop-down list.
F “Light control output C1 –Constant light
parameter windows
IG.20
1.9 Alarm function
F Alarm function parameter windowsIG.22
2 COMMUNICATION OBJECTS
DESCRIPTION
In this section will introduce the communication objects, The
objects will show by setting the function enable .
2.1 Overview
The following table shows the default settings of the
communication objects:
You can see the default values for the communication objects
from the upper chart. The priority of the particular
communication objects as well as the flags can be adjusted by
user as desired.
HVAC delay
time
Default:
5min
It is used to set the read-in delay time when the
detector is triggered, and use the drop-down list
for time selection.
Click the menu of delay off time in
the edit interface to set the desired
value for HVAC control output C3.
Behaviour
at switching
on lock by
communi-
cation
object
Default:
No reaction
5sec -
60min
Click the menu can nset the operatio
mode when HVAC is switched on.
It is used to set the output status of detector when
it is triggered and switched on.
Behaviour
at switching
off lock by
communi-
cation
object
Default:
No reaction
Number of
switch-off
windows
Default:
10
Menu Function
Behaviour
at switching
on lock by
communi-
cation
object
Default:
No reaction
It is used to select the behavior when ON: “no
reaction”, OFF”, ON”.
0 - 100
Behaviour
at switching
off lock by
communi-
cation
object
Default:
No reaction
HVAC
switch-
'ON' delay
Default:
1min
It is used to set the switch on delay time of HVAC
when a person presents in detection area and
trigger the detector, in order to avoid HVAC
control system start immediately when the person
presents in a short period.
Click this menu can set the switch on
delay parameter of HVAC.
Menu Function
0 - 30min
Object Function Description Object Function Description
Object 11:
Output:
C1
Constant
light
control” -
Relative
dimming
Object 12:
“Output:
C2 Light
control
output -
ON/OFF
Settings for
lighting
channel 1 -
Relative
dimming
control
Settings for
lighting
channel 2 -
ON/OFF
Refer to the description of
Object 9.
Object
Output:
C2 Light
control
dimming
value” -
Absolute
dimming
13: Settings for
lighting
channel 1 -
Absolute
dimming
control
Refer to the description of
Object 10.
Object 14:
Output:
C2
Constant
light
control” -
Relative
dimming
Settings for
lighting
channel 2 -
Relative
dimming
control
Refer to the description of
Object 11.
Object 15:
Output:
C3 HVAC
control
output -
ON/OFF
Settings for
HVAC
channel 3 -
ON/OFF
If persons are detected,
depending on the input delay, an
sON telegram is sent. If no person
are detected, depending on the
switch-off delay time, an OFF
telegram is sent.
Object 16:
Output:
C4 HVAC
control
output -
ON/OFF
Settings for
HVAC
channel 4 -
ON/OFF
Refer to the description of
Object 15.
This object is a constant lighting
control object of detector. When
the movement is detected or
receiving a telegram form slave
detector, the output sends an ON
telegram via this object and
execute constant lighting control
function refer to the setting of
Preset set point during delay off
time. If no person is present, an
OFF telegram is sent once the
switch-OFF delay time has
elapsed.
Object 17:
Output:
Lock
alarm” -
“1” locks ;
“0”unlocks
Settings for
Alarm
channel 3 -
“1” locks ;
“0”unlocks
“1” locks the alarm function,
while “0” unlocks the alarm
function.
Object 18:
Output:
Alarm
output -
ON/OFF
Settings for
Alarm
channel 3 -
ON/OFF
An alarm is triggered if a
continuous number of movements
are detected within a parameter
is able time frame. Different time
frames can be defined for the
switching ON and OFF of an
alarm.
It is used to set the output status of detector when
it isn’t triggered and switched off.
Click the menu can nset the operatio
mode when HVAC is switched off.
It is used to set the number of times the object
moves within a certain period of time to turn off
the alarm.
It is used to set the number of times
the object moves within a certain
period of time to turn off the alarm.
It nis used to select the behavior whe
ON: “no reaction”, OFF”, ON”.
It is used to select the behavior when OFF: “no
reaction”, OFF”, ON”.
It nis used to select the behavior whe
OFF: “no reaction”, “OFF”, “ON”.
Object 4:
“Measured
Lux value
output" -
Current
light value
Report the
internal Lux
value of
detector
Send the report of detector's
internal Lux value. In order to
make it easier for ETS / other
devices to read the internal Lux
value of detector, the detector
will report the measured Lux
value to Bus every 5sec when the
object is switched on.
