Foster Solo Plus Sercie Manual

Type
Sercie Manual

This manual is also suitable for

S e r v i c e M a n u a l
Solo Plus
Units 2001
PART 1A
Wall Mount Units
Ceiling Mounted Units
DIMENSIONS
Solo Plus DRWG 1 d + e
N
J
H
I
MODEL CONDENSER UNIT EVAPORATOR UNIT PLUG SIZE CUT-OUT SIZE
A x B x C (mm) G x E x F (mm) W x H (mm) W X H (mm)
H x J x K (mm) I x M x N (mm)
SP 1 HC 620 x 719 x 357 545 x 150 x 332 545 x 332 550 x 337
SP 2 H & LC 620 x 719 x 357 545 x 150 x 332 545 x 332 550 x 337
SP 3 H & LC 820 x 809 x 390 745 x 150 x 332 745 x 332 750 x 337
SP 4 HC 820 x 809 x 390 745 x 150 x 332 745 x 332 750 x 337
SP 4 LC 820 x 929 x 427 745 x 220 x 452 745 x 452 750 x 458
SP 5 HC 820 x 929 x 427 745 x 220 x 452 745 x 452 750 x 458
1
Mod. A B C D E F G
SP101LW, SP101HW
735 264 790 400 280 510 368
SP201HW, SP301HW
SP201LW, SP401HW
830 264 790 620 280 510 585
SP501HW
SP301LW, SP601HW 830 364 982 620 350 632 585
2
2. SOLO PLUS TECHNICAL DATA
Foster Nom. HP Cut Out HP Cut In Suction Valve Noise Heat Rejected RoomVent 32°C Ambient 43°C Ambient Air Air Vol Electrical Nominal Defrost Condensate Net Gross
Model No. HP Press Bar Press Bar Press Bar Level dBa Max Watts @ 32°C
m
3
/ h # Watts Room Cap Watts Room Cap Throw mts m
3
/ h
Volts
Phase
Hz
Amps Watts Type Vaporisation Wt. Kg Wt. Kg
NOTE: The condenser fan pressure stat fitted on Low Ambient units should be set at 17bar with a 1.5bar differential, this applies to high and low temperature models.
SP 101HW 0.375 28 23 ------ 58 1900 700 1300 11 1160 8 4 600 230 1 50 3.9 600 Hot Gas Auto 53 74
SP 201HW 0.5 28 23 ------ 60 2050 700 1450 13 1200 11 4 600 230 1 50 5.5 600 Hot Gas Auto 56 77
SP 301HW 0.75 28 23 ------ 60 2700 700 1800 16 1550 14 4 600 230 1 50 5.6 900 Hot Gas Auto 64 85
SP 401 HW 0.75 28 23 ------ 60 3650 1400 2550 25 2200 20 4 1200 230 1 50 7 1100 Hot Gas Auto 80 110
SP 501HW 1 28 23 ------ 62 5100 1400 3100 33 2700 27 4 1200 400 3 50 5.2 1800 Hot Gas Auto 80 110
SP 601HW 1.5 28 23 ------ 63 6900 1500 4700 58 4000 48 9.5 1800 400 3 50 5.9 2200 Hot Gas Auto 100 135
STORAGE TEMP +10°C
Foster Ref Qty Capillary Size
Model No. Gas Grms No. x Dia x Len
SP 101HW R404A 0.67 1 x 1.5 x 2500
SP 201HW R404A 0.67 1 x 1.5 x 2500
SP 301HW R404A 0.64 1 x 1.8 x 2000
SP 401HW R404A 1.10 1 x 2.0 x 2900
SP 501HW R404A 0.88 2 x 1.8 x 2500
SP 601HW R404A 1.11 2 x 2.0 x 2000
Foster Nom. HP Cut Out HP Cut In Suction Valve Noise Heat Rejected RoomVent 32°C Ambient 43°C Ambient Air Air Vol Electrical Nominal Defrost Condensate Net Gross
Model No. HP Press Bar Press Bar Press Bar Level dBa Max Watts @ 32°C
m
3
/ h # Watts Room Cap Watts Room Cap Throw mts m
3
/ h
Volts
Phase
Hz
Amps Watts Type Vaporisation Wt. Kg Wt. Kg
SP 101HW 0.375 28 23 ------ 58 1650 700 1050 7 900 6 4 600 230 1 50 3.9 600 Hot Gas Auto 53 74
SP 201HW 0.5 28 23 ------ 60 1756 700 1150 9 1050 7 4 600 230 1 50 5.5 600 Hot Gas Auto 56 77
