  • I have reviewed the installation instructions for the Siemens D2300-MP, D2300CP, PS-5A, D2300CPS and D2325CPS modules. This document provides information on mounting the modules within a FireFinder XLS CAB enclosure. It also includes important warnings about the voltage requirements for the D2300CPS and D2325CPS modules. I am ready to answer your questions about the installation and specifications of these devices.
  • What is the purpose of the D2300-MP?
    Are D2300CPS and D2325CPS modules compatible with D2300CP?
    What voltage do the D2300CPS and D2325CPS modules use?
P/N 315-034758-3
Installation Instructions
Model D2300-MP
Fiber Optic Interface Mounting Plate
INTRODUCTION
The Model D2300-MP from Siemens Industry, Inc., is a
bracket for mounting up to two D2300CP modules and
a PS-5A, two D2300CPS or two D2325CPS modules in
any FireFinder XLS CAB enclosure. The D2300-MP fits
in the same footprint as a CC-5 and mounts directly into
the CAB enclosure or to the optional CAB-MP. A hard-
ware kit is provided for attaching the D2300-MP to the
CAB enclosure or the CAB-MP and for mounting two
D2300CP and one PS-5A, two D2300CPS or two
D2325CPS modules onto the D2300-MP.
WARNING: The D2300CPS and D2325CPS modules
are NOT backwards compatible with the existing
D2300CP. The D2300CPS and D2325CPS use
+24VDC. Make sure to read the front of the module
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
Figure 1
Mounting the D2300CP/D2300CPS/D2325CPS in a CAB-1 Backbox
DATAPXTMR
DATAPXTMR
POWER
B
A
DATAPREC
DATAPREC
D2300CP/
D2300CPS/
D2325CPS
D2300-MP
PS-5A
(for D2300CP only)
DATAPXTMR
DATAPXTMR
POWER
B
A
DATAPREC
DATAPREC
D2300CP/
D2300CPS/
D2325CPS
D2300-MP
DATAPXTMR
DATAPXTMR
POWER
B
A
DATAPREC
DATAPREC
D2300CP/
D2300CPS/
D2325CPS
PS-5A
(for D2300CP only)
and connect to the correct voltage. Otherwise, seri-
ous damage to the unit will result.
Mount the D2300CP and PS-5A /D2300CPS/D2325CPS
modules prior to installing the D2300-MP onto the CAB
enclosure or the CAB-MP. Note that when using two
D2300CP/D2300CPS/D2325CPS modules, the center
two mounting holes on each D2300CP/D2300CPS/
D2325CPS share the two center slots on the D2300-MP
(See Figure 1). For additional information refer to the
D2300CP Installation Instructions, P/N 315-092882, the
D2300CPS Installation Instructions, P/N 315-050018,
or the D2325CPS Installation Instructions, P/N 315-050019,
as applicable.