Object 6:
“input: C2
manual
input” -
ON/OFF/
Dim
Channel 2 -
ON/OFF/Dim
manual control
Refer to the description of
Object 5.
Object 7:
“input: C3
manual
input -
ON/OFF
Channel 3 -
ON/OFF
manual control
Receive the telegram from the
dpush button (ON/OFF) connecte
to the bus and control channel 3.
Remark: The input can be
gavailable on when settin
o“Reaction rising edge” t
on” and “Reaction on
falling edge” to “off .
Object 8:
“input: C4
manual
input” -
ON/OFF
Channel 4 -
ON/OFF
manual control
Refer to the description of
Object 7.
Object 9:
Output:
C1 Light
control
output -
ON/OFF
Settings for
lighting
channel 1 -
ON/OFF
When the movement is detected
and the ambient light level is
below the pre-set Lux value, the
output sends an ON telegram. If
ambient light is sufficient and/or
no person is present, an OFF
telegram is sent once the switch-
OFF delay time has elapsed.
Object 10:
Output:
C1 Light
control
dimming
value” -
Absolute
dimming
Settings for
lighting
channel 1 -
Absolute
dimming
control
This object is a absolute object
for lighting control channel of
detector. When the movement is
detected or receiving a telegram
form slave detector, the output
sends a pre-set light level
rstelegram via this object and ente
into delay off mode. When the
delay off time is elapsed, the
output sends a pre-set Standby
brightness telegram and enters
into Standby mode and sends an
OFF telegram once the Standby
delay time has elapsed.
No reaction
Switch off
Switch on
No reaction
Switch off
Switch on
No reaction
Switch off
Switch on
No reaction
Switch off
Switch on
Possible causeProblem Suggested solution
6.3 Trouble shooting of IR KNX
When remote controller IR KNX works abnormally, please
check
assumptive problems and suggested solutions in following
chart
that hopefully solve your problem.
Detector
fails to
receive
signal
1. Exceed the
Transmission
range.
2. Low battery
power.
3. Detector works
abnormally.
1. Operate within transmission
range (<10m), and ensure
IR-11KNX aiming directly to
the detector.
2. Replace a new battery.
3. Check the trouble of detector,
then refer the TROUBLE
SHOOTING of detector
manual for repairing.
No
signal
1. Low battery
power.
2. Press two or
more buttons
once.
3. The battery
insulation sheet
is not took out.
1. Replace a new battery.
2. Press one button once.
3. Take out the battery
insulation sheet.
Fail to
transmit
signal
Unlock IR KNX.
In locked mode.
FIG.14 “General-Master parameter windows
PA
R
T I
I
ET
S S
o
f
t
w
a
re Set
t
i
ng
s
The database of KDP KNX 01
is designed
by ETS4.0, please
refer to the following introduction for the
interface and the
application parameter of function.
Detector has five output channels, they are Light control output
C1, Light control output C2, HVAC control output C3, HVAC
control output C4 and Alarm function. Each channel is
independent and C1 / C2 is the same channel; C3 / C4 is the
same channel, so that it is enough to know C1, C3 and alarm
function. Please refer to the following description for the
detailed information .
1
PARAMETER SETTING
1.1General-Master
1.2 General-Slave
FIG.15 “General-Slave” parameter windows
1.3 Motion sensor
F “Motion sensor parameter windowsIG.16
Menu Function
Sensor
sensitivity
Default:
Maximum
It is used to increase or decrease the
sensitivity of PIR fixed in detector. The
sensitivity can be adjusted according to
user’s requirement no matter the detector is
master or slave.
Maximum
High
Medium
Low
OFF
Highest sensitivity.
Higher sensitivity.
Medium sensitivity.
Lowest sensitivity.
Deactivate the detecting
function of PIR.
LED turns on
when PIR is
triggered
Default:
Enable
It is used to set if switching on the LED for
indication when PIR is triggered.
Disable Waive the LED indicating
function when PIR is triggered.
But other LED indicating
functions are remained.
LED will turn on for 1sec for
indication when PIR is triggered.
Enable
In the parameter of the general windows can setup some
common functions.