SP 301HW 0.75 28 23 ------ 60 2356 700 1450 13 1300 10 4 600 230 1 50 5.6 900 Hot Gas Auto 64 85
SP 401 HW 0.75 28 23 ------ 60 3000 1400 1900 20 1600 14 4 1200 230 1 50 7 1100 Hot Gas Auto 80 110
SP 501HW 1 28 23 ------ 62 4500 1400 2700 30 2350 24 4 1200 400 3 50 5.2 1800 Hot Gas Auto 80 110
SP 601HW 1.5 28 23 ------ 63 6300 1500 4100 50 3300 35 9.5 1800 400 3 50 5.9 2200 Hot Gas Auto 100 135
Foster Nom. HP Cut Out HP Cut In Suction Valve Noise Heat Rejected RoomVent 32°C Ambient 43°C Ambient Air Air Vol Electrical Nominal Defrost Condensate Net Gross
Model No. HP Press Bar Press Bar Press Bar Level dBa Max Watts @ 32°C
m
3
/ h # Watts Room Cap Watts Room Cap Throw mts m
3
/ h
Volts
Phase
Hz
Amps Watts Type Vaporisation Wt. Kg Wt. Kg
SP 101HW 0.375 28 23 ------ 58 1450 700 850 6 750 5 4 600 230 1 50 3.9 600 Hot Gas Auto 53 74
SP 201HW 0.5 28 23 ------ 60 1550 700 950 7 850 6 4 600 230 1 50 5.5 600 Hot Gas Auto 56 77
SP 301HW 0.75 28 23 ------ 60 2100 700 1300 11 1200 9 4 600 230 1 50 5.6 900 Hot Gas Auto 64 85
SP 401 HW 0.75 28 23 ------ 60 2800 1400 1700 15 1400 11 4 1200 230 1 50 7 1100 Hot Gas Auto 80 110
SP 501HW 1 28 23 ------ 62 4100 1400 2300 21 2000 17 4 1200 400 3 50 5.2 1800 Hot Gas Auto 80 110
SP 601HW 1.5 28 23 ------ 63 5550 1500 3350 36 2800 26 9.5 1800 400 3 50 5.9 2200 Hot Gas Auto 100 135
Foster Nom. HP Cut Out HP Cut In Suction Valve Noise Heat Rejected RoomVent 32°C Ambient 43°C Ambient Air Air Vol Electrical Nominal Defrost Condensate Net Gross
Model No. HP Press Bar Press Bar Press Bar Level dBa Max Watts @ 32°C
m
3
/ h # Watts Room Cap Watts Room Cap Throw mts m
3
/ h
Volts
Phase
Hz
Amps Watts Type Vaporisation Wt. Kg Wt. Kg
SP 101LW 1.25 28 23 2.5 62 1950 700 1050 7 850 5 4 600 230 1 50 5.2 900 Hot Gas Auto 64 85
SP 201LW 1.5 28 23 2.5 63 3200 1400 1700 14 1400 10 4 1200 400 3 50 4.3 1500 Hot Gas Auto 80 110
SP 301LW 2.2 28 23 2.5 63 4440 1500 2700 28 2250 20 9.5 1800 400 3 50 4.5 1700 Hot Gas Auto 105 140
Foster Ref Qty Capillary Size
Model No. Gas Grms No. x Dia x Len
SP 101HW R404A 0.67 1 x 1.5 x 2500
SP 201HW R404A 0.67 1 x 1.5 x 2500
SP 301HW R404A 0.64 1 x 1.8 x 2000
SP 401HW R404A 1.10 1 x 2.0 x 2900
SP 501HW R404A 0.88 2 x 1.8 x 2500
SP 601HW R404A 1.11 2 x 2.0 x 2000
Foster Ref Qty Capillary Size
Model No. Gas Grms No. x Dia x Len
SP 101HW R404A 0.67 1 x 1.5 x 2500
SP 201HW R404A 0.67 1 x 1.5 x 2500
SP 301HW R404A 0.64 1 x 1.8 x 2000
SP 401HW R404A 1.10 1 x 2.0 x 2900
SP 501HW R404A 0.88 2 x 1.8 x 2500
SP 601HW R404A 1.11 2 x 2.0 x 2000
STORAGE TEMP +10°C STORAGE TEMP +1/4°C STORAGE TEMP 0/-2°C
STORAGE TEMP +1/4°C
STORAGE TEMP 0/-2°C
STORAGE TEMP -18/-21°C
Foster Ref Qty Capillary Size
Model No. Gas Grms No. x Dia x Len
SP 101LW R404A 0.53 1 x 1.5 x 2500
SP 201LW R404A 0.84 1 x 1.8 x 2500
SP 301LW R404A 1.13 2 x 1.6 x 2800
STORAGE TEMP -18/-21°C
3. ACCESS TO THE UNIT COMPARTMENT / EVAPORATOR HOUSING
WALL MODEL
Front Panel: Grasp each side of the front panel and “pull forward” releasing it from the spring clips located
down each edge,it may be necessary to separate the front panel from the main body using a flat
blade screwdriver and gently ease away.
Condenser Fan After removing the front panel “pull upwards” the fan housing assembly releasing it from
Assembly: the 4 “spring clips” located in each corner, it may be necessary to separate the fan housing
assembly from the main body using a flat blade screwdriver and gently ease away.
Evaporator Fan Remove the screw securing the drain tube to the drip tray and remover the drain tube.
Remove the four screws securing the drain pan and remove.
Remove the three remaining screws securing the side panel and remove it allowing access into
the evaporator fan assembly.
4. CONTROLLER OPERATION
DESCRIPTION OF ELECTRONIC PANEL
5
9
10
6
1
2
4
3
8
7
3
1) CONTROL LED (Green):
Lit: Compressor running, unit is refrigerating. FLASHING: Compressor is in start delay mode
(waiting for signal to start) OFF: Compressor is OFF. Room is down to set temperature.
2) CONTROL LED (Green):
LIT: Evaporator fan(s) running. FLASHING: Evaporator fan(s) in start delay mode (waiting for
signal to start ) OFF: Evaporator fan (s) OFF
3) Control LED (Yellow):
LIT: Unit in defrost mode (auto or manual)
Flashing Evaporator drip time with compressor and evaporator fan off.
4) ALARM LED (Red):
LIT: Alarm is active – see separate ALARMS section. OFF: Unit is functioning normally
5) DISPLAY:
When connected to the mains the display will read OFF indicating the condition of the unit. By
pressing the ON/OFF key for 3 seconds the unit will turn ON and display the room temperature.
During programming mode the various parameters will be displayed and during alarm mode an
alarm code will be displayed.
6) SET/ESC KEY:
Pressed for 3 seconds, the led is lit and setting of required room temperature is enabled. During
programming it is used to pass from a sub menu to an upper one.
7) DOWN/ ROOM LIGHT KEY:
During programming mode or setting of room temperature it serves to reduce the display value.
At other times it serves to control the room light.
8) DEFROST/ UP KEY:
By pressing for more than 4 seconds it activates a manual defrost. During programming mode or
setting of room temperature it serves to increase the displayed value.
9) ON/OFF KEY:
To turn the unit ON or OFF press and hold for more than 3 seconds.
10) ENTER KEY:
Permits access to the programming menu and passage to the sub menu. Access to this programming
mode should be by qualified persons only.
°C
4
5
6
7
8
CONTROLLER ALARMS AND FAULT FINDING.
When an alarm condition occurs the unit will display an alarm code ERR (this will differ according to the nature of
the alarm):
Alarm LED will illuminate (4)
Buzzer will sound (if remote alarm is fitted)
The alarm relay (for remote alarms) will be energised.