Menu Function
The device
type is
Default:
Master
Input Slave
Default:
Light
output C1
Light
control
output C1
Default:
Enable
HVAC
control
output C3
Enable
Default:
HVAC
control
output C4
Disable
Default:
Alarm
function
Default:
Disable
The function of the detector is set as a master or
slave device
rDetector is set to: (Both master and slave detecto
are applied)
rWhen detector is enabled for maste
detector, all the functions are
workable, also can receive the
triggering signal from one or more
slave detectors. However, the signal
reception channel can be selected
refer to the requirement.
When detector is enabled for slave
detector, it is used exclusively to
extend the field of detection.
rPresence is transmitted to the Maste
for evaluation according to the set
parameters.
Set C1 - C4 to receive slave signal or not.
Light
output C1
Light
output C2
HVAC
output C3
HVAC
output C4
Assign channel to receive the signal
from slave detector. Please refer to
above mentioned section “Master/
slave” for detailed information.
When “Enable” the light control output C1, the
relevant setting interface is shown, otherwise it is
hidden.
When “Enable” the light control output C2, the
relevant setting interface is shown, otherwise it is
hidden.
When “Enable” the light control output C3, the
relevant setting interface is shown, otherwise it is
hidden.
When “Enable” the light control output C4, the
relevant setting interface is shown, otherwise it is
hidden.
When “Enable” the alarm function output, the
relevant setting interface is shown, otherwise it is
hidden.
Disable
Enable
Disable Light control output C1
interface functions;
Activate the Light control output C1
interface function;
Light
control
output C2
Default:
Disable
Disable
Enable
Disable HVAC control output C3
interface functions;
Activate the HVAC control output
C3 interface function;
Disable Alarm interface functions;
n;Activate the Alarm interface functio
Disable
Enable
Master
Slave
Disable
Enable
Disable Light control output C2
interface functions;
Activate the Light control output C2
interface function;
Disable
Enable
Disable HVAC control output C4
interface functions;
Activate the HVAC control output
C4 interface function;
1.4 Light control output C1 / C2 –Switching
F “Light control output C1 - Switching” parameter windowsIG.17
Menu Function
Lux / Time /
Sensitivity (Meter)/
STBY selected
by Default: ETS
Test mode
Default:
Disable
Sensor
sensitivity
Default:
Maximum
Test mode is activated after download the
program and exited automatically 10min
later, and then enters into auto mode or
semi-auto mode according to the setting
item of Auto-Semi-auto select”.
Disable
Enable
Test mode function is disabled.
Test mode function is activated.
Once the movement is detected,
both of load and LED will be
2sec on 2sec off.
When the control mode is set to
ETS, all the parameters on
detector can only be changed
by software ETS4 after
completing the object build up.
Also, the setting values on
detector set by IR KNX is
invalid.
When the control mode is set to
IR control, all the parameters
on detector can be changed by
IR KNX. Such as changing
the
delay off time value, switch
on
Lux value, etc.
ETS
IR
It is used to set the parameter of Lux, Time,
Sensitivity (Meter), STBY of detector is changed
by ETS software or IR remote control.
Note: It is valid only for C1 and C2.
It is used to increase or decrease the
sensitivity of PIR in detector. The sensitivity
can be adjusted according to user’s
rrequirement no matter the detector is maste
or slave.
Maximum
High
Medium
Low
OFF
Highest sensitivity.
Higher sensitivity.
Medium sensitivity.
Lowest sensitivity.
Deactivate the detecting
function of PIR.
Auto/
Semi-auto
select
Default: Auto
It is used to activate / deactivate Auto mode or
Semi-auto mode of Light control output C1.
Under auto mode, the load will turn
on automatically when 4 bit
movement is detected and the
ambient light level is below the Lux
setting value. When movement is no
longer detected and the delay time
has expired, the load will turn off
automatically.
Under semi-auto mode, load can
only be manually switched on by
operating the connected external
push button. When the load is
switched on, it will keep be on if the
movements are detected constantly.
Load will turn off only when
movement is no longer detected and
the delay time has expired.
Auto
Semi-
auto
Output type
Default:
Switching
eIt is used to set the output type of detector to b
Switching or Dimming.
Switching
Dimming
gSet the output type of C1 to switchin
so that it can connect the switching
actuator for ON/OFF operation.
Switch ON
Lux value
Default:
2000Lux
It is used to set sensor switch on Lux value, and
select the value via drop-down list.