The pressing of any key will mute the alarm buzzer.
When the alarm is muted the LED will continue to flash for as long as the alarm condition persists.
To display the alarm code it is necessary to enter the alarm menu:
Press the ENTER key (10) for more than three seconds. FnC will be displayed. Press the DEFROST/UP key (8)
until AL is displayed and then press ENTER (10). At this point the alarm code will be displayed indicating the nature
of the alarm.
High Temperature Alarm (HI)
The red LED, buzzer and remote alarm relay are activated; the alarm code HI is displayed in the Alarm Menu.
The cause can be:
Product to warm
Excessive door openings
Excessive product load
Unit malfunction
Low Temperature Alarm (LI)
The red LED, buzzer and remote alarm relay are activated; the alarm code LI is displayed in the Alarm Menu.
The cause can be:
Malfunction of the electronic controller
High Pressure Alarm (EO)
Each time the pressure switch trips, the buzzer and red LED are activated. If more than ten trips occur during a
1-hour period then the unit will shut down automatically. The remote relay will be activated and the label
ERR will
flash on the display alternating with the room temperature. The alarm code EO is displayed in the Alarm Menu.
The cause can be:
Dirty condenser
Condenser fan not running
Front cover not fitted
Obstructed condenser air inlet
Obstructed condenser air outlet
Inadequate ventilation
Voltage Monitor Alarm (E8 – only when fitted as an option)
The optional voltage monitor is an electronic device that checks the units’ electrical supply. Should the voltage vary
by +/- 12% the unit will shut down for a period of 6 minutes (not adjustable) before attempting to re-start automatically
providing the voltage has returned to within limits. The red LED, buzzer and remote alarm relay are activated; the
label ERR will flash on the display alternating with the room temperature. The alarm code E8 is displayed in the
alarm menu.
WARNING: if the Voltage monitor is fitted it is important to note that on start up it has a time delay of seven minutes,
during this period the power should be on with the controller in the OFF position.
Room Sensor Fault (E1)
The red LED, buzzer and remote alarm relay are activated; the label ERR will flash on the display alternating with
the room temperature: alarm code E1 in the alarm menu.
Possible causes are:
Faulty room sensor.
Room sensor terminals badly connected.
9
Defrost sensor fault (E2)
The red LED, buzzer and remote alarm relay are activated; the label ERR will flash on the display alternating with
the room temperature: alarm code E2 in the alarm menu.
Possible causes are:
Faulty defrost sensor
Defrost sensor terminals badly connected.
Condenser Sensor Fault (4)
The red LED, buzzer and remote alarm relay are activated; the label
ERR will flash on the display alternating with
the room temperature: alarm code E4 in the alarm menu.
Possible causes are:
Faulty condenser sensor
Condenser sensor terminals badly connected.
Condenser Temperature Alarm (H4)
If the condensing temperature exceeds the factory pre set value (not adjustable) the red LED, buzzer and remote
alarm relay are activated: The alarm code H4 is displayed in the alarm menu.
Possible causes are:
Dirty condenser
Condenser fan not running
Front cover not fitted
Obstructed condenser air inlet
TROUBLE SHOOTING
1) Compressor stops. There is an internal over temperature device (Klixon) that stops the compressor each time the
admissible temperature of the motor windings is exceeded.
Possible causes are:
Insufficient ventilation to the compressor
Mains voltage anomaly
Faulty condenser fan
The device will re-set automatically when the windings cool down.
2) Formation of ice on evaporator coil impeding airflow.
Possible causes are:
Excessive door openings
Door left open for long periods
Evaporator fan/s faulty
Door switch faulty (if fitted)
Faulty defrost heater (if fitted)
Faulty hot gas solenoid valve (if fitted)
Pre set defrost routine not sufficient to clear evaporator of ice build up.
Decrease the time interval between defrosts.
3) Display does not illuminate.
Is their power to the unit?
Is the mains cable connected correctly?
Have the fuses in the electrical panel blown?
7. PARAMETER LIST
10
Medium Low
Label Description
Unit of
Range
Hot gas Hot gas
measure defrost defrost
dro Display Readout °C or °F ( 0=°C. 1=°F) Flag 0 or 1 0 0
CA1 Calibration of room sensor °C -12 to +12 0 0
Compressor rE1 menu. coP
diF Differential °C/1 2 2 2
HSE Maximum set point °C/1 LSE to 150 10 -15
LSE Minimum set point °C/1 -50 to HSE -5 -25
dbi Time delay between 2 compressor starts Minutes 0 to 15 2 2
dOF Time delay between compressor OFF and next start Minutes 0 to 15 2 2
Ont Compressor ON time if room sensor fails Minutes 0 to 250 10 10
OFt Compressor OFF time if room sensor fails Minutes 0 to 250 20 20
Defrost rE2 menu. dEF
dit Time interval between 2 defrosts Hour 0 to 31 3 3
dEt Defrost time override Minutes 1 to 250 20 20
dCt Defrost interval time count mode Number 0 to 3 0 0
0 = compressor run time
1 = unit run time
2 = each time compressor stops
3 = determined on a real time basis
dtY Defrost type selection Number 0 to 3 2 2
0 = Timed defrost
1 = Electric defrost
2 = hot gas
3 = Off cycle
dt Drain down time Minutes 0 to 250 2 2
dSt Defrost termination temperature °C/1 -50 to 150 15 15
Evaporator Fans rE3 menu. FAn
Fdt Fan delay time Minutes 0 to 15 3 3
FCO Evaporator fan/s run with compressor Flag n / y n n
dFd Fan/s stops during defrost Flag n / y y y
Fod Fan/s off when door opened Flag on/off on on
FSt Fan stop temperature °C/1 -50 to 150 50 50
Room Light rE4 menu. LUc
No parameters
Temperature Alarms rE5 menu. ALP
LAL Low temperature alarm °C/1 -50 to HAL -5 -5
HAL High temperature alarm °C/1 LAL to 150 5 5
AFd Alarm differential °C/1 -12 to 12 2 2
PAO Alarm delay after start-up Hour 0 to 10 3 6
dAo Alarm delay after defrost Minutes 0 to 250 60 60
OAO Alarm delay after door opening Hour 0 to 10 1 1
Pressure alarms rE6 menu. PP
PEi Time period for pressure trips Minutes 1 to 99 60 60
Pen Numbers of pressure trips Number 0 to 15 10 10
Condensing temperature alarms rE7 menu. ALP
HAL Maximum condensing temperature alarm setpoint °C/1 0 to 99 55 55
AFd Alarm differential °C/1 -12 to 12 2 2
Fig 1.
8. ELECTRICAL CONNECTIONS
The unit operates from a 220/240v1-50hz or a 400v- 3-50hz electrical supply as denoted in the technical data.
For 60hz application consult Foster.
The selection of mains cable depends on the unit (Amps) and on the siting of the cable itself.
The installer will therefore evaluate the most suitable one on a case by case basis.
The table below gives a rough sizing and should be used as a guide only
Unit Amps Cable diameter
Up to 12 Amps 1.5mm
2
12 to 17 Amps 2.5mm
2
Over 17 Amps 4mm
2
Remove the front panel of the unit and connect the cables to the terminal box as per the diagrams in fig 1,2,3 and 4.
11
Single Phase Unit
L1 – Brown
N – Blue
PE – yellow / green
BR BL YG
L 1
L 1
N
N
PE
Mains Supply Cable
230V/ three phase unit without neutral.
L1 – Brown L2 Black
L3 – Blue
PE – yellow / green
BR BLK BL YG
L 2
L 2
L 3
L 3
N
N
Mains Supply Cable
Fig 2.
PE
PE
400V/ three phase unit with neutral.
L1 – Brown L2 Black
N – Blue L3 Black
PE – yellow / green
BR BLK BLK BL YG
L 2
L 2
L 3
L 3
N
N
Mains Supply Cable
Fig 3.