Click the menu of Lux value in the
edit interface to set the desired
switch on Lux value for Light control
output C1.
Infinity: Uncontrolled by Lux value.
5Lux
~
2000Lux
Infinity
Lighting
delay time
Default: 5min 5sec
60min.
Click the menu of delay off time in
the edit interface to set the desired
value for Light control output C1.
It is used to set Auto off time,
value via drop-down list.
and select the
~
Menu Function
Set the output type of C1 to dimming
so that it can connect the dimming
actuator for the operation of output
with absolute brightness, standby
brightness and/or constant
brightness control.
LED turns on
when PIR is
triggered
Default: Enable
It is used to set if switching on the LED for
indication when PIR is triggered.
Disable Waive the LED indicating
function when PIR is triggered.
But other LED indicating
functions are remained.
LED will turn on for 1sec for
indication when PIR is triggered.
Enable
Menu Function
External switch
as ON / OFF /
Dim input
Default: NO
The Manual ON/OFF and DIM function is
operated by the switch built-in/connected
with KNX interface module on KNX bus
system.
NO
YES
Disable this feature.
Enable this feature.
1.8 HVAC control output C3 / C4
F “HVAC control output C3 parameter windowsIG.21
Constant
light control
Default:
Disable
It is used to activate or deactivate the constant
light control function.
Deactivate the lconstant light contro
function;
Activate the constant light control
function;
Disable
Enable
Preset
setpoint
Default:
300Lux
It is used to set the pre-set Lux value for constant
light control function and only can be set by
ETS.
The preset setpoint in Lux for
constant light control can be preset
by ETS.
Lux
deviation
Default:
10Lux
It is used to set the deviate value of constant
dimming function, that tis the detector will reac
refer to what the deviation of the ambient light
level is.
The deviation of dimming up / down
the ambient light level.
0 -
255Lux
Time after
switch-on
until constant
light control
starts
Default:
1min
1sec -
5min
It executes the standby time of
constant dimming, it is mainly used
to set rthe time of lighting from powe
on to stable.
It is used to set the standby time of starting to
execute the constant light control function rafte
the load is switched on.
Menu Function
10Lux -
2000Lux
Auto/
Semi-auto
select
Default:
Auto
It is used to activate / deactivate the auto /
semi-auto mode of HVAC control output C3.
Under auto mode, the load will turn
on automatically when 4 bit
movement is detected and the
ambient light level is below the Lux
setting value. When movement is no
longer detected and the delay time
has expired, the load will turn off
automatically.
Under semi-auto mode, load can
only be manually switched on by
operating the connected external
push button. When the load is
switched on, it will keep be on if the
movements are detected constantly.
Load will turn off only when
movement is no longer detected
and the delay time has expired.
Auto
Semi-
auto
Menu Function
Duration of
one
switch-on
window
Default:
0.3sec
It is used to set the time condition for the alarm to
be turned on.
It ris used to set the time condition fo
the alarm to be turned off.
0.3sec
to 1hr
Number of
switch-on
windows
Default:
10
It is used to set the number of times the object
moves within a certain period of time to turn on
the alarm.
It is used to set the number of times
the object moves within a certain
period of time to turn on the alarm.
Duration
of one
switch-off
window
Default:
0.3sec
Menu Function
0 - 100
0.3sec
to 1hr
It is used to set the time condition for the alarm to
be turned off.
It ris used to set the time condition fo
the alarm to be turned on.
Object 1:
“input:
Slave
input -
Slave
motion
Object Function
Object 2:
Output:
Slave
output
- Slave
motion
Description
Slave signal
input
When install the detector in a
large space, one or more slave
detectors can be parallelly
rconnected to the master detecto
eto enlarge the detection coverag
if one master detector can not
meet user’s requirement.
Slave signal
Output
mSend the detecting telegram fro
slave detector while set the
detector to Slave.
Object 3:
Output:
Test
output
- ON/OFF
Test mode
output
Used to check and adjust the
detection coverage while
installing the detector.
Object 5:
“input: C1
manual
input -
ON/OFF/
Dim
Channel 1 -
ON/OFF/Dim
manual control
Receive the telegram from the
push button (ON/OFF/Dim)
connected to the bus and control
channel 1.
Remark: The input can be
available on when setting
o“Reaction rising edge” t
on” and “Reaction on
falling edge” to “off .
Note: The ETS setting logic for C2 is same as it is for C1.