PE
PE
L 1
L 1
L 1
L 1
Connections for options
1 = Brown 5 = Brown
2 = Blue 6 = Blue
3 = Brown
4 = Blue
= yellow/green
BR BL BR BL GV BR BL
Fig 4.
6
6
Door Heater
Remote Alarm Cable
5
5
1
1
2
2
3
3
4
4
Door Microswitch
PE
9. PROBE RESISTANCE VALUES
The air and defrost probes have the following temperature resistance values (K ohms)
Temperature Kohms Temperature Kohms
+50°C 4,161 0°C 27,280
+40°C 5,828 -10°C 42,450
+30°C 8,313 -20°C 67,740
+20°C 12,090 -30°C 111,300
+10°C 17,960 -40°C 188,400
10. FUSE RATINGS
NOTE: LA refers to Low Ambient Models
FOSTER CODE Internal fuse Wiring diagram
SP101HW 16 A J1018
SP201HW 16 A J1018
SP301HW 20 A J1018
SP401HW 25 A J1018
SP501HW No fuses J2020
SP601HW No fuses J2019
SP101LW 20 A J1018
SP201LW No fuses J2019
SP301LW No fuses J2019
SP101HW LA 16 A J1019
SP201HW LA 16 A J1019
SP301HW LA 20 A J1019
SP401HW LA 25 A J1019
SP501HW LA No fuses J2021
SP601HW LA No fuses J2022
SP101LW LA 20 A J1019
SP201LW LA No fuses J2022
SP301LW LA No fuses J2022
12
11. WIRING DIAGRAMS
ROOM SENSOR
CONDENSER ALARM SENSOR
DEFROST SENSOR
SPEED REGULATOR
SPEED REGULATOR SENSOR
DEFROST HEATER
RESISTENZA CARTER COMPRESSORE
COMPRESSOR CRANKCASE HEATER
DOOR HEATER CIRCUIT
CONTROL BOARD HEATER
VOLTAGE REGULATOR HEATER
CONDENSATE DRAIN HEATER
VOLTAGE REGULATOR FUSE
COMPRESSOR FUSE
ELECTRONIC CONTROL CAB
AUXILIARY FUSE
ROOM LIGHT FUSE
VOLTAGE REGULATOR
13
BA
BC
BS
BVR
BVRS
E
E1
M1
EP
ER1
ER2
ES
F13
F1
F1E
FL
F20
FM
EMERGENCY ‘STAT
ALARM
CONTACTOR
DEFROST CONTACTOR
COMPRESSOR MOTOR Nr.1
DOOR MICROSWITCH(ROOM)
CONDENSER FAN MOTOR
EVAPORATOR FAN MOTOR
COND. FAN STARTING PRESSURE SWITCH
L/P SWITCH
H/P SWITCH
MAIN SWITCH
COND. FAN SPEED REGULATOR
“OFF” SWITCH
TRANSFORMER
TERMINAL BOARD-CONNECTOR
REFRIGERANT SOLENOID
HOT GAS SOLENOID
FTE
HI
K1
K11
M1
MPC
MVC
MVE
P1MX
PMI
PMX
Q1
Q3
T
X
YS
YG
COMPONENT IDENTIFICATION
14
SUPPLY
400V/3N-/50Hz
Colour Code
MA - BROWN
BL - BLUE
GV - GREEN/YELLOW
NE - BLACK
Drawing No. Sheet No.
J2020 1 of 1
Drawn By Approved Date
Title
SP501HW
FOSTER REFRIGERATOR - A Division of ITW
Ltd.
15
LOW TEMP ONLY
SUPPLY
230-220V/1N-/50Hz
Colour Code
MA - BROWN
BL - BLUE
GV - GREEN/YELLOW
NE - BLACK
Drawing No. Sheet No.
J1018 1 of 1
Drawn By Approved Date
Title
SP101LW
SP101HW
SP201HW
SP301HW
FOSTER REFRIGERATOR - A Division of ITW
Ltd.
SP101LW
SPE
16
SUPPLY
400V/3N-/50Hz
Colour Code
MA - BROWN
BL - BLUE
GV - GREEN/YELLOW
NE - BLACK
Drawing No. Sheet No.
J2019 1 of 1
Drawn By Approved Date
Title
SP201LW
SP301LW
SP601HW
FOSTER REFRIGERATOR - A Division of ITW
Ltd.
PART 1B
Ceiling Mounted Solo January 2003 Controller Settings
Dimensions
Description
1. Condensing unit and Evaporator (evaporator plaed in an insulated box) located outside of the coldroom.
2. Air inlet and outlet to the evaporator located inside the coldroom.
3. Electrical control panel located in the condensing unit enclosure.
4. Wall mounted control panel.
A B C D E F G H I L M X Y
SP1/SP2 357 250 719 340 122 28 332 506 60 620 545 337 550
SP3/SP4 390 250 809 360 122 28 332 540 60 820 745 337 750
SP5 427 250 929 410 122 98 452 645 60 820 745 458 750
17
WALL MOUNT SOLO PLUS TECHNICAL DATA
Foster Nom. HP Cut Out HP Cut In Suction Valve Noise Heat Rejected RoomVent 32°C Ambient 43°C Ambient Air Air Vol Electrical Nominal Defrost Condensate Net Gross
Model No. HP Press Bar Press Bar Press Bar Level dBa Max Watts @ 32°C
m
3
/ h # Watts Room Cap Watts Room Cap Throw mts m
3
/ h
Volts
Phase
Hz
Amps Watts Type Vaporisation Wt. Kg Wt. Kg
NOTE: Noise levels taken in a room with a concrete floor, no sound attenuation and ceiling height of 7 metres with the unit base 1.5 metres from floor level, installed in a coldroom and the Sound Metre 3 metres distance.
SP 1HC 0.625 28 23 ———- 59 2300 750 1550 10 1400 7 3 550 230 1 50 4.4 700 Hot Gas Auto 59 90
SP 2HC 0.75 28 23 ———- 60 2675 750 1750 12 1600 10 3 550 230 1 50 5.2 800 Hot Gas Auto 59 90
SP 3HC 1 28 23 ———- 60 3750 1400 2600 20 2200 16 3.5 1100 230 1 50 6.9 1100 Hot Gas Auto 74 114
SP 4HC 1.2 28 23 ———- 60 4200 1400 2900 28 2700 22 3.5 1100 400 3 50 4.4 1500 Hot Gas Auto 75 115
SP 5HC 2 28 23 ———- 63 7200 5200 5200 56 4600 48 6 2300 400 3 50 5.1 2100 Hot Gas Auto 93 139
STORAGE TEMP +10°C
Foster Ref Qty Capillary Size
Model No. Gas Grms No. x Dia x Len
SP 1HC R404A 0.54 1 x 1.63 x 2200
SP 2HC R404A 0.60 1 x 1.83 x 3100
SP 3HC R404A 0.73 2 x 1.38 x 3100
SP 4HC R404A 0.70 2 x 1.98 x 2900
SP 5HC R404A 1.10 2 x 1.98 x 2000
Foster Nom. HP Cut Out HP Cut In Suction Valve Noise Heat Rejected RoomVent 32°C Ambient 43°C Ambient Air Air Vol Electrical Nominal Defrost Condensate Net Gross
Model No. HP Press Bar Press Bar Press Bar Level dBa Max Watts @ 32°C
m
3
/ h # Watts Room Cap Watts Room Cap Throw mts m
3
/ h
Volts
Phase
Hz
Amps Watts Type Vaporisation Wt. Kg Wt. Kg
SP 1HC 0.625 28 23 ———- 59 1950 750 1150 7 1050 6 3 550 230 1 50 4.4 700 Hot Gas Auto 59 90
SP 2HC 0.75 28 23 ———- 60 2200 750 1350 9 1250 6 3 550 230 1 50 5.2 800 Hot Gas Auto 59 90
SP 3HC 1 28 23 ———- 60 2850 1400 1900 17 1600 10 3.5 1100 230 1 50 6.9 1100 Hot Gas Auto 74 114
SP 4HC 1.2 28 23 ———- 60 3350 1400 2300 20 2050 12 3.5 1100 400 3 50 4.4 1500 Hot Gas Auto 75 115
SP 5HC 2 28 23 ———- 63 5700 1500 4100 46 3600 28 6 2300 400 3 50 5.1 2100 Hot Gas Auto 93 139
Foster Nom. HP Cut Out HP Cut In Suction Valve Noise Heat Rejected RoomVent 32°C Ambient 43°C Ambient Air Air Vol Electrical Nominal Defrost Condensate Net Gross
Model No. HP Press Bar Press Bar Press Bar Level dBa Max Watts @ 32°C
m
3
/ h # Watts Room Cap Watts Room Cap Throw mts m
3
/ h
Volts
Phase
Hz
Amps Watts Type Vaporisation Wt. Kg Wt. Kg
SP 1HC 0.625 28 23 ———- 59 1750 750 1050 6 925 4 3 550 230 1 50 4.4 700 Hot Gas Auto 59 90
SP 2HC 0.75 28 23 ———- 60 2000 750 1200 7 1100 5 3 550 230 1 50 5.2 800 Hot Gas Auto 59 90
SP 3HC 1 28 23 ———- 60 2650 1400 1700 12 1450 9 3.5 1100 230 1 50 6.9 1100 Hot Gas Auto 74 114
SP 4HC 1.2 28 23 ———- 60 3150 1400 2000 15 1700 12 3.5 1100 400 3 50 4.4 1500 Hot Gas Auto 75 115
SP 5HC 2 28 23 ———- 63 5100 1500 3600 36 3200 17 6 2300 400 3 50 5.1 2100 Hot Gas Auto 93 139
Foster Nom. HP Cut Out HP Cut In Suction Valve Noise Heat Rejected RoomVent 32°C Ambient 43°C Ambient Air Air Vol Electrical Nominal Defrost Condensate Net Gross
Model No. HP Press Bar Press Bar Press Bar Level dBa Max Watts @ 32°C
m
3
/ h # Watts Room Cap Watts Room Cap Throw mts m
3
/ h
Volts
Phase
Hz
Amps Watts Type Vaporisation Wt. Kg Wt. Kg
SP 2LC 1.7 28 23 3 60 2050 750 1200 6 1050 3 3 550 230 1 50 5.9 900 Hot Gas Auto 68 99
SP 3LC 2 28 23 3 61 2850 1400 1650 11 1400 7 3.5 1100 400 3 50 4.2 1400 Hot Gas Auto 87 118
SP 4LC 3 28 23 3 63 5000 1400 2400 18 220 13.5 6 2300 400 3 50 4.6 1800 Hot Gas Auto 102 142
Foster Ref Qty Capillary Size
Model No. Gas Grms No. x Dia x Len
SP 1HC R404A 0.54 1 x 1.63 x 2200
SP 2HC R404A 0.60 1 x 1.83 x 3100
SP 3HC R404A 0.73 2 x 1.38 x 3100
SP 4HC R404A 0.70 2 x 1.98 x 2900
SP 5HC R404A 1.10 2 x 1.98 x 2000
Foster Ref Qty Capillary Size
Model No. Gas Grms No. x Dia x Len
SP 1HC R404A 0.54 1 x 1.63 x 2200
SP 2HC R404A 0.60 1 x 1.83 x 3100
SP 3HC R404A 0.73 2 x 1.38 x 3100
SP 4HC R404A 0.70 2 x 1.98 x 2900
SP 5HC R404A 1.10 2 x 1.98 x 2000
STORAGE TEMP +10°C STORAGE TEMP +1/4°C STORAGE TEMP 0/-2°C
STORAGE TEMP +1/4°C
STORAGE TEMP 0/-2°C
STORAGE TEMP -18/-21°C
Foster Ref Qty Capillary Size
Model No. Gas Grms No. x Dia x Len
SP 1LC R404A 0.42 1 x 1.49 x 1900
SP 2LC R404A 0.72 1 x 1.98 x 3000
SP 3LC R404A 0.96 2 x 1.63 x 2900
STORAGE TEMP -18/-21°C
18
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53

Foster Solo Plus Sercie Manual

Type
Sercie Manